Search NASA⌕ Search

Engineering topics

Tuffner, Francis K.

Publications and source records attributed to Tuffner, Francis K..

At least 37 records · Page 2

Simultaneous Forward-Backward Prony Estimation

Power system dynamic stability can be evaluated through the analysis of transient oscillations that occur following significant system events. One of the earliest methods for this type of study is Prony analysis, which estimates the system's electromechanical modes. While previous studies have highlighted advantages of performing Prony analysis on data in the forward and backward directions, the proposed method does so simultaneously. As a result, signal poles corresponding to electromechanical modes can be distinguished from spurious poles more reliably. The method also produces a single mode estimate, where independent application in the forward and backward directions would produce two estimates for each mode. The method is validated using simulated and measured power system data.

Follum, James D.↗

Using Distributed Dynamic Voltage Restorers to Improve the Frequency Stability of Low-Inertia Networked Microgrids

This paper elucidates the novel concept of using distributed dynamic voltage restorers (DVRs), which are traditionally used to compensate for voltage sags, to improve the frequency stability of low-inertia networked microgrids. During frequency transients, the distributed DVRs rapidly regulate load voltages within an acceptable range, resulting in a fast change of load power consumption and helping improve frequency stability. To enable large-scale network simulation, a phasor-based model of DVRs is developed and validated against real data from a commercially available device. Finally, simulation results of a modified IEEE 123-node test feeder that comprises three microgrids and six DVRs verify the effectiveness of the proposed method.

Du, Wei↗

Applying Utility's Advanced Grid Technologies to Improve Resiliency of a Critical Load

The US DOE Office of Electricity's Energy Storage Program's joint R&D work with the Cordova Electric Cooperative (CEC) has deployed several advanced grid technologies that are providing benefits today to Cordova Alaska's electricity users. Advanced grid technologies deployed through DoE co-funded R&D include a 1MW Battery Energy Storage System (BESS), and enhanced monitoring including Phasor Measurement Units (PMU's) to help better understand the operational impacts of the added BESS. This paper will highlight key accomplishments to-date in deploying and using advanced grid technologies, and then outline the next phase of work that will use these technologies to implement an operating scheme to reconfigure the utility's distribution system and utility resources including BESS to provide emergency back-up power to a critical load: the Cordova Community Medical Center (CCMC). This paper will include additional insights on the use of utility resources to support critical loads via case study examples by the National Rural Electric Cooperative Assoc. (NRECA).

BESS↗

Critical values of cyber parameters in a dynamic microgrid system

An islanded microgrid can be used to serve critcal load as a resiliency source when a severe outage occurs. In an islanded mode, control of a microgrid relies on the communication system significantly. Hence, microgrids are cyberphysical systems and, therefore, the cyber system plays a crucial role in the performance of the cyber-power system. A microgrid control scheme is proposed for power dispatch and regulation based on the droop and proportional-integral (PI) feedback control. The proposed control strategy is validated for transient stability following dynamic events. To evaluate the impact of a networked control system on control performance, a cyber model is developed to represent data acquisition periods and communication delays. An analytical method is proposed to determine the critical values for the data reporting periods and communication delays. The analytical method based on a state space model of a networked control system is applicable for large-scale systems. A 2-dimensional stability region of a microgrid in the space of cyber parameters can be obtained by the proposed method, and the critical values of cyber parameters are determined based on the stability region. Simulation results validate that the design of a microgrid as a cyber-physical system needs to be guided by critical values for the data reporting period and communication delay to prevent system instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Energy Sector Position, Navigation, and Time Cybersecurity Profile

The Pacific Northwest National Laboratory has developed this positioning, navigation, and timing (PNT) profile for the Energy Sector at the request of the U.S. Department of Energy. The Department of Energy is the sector-specific agency for the Energy Sector and is responsible for providing guidance in the form of this PNT Profile, per Executive Order 13905, Strengthening National Resilience Through Responsible Use of Positioning, Navigation, and Timing Services (Executive Office of the President 2020) issued February 18, 2020. Executive Order 13905 directed the National Institute of Standards & Technology to develop a PNT Profile that is broadly applicable to all sectors and to serve as a foundation for sector-neutral guidance, NISTIR 8323 Foundational PNT Profile: Applying the Cybersecurity Framework for the Responsible Use of Positioning, Navigation, and Timing (PNT) Services. This document builds on NISTIR 8323 to identify and serve as the required Energy Sector specific guidance. For purposes of this PNT Profile, Energy Sector precise time is 0.5 µs (microseconds) to 1 µs accuracy. Currently, the electricity subsector has systems that use this level of precision time, but the oil and natural gas subsector currently does not. While the electricity subsector uses precision timing, it does not use positioning and/or navigation at this level of accuracy. For this reason, this PNT Profile will focus on only precise time for the electricity subsector.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Study of microgrid resilience through co-simulation of power system dynamics and communication systems

