Search NASA⌕ Search

Engineering topics

You, Shutang

Publications and source records attributed to You, Shutang.

At least 19 records

Ambient-Frequency-Data Based System-Level Inertia Estimation Using Physical Equation and its Practice on Hawaii Islands

Here, in this paper, a practical ambient-frequency-data-based inertia estimation method using a physical equation is proposed and validated by real measurement data from Hawaii island grids. With high renewable penetration, accurate inertia estimation is important and urgent. Ambient frequency oscillation always exists in power grids, so the proposed method has advantages of real-time inertia estimation and no need for additional disturbances. This paper first developed the physical equation for inertia estimation to offer a clear mechanism for easy implementation in practice. To apply the proposed method in actual grids, a practical method to extract the ambient frequency oscillation from frequency measurement is further proposed. The inertia estimation using the physical equation is validated by KIUC simulation data and HECO field data, in which error rates are around 2% and 8%, respectively. Practical inertia estimation is challenging due to the large amounts of resources contributing to the power grid's effective inertia, but the method provided in this paper can offer a novel way for practical inertia estimation, which can help renewable penetration to boost carbon-free grid.

14 SOLAR ENERGY↗

Neural Networks-Based Inverter Control: Modeling and Adaptive Optimization for Smart Distribution Networks

The optimal voltage control of inverter-based resources, especially under the high penetration of solar photovoltaics, is critical to the stability of the distribution power system. However, the computational complexity as well as the coordinated operation performance of the voltage control optimization in the distribution power system limits the real-time applications. To mitigate this issue, a model-free based adaptive optimal control scheme for the smart inverter is proposed to maximize the active power generation, minimize the power loss, and maintain the bus voltages in smart distribution networks. An inverter-based optimization model for coordinated operation is first established, considering the uncertainties of renewable power generation. Subsequently, by collecting the data and control strategies, the neural networks (NNs) based algorithm is proposed to efficiently predict the best possible control strategy. The main objective of this scheme is to accurately predict candidate optimal solutions with near-negligible feasibility and optimization gaps, with the advantage of avoiding complicated iteration-based numerical algorithms. Thereafter, the co-simulation among OpenDSS, MATLAB, and Python is set up to fully take advantage of the three individual software. Experiments are conducted based on different control parameter characteristics and structures of NNs. Finally, the results reveal that an average mean squared error of 0.013 and 1 ms response time are achieved, which is lower than some state-of-the-art methods.

42 ENGINEERING↗

Field Measurement and Analysis of Frequency and RoCoF for Low-Inertia Power Systems

The frequency measurement and rate of change of frequency (RoCoF) calculations are important for active power, frequency control, and frequency-related protection in power system operations. With the rapid decrease in inertia under modern power systems, however, multiple power variations introduced by variable renewable energy bring large RoCoF and introduce oscillations in frequency measurements. To shed light on this issue, this article proposes a frequency measurement and RoCoF analysis technology, as well as the sensitivity analysis for the real low-inertia power grid. First, a real-world event in an island power grid is analyzed as an example, and an event numerical model is estimated considering four uncertainties, including event RoCoF, oscillation magnitude, oscillation frequency, and underfrequency load-shedding threshold. Then, a sensitivity analysis is performed using the Sobol indices method and quasi-Monte Carlo simulations to identify the dominant uncertainties based on the event model. Here, the dominant uncertainties are compared to provide a guideline for the frequency estimation algorithm selection under different event cases. This algorithm is compared with an enhanced zero-crossing algorithm and gives a 3.41% better RoCoF error rate. Finally, an experiment is conducted using universal grid analyzers to validate the simulation results and the theoretical analysis.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Real-Time Detection and Localization of Line Trip Event Via Relative Phase Angles