The interdependence of power and communication systems in smart grid technologies is acknowledged, but difficult to quantify. Communication systems can be essential to maintaining stability in microgrids that are islanded due to extreme events. Though many power system studies assume the presence of communication networks, detailed modeling of power and communication systems for dynamic studies of microgrids is rare. The work presented in this paper develops a framework for power and communication system co-simulation to study the impact of communications system on microgrid stability. An operational use case is examined where a battery energy storage system operates to offset the loss of generation in an islanded microgrid. The framework is evaluated for different communication technologies, network structures, and communication media.

Thekkumparambath Mana, Priya↗

Comparison of Electromagnetic Transient and Phasor-based Simulation for the Stability of Grid-Forming-Inverter-based Microgrids

The increasing interest in studying feeder-level, inverter-based microgrids requires appropriate simulation methods that can effectively simulate the dynamics of distribution feeders that typically have thousands of nodes. To examine the accuracy of phasor-based simulation for the stability of feeder-level, inverter-based microgrids, a comparative study between electromagnetic transient (EMT) and phasor-based simulation was conducted. Case studies of a two-inverter small microgrid and a modified version of the IEEE 34-Node Test System that has seven grid-forming inverters show that phasor-based simulation agrees well with EMT simulation when the P-f droop gains of grid-forming inverter controllers are within normal ranges. However, under extremely high P-f droop gains, phasor-based simulation can result in over-optimistic stability results. This study provides insight into the applicability of phasor-based simulation for the stability of feeder-level, inverter-based microgrids.

Du, Wei↗

Modeling and Simulation of Inrush Currents in Harmonic Domain

Modeling and simulation capabilities are critical to the stability analysis and evaluation of power distribution systems, with respect to the emphasis on resiliency, microgrids, and distributed energy resources. In this paper, a computational method in the harmonic domain is proposed for the periodic steady-state analysis of the nonlinear inrush current phenomenon. The efficient inrush calculation facilitates the predictions of current amplitudes for the power system operation and control. To demonstrate the accuracy and efficiency, simulation results in the harmonic domain are compared with results from PSCAD in an electromagnetic timescale, as well as the authors’ previous works in the frequency-domain. Impacts of the settings of both offset flux and interested harmonic order are discussed. In addition, within the proposed harmonic-domain method, a general approach that utilizes the discrete Fourier transform to obtain the response of a nonlinear device from a stimulus represented in the frequency-domain is utilized. This method can also be extended to perform the transient analysis in future, using trapezoidal rule for the integration.

Xie, Jing↗

Dynamic-Phasor Model of Transformer Inrush Simulation for Unbalanced Distribution System

Abstract— Power system stability is a critical concern, with respect to the increasing distributed energy resources, microgrids, and emphasis on enhancing resiliency. For stability analysis and evaluation, modeling and simulation capabilities are important. In this paper, the authors’ previous work on modeling transformer inrush dynamics is improved with a new formulation of the key equation that converts the dynamic-phasor into real-time value. Simulation results in an electromechanical time-scale are compared with PSCAD results in an electromagnetic time-scale to demonstrate the improvement. The impact of simulation step size is discussed. A bug in PSCAD transformer setting that leads to incorrect magnetizing flux and current under Delta winding type is identified and reported. In addition, explanations and analysis are provided on two modeling techniques utilized since the previous work. This work is being incorporated into the next release of GridLAB-D. The improved transformer inrush calculation enables more accurate predictions of current amplitudes for analyzing the dynamics of distribution operation and control.

power transformers, power system simulation, satur↗

Detecting and Analyzing Power System Disturbances in PMU Data with the Open-Source Archive Walker Tool

As the number of Phasor Measurement Units (PMUs) deployed in power systems increases, so do the archives of synchrophasor measurements stored by utilities. Significant value can be extracted from these archives by using them to support studies such as frequency response analysis, small-signal stability analysis, and power plant model validation. To better enable utilities to perform these studies, the open-source Archive Walker tool was developed. This tool examines PMU data for grid disturbances and periods of interest. Once identified, the data can be further analyzed inside Archive Walker or exported to specialty tools. In this paper, the various disturbance detectors available in Archive Walker are described, and its interactions with other openly-available tools are highlighted.

Follum, James D.↗

Dynamics and Control of Microgrids as a Resiliency Source

Microgrids can be operated in a utility-connected mode with the neighboring distribution system or in an islanded mode in separation with the distribution system. As the major disasters occur more and more often, islanded microgrid is proposed as a possible solution to serve essential loads until the utility service is restored. This paper evaluates the feasibility of using microgrids as a resiliency resource by a field test. A control scheme, integrating droop control and feedback control, is applied on a modified IEEE 13-node test feeders. The simulation results validate the proposed control scheme and the transient stability

Lee, Lung-An↗

Learning-Based Load Control to Support Resilient Networked Microgrid Operations

Microgrids have proven to be an effective option for increasing the resiliency of critical end-use loads during extreme events. Building on past operational experiences, some microgrid operators are examining the potential to network microgrids to further improve resiliency. However, the frequency deviations experienced on isolated microgrids during transient events, such as switching operations, step increases in load, and loss of generation, are significantly larger than those typically seen on bulk transmission systems. The larger frequency deviations can cause a loss of inverter-connected assets, resulting in a loss of power to critical end-use loads. This paper presents a method of mitigating the impact of transient events by engaging end-use loads using Grid-Friendly Appliance TM (GFA) controllers. An online, i.e., real-time, device-level algorithm is presented, which adjusts individual GFA controller frequency set-points based on the operational characteristics of each end-use load, and on the changing grid dynamic characteristics. The presented method improves the dynamic stability of the networked microgrid operations while minimizing the interruptions to end-use loads. The presented work is validated with dynamic simulations using a modified version of the IEEE 123-node test system with three microgrids, using the GridLAB-D TM simulation environment.

Radhakrishnan, Nikitha↗

Grid stabilization using adjusted voltage regulator response to grid characteristics

Apparatus and methods are disclosed for control systems for improving stability of electrical grids by temporarily reducing voltage output of electrical generators responsive to transient events on an electrical grid. In one example of the disclosed technology, a controller is coupled is to an automatic voltage regulator, which in turn adjusts excitation current of an electrical generator responsive to changes in frequency detected for the electrical grid. Reducing the output voltage temporarily allows for smaller generators to provide power to the microgrid. Methods for selecting parameters determining how the controller generates a regulation signal used to adjust the excitation current are further disclosed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Calibrating Synchronous-Generator-Interfaced DG Models in Microgrids Using Multiple Event Data

Microgrids, consisting of distributed generators (DGs), loads, and energy storage systems, play an important role in future smart grids. In order to evaluate how microgrids operate and their dynamic response, it is necessary to develop accurate dynamic models of DGs in microgrids. This paper proposes a systematic method to calibrate synchronous-generator-interfaced DG models. Challenges associated with model validation in microgrids are analyzed. Underlying parameters are categorized into two groups, i.e., the steady-state parameters and time constants, which are estimated in two successive stages using multiple event data. This methodology ensures that the validated model with the estimated parameters are applicable for all events. A modified unscented Kalman filter (UKF) is proposed to deal with the cases in which measurement of power angle is unavailable. The effectiveness of the proposed method is validated using field test data of a 2.6 MVA diesel generator in a real microgrid.

Wang, Zhiwen↗

Open Source Suite for Advanced Synchrophasor Analysis

The report presents the results of the development of the open-source suite of applications for synchrophasor analysis. The suite includes several software tools for oscillation analysis, power plant model validation, and frequency response analysis using synchrophasor measurements. All tools are based on the common framework and data sources. The developed tools have been used by different electrical utilities for synchrophasor analysis. The report includes several use cases based on the actual system PMU data.

20 FOSSIL-FUELED POWER PLANTS↗

Modeling of Grid-Forming and Grid-Following Inverters for Dynamic Simulation of Large-Scale Distribution Systems

Historically, distribution system planning studies mainly focused on steady state and quasi-steady state analysis, with limited attention paid to dynamic analysis. This paper develops three-phase, electromechanical models for both grid-forming and grid-following inverters, and integrates them into an open source, three-phase distribution network solver, thereby enabling dynamic simulation of large-scale, three-phase unbalanced distribution systems with high penetration of inverter-based DERs. The proposed inverter models are validated against electromagnetic simulation and field test data from the CERTS/AEP microgrid testbed, and simulated in an islanded 5252 node distribution system in the GridLAB-D simulation environment. Simulation verifies the effectiveness of the proposed inverter models for large-scale distribution system analysis. Finally, study results show that compared to traditional grid-following inverters, the high penetration of grid-forming inverters can improve the voltage and frequency stability of islanded distribution systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