Line trip events widely exist in power systems. They can result in power outages and a huge economic loss if not promptly detected and localized. To provide a fast and precise solution, this paper presents a Complete Coverage of Voltage Measurement (CCVM)-based line trip event detection algorithm and a Relative Phase Angle (RPA)-based line trip event localization algorithm. First, frequency and relative phase angle features during a line trip event are calculated. Then, the CCVM-based algorithm is proposed from both frequency and rate of change of frequency estimation algorithm aspects. Additionally, the RPA-based algorithm is presented, and two cases are studied to demonstrate the uniqueness of the proposed algorithm. Various experiments are conducted, where the simulation results demonstrate that the proposed CCVM-based algorithm can detect a line trip event as short as 2.07 ms. In addition, the RPA-based algorithm has 1.26 times higher localization accuracy compared with the frequency magnitude-based and phase angle-based algorithms. In conclusion, the experiment results on the examples from two interconnected power systems in the U.S. verified the performance of the proposed algorithms in wide-area power systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Multi-Timescale Integrated Dynamics and Scheduling for Solar (MIDAS-Solar) (Final Technical Report)

Solar photovoltaic (PV) installations have experienced unprecedented growth in the United States. PV will become not only an energy producer but also a necessary provider of ancillary services at multiple timescales. Conventional methods to simulate power systems operations - such as long-term production simulation (which typically considers schedules from hours to minutes by using an optimization framework) and short-term transient studies (which simulate dynamics from seconds to sub-seconds using state variables and differential equations) - are not sufficient for studying the multiple-timescale variation of solar generation and its impact on system reliability. Long-term system economics and short-term system dynamics are highly coupled, particularly when the penetration level of renewable generation is extremely high, because the uncertainty and variability of solar generation will impact both power system steady-state and dynamic performance. This project helps meet and exceed the U.S. Department of Energy Office of Energy Efficiency and Renewable Energy Solar Energy Technologies Office goal of systems integration by directly addressing this stability and reliability challenge for power grid planning and operation. We have developed a temporally comprehensive, closed-loop simulation model, named Multi-timescale Integrated Dynamics and Scheduling (MIDAS), that seamlessly simulates power system operations from economic scheduling (day-ahead to hours) to dynamic response analysis (seconds to sub-seconds). For schedules with very high levels of inverter-based resources (IBRs), up to and including 100%, the stability of grid controls has been evaluated through electromagnetic transient (EMT) simulations and power-hardware-in-the-loop (PHIL) simulations of key transient events at key schedule points. Specifically, MIDAS provides: 1) a closed-loop simulation framework for simulating timescales from economic scheduling to dynamic stability analysis; 2) machine learning-based stability assessment; 3) EMT modeling and analysis for large-scale power systems; 4) MIDAS PHIL test bed. We worked with Hawaii Electric Companies to apply the MIDAS study framework to a Maui grid study. The entire island's transmission system was modeled in detail - from a yearly scheduling model, to a second-level frequency dynamic model, down to a sub-second-scale EMT model to address critical stability issues. The project demonstrated how MIDAS can help system planners and operators assess system reliability and stability while the power grid is marching toward a high-renewable, high-IBR future. In this Maui grid study, we found that 100% instantaneous IBR operation is achievable in EMT simulation and PHIL testing, and grid planners and operators might need new analysis/simulation tools to assess grid reliability and stability in the scheduling stage. MIDAS will bring Maui and other systems closer to 100% clean and stable energy futures. (In this study, we examined transient stability. Other topics necessary for 100% IBR operation, such as protection and resource adequacy, were not examined.)

100% Renewables↗

AI-Based Faster-Than-Real-Time Stability Assessment of Large Power Systems with Applications on WECC System

Achieving clean energy goals will require significant advances in regard to addressing the computational needs for next-generation renewable-dominated power grids. One critical obstacle that lies in the way of transitioning today’s power grid to a renewable-dominated power grid is the lack of a faster-than-real-time stability assessment technology for operating a fast-changing power grid. This paper proposes an artificial intelligence (AI) -based method that predicts the system’s stability margin information (e.g., the frequency nadir in the frequency stability assessment and the critical clearing time (CCT) value in the transient stability assessment) directly from the system operating conditions without performing the conventional time-consuming time-domain simulations over detailed dynamic models. Since the AI method shifts the majority of the computational burden to offline training, the online evaluation is extremely fast. This paper has tested the AI-based stability assessment method using multiple dispatch cases that are converted and tuned from actual dispatch cases of the Western Electricity Coordinating Council (WECC) system model with more than 20,000 buses. The results show that the AI-based method could accurately predict the stability margin of such a large power system in less than 0.2 milliseconds using the offline-trained AI agent. Therefore, the proposed method has great potential to achieve faster-than-real-time stability assessment for practical large power systems while preserving sufficient accuracy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Deep Learning Based Frequency Stability Assessment in Power Grid with High Renewables

Frequency stability assessment is one critical aspect of power system security assessment. Traditional N-1 screening method is based on the simulations of a few typical daily and seasonal operation scenarios. However, the increasing integration of inverter-based renewables and the retirement of conventional synchronous generators result in decreasing system inertia and growing complexity of system operating conditions. Selecting a few typical operation scenarios cannot cover all operating conditions, and the time-domain simulation of all operation conditions requires tremendous time. This paper proposes a more efficient frequency stability assessment method based on deep learning. The affinity propagation clustering algorithm is used to divide the dataset into different clusters, so the selected dataset for training can cover the diversified operating conditions as much as possible. Also, feature normalization is applied to both the training dataset and testing dataset in order to remove any unnecessary bias. Especially, trained model based on full dataset normalization has bounded error in the prediction. The case study on the reduced 240-bus WECC system demonstrates that the proposed method can predict accurate frequency nadir with limited training dataset. The deep learning model using the revised feature normalization can predict more accurate frequency nadir than that using the traditional feature normalization and has very small maximum prediction error.

affinity propagation↗

A Fast and Accurate Transient Stability Assessment Method Based on Deep Learning: WECC Case Study

Transient stability is one of the critical aspects of power system stability assessment. The increasing integration of inverter-based resources and the retirement of conventional synchronous generators result in the decreasing system inertia and growing complexity of system operating conditions. Using a few selected typical operating conditions cannot guarantee system transient stability in all operating conditions, and the time-domain simulation of all operating conditions requires tremendous time and is often infeasible. This paper proposes a more efficient transient stability assessment method based on deep learning. The binary search method is used to determine the critical clearing time (CCT) in creating training databased by time-domain simulation. This method is fast and accurate with 1 ms resolution. The buses whose CCTs are lower than 200 ms are considered critical buses. Buses close to each other are grouped based on their mutual admittance matrix to reduce the search space of the critical buses. This paper also proposes the generator feature normalization based on the physical model. Case study on the reduced 240-bus WECC system model demonstrates that the proposed method can predict CCT accurately and efficiently.

critical clearing time↗

Practical Event Location Estimation Algorithm for Power Transmission System Based on Triangulation and Oscillation Intensity

Event location in power systems is quite essential information for system operators to enhance control-room situational awareness capability. Therefore, it is of great importance to develop an event location estimation algorithm for transmission systems with high accuracy. With the development of wide-area measurement system (WAMS) such as FNET/GridEye, and the synchrophasor measurement devices (SMDs) such as frequency disturbance recorders (FDRs), the synchronous measurement data including frequency, voltage amplitude and phase angle can be collected and used for event location estimation. First, the phase angle and rate of change of frequency (RoCoF) trajectories are respectively used for determining two sets of wave arrival time associated with each FDR. Then, a convolutional neural network (CNN) is utilized to determine the wave arrival order to select the more suitable set of wave arrival times for a given case and to perform corresponding modifications. Next, the oscillation intensity associated with each FDR is determined based on phase angle trajectories in the center of inertia (COI) coordinate system. Finally, the multiple criteria for event location estimation are represented. In conclusion, case studies and comparisons between the proposed and previous algorithms using actual and confirmed cases in U.S. power systems are performed to demonstrate the effectiveness and improvement of the proposed algorithm in practical applications.

frequency disturbance recorder (FDR)↗

Precise ROCOF estimation algorithm for low inertia power grids

The precise estimation of Rate Of Change Of Frequencies (ROCOFs) in a generation trip event can be helpful on power system inertia estimation, fast system response, and accurate event capturing. However, the ROCOF estimations from the existing Synchronized Measurement Devices (SMDs) are usually simply calculated by the finite difference between two adjacent frequency measurement points. The ineluctable noises, disturbances, and spikes from real-world frequency measurements can bring large dynamics to the ROCOF estimation and thus can result in an inaccurate estimation of the initial ROCOF. This issue becomes more serious when the target power grid has low inertia, and a large amount of distributed energy sources are deployed. To address this issue, a precise ROCOF estimation algorithm is designed based on least square method with flexible window size. In addition, a median filter is also designed and applied on the frequency measurements before using the proposed algorithm. The window size and thresholds in the proposed algorithm are determined with historical event data analysis. The proposed algorithm is deployed in a low cost, flexible, and distribution level universal grid analyzer (UGA) platform. In conclusion, multiple experiments are conducted in both a laboratory and the Hawaiian Islands to verify the effectiveness of the proposed algorithm.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Adding power of artificial intelligence to situational awareness of large interconnections dominated by inverter‐based resources

Abstract Large‐scale power systems exhibit more complex dynamics due to the increasing integration of inverter‐based resources (IBRs). Therefore, there is an urgent need to enhance the situational awareness capability for better monitoring and control of power grids dominated by IBRs. As a pioneering Wide‐Area Measurement System, FNET/GridEye has developed and implemented various advanced applications based on the collected synchrophasor measurements to enhance the situational awareness capability of large‐scale power grids. This study provides an overview of the latest progress of FNET/GridEye. The sensors, communication, and data servers are upgraded to handle ultra‐high density synchrophasor and point‐on‐wave data to monitor system dynamics with more details. More importantly, several artificial intelligence (AI)‐based advanced applications are introduced, including AI‐based inertia estimation, AI‐based disturbance size and location estimation, AI‐based system stability assessment, and AI‐based data authentication.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Deep Learning-Based Adaptive Remedial Action Scheme with Security Margin for Renewable-Dominated Power Grids

The Remedial Action Scheme (RAS) is designed to take corrective actions after detecting predetermined conditions to maintain system transient stability in large interconnected power grids. However, since RAS is usually designed based on a few selected typical operating conditions, it is not optimal in operating conditions that are not considered in the offline design, especially under frequently and dramatically varying operating conditions due to the increasing integration of intermittent renewables. The deep learning-based RAS is proposed to enhance the adaptivity of RAS to varying operating conditions. During the training, a customized loss function is developed to penalize the negative loss and suggest corrective actions with a security margin to avoid triggering under-frequency and over-frequency relays. Simulation results of the reduced United States Western Interconnection system model demonstrate that the proposed deep learning–based RAS can provide optimal corrective actions for unseen operating conditions while maintaining a sufficient security margin.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Data-driven Event Identification in the U.S. Power Systems Based on 2D-OLPP and RUSBoosting Trees

Accurate event identification is an essential part of situation awareness ability for power system operators. Therefore, this work proposes an integrated event identification algorithm for power systems. First, to obtain and filter suitable inputs for event identification, an event detection trigger based on the rate of change of frequency (RoCoF) is presented. Then, the wave arrival time difference-based triangulation method considering the anisotropy of wave propagation speed is utilized to estimate the location of the detected event. Next, the two-dimensional orthogonal locality preserving projection (2D-OLPP)-based method, which is suitable for multiple types of measured data, is employed to achieve higher effectiveness in extracting the event features compared with traditional one-dimensional projection and principle component analysis (PCA). Finally, the random undersampling boosted (RUSBoosted) trees-based classifier, which can mitigate the data sample imbalance issue, is utilized to identify the type of the detected event. Furthermore, the proposed approach is demonstrated using the actual measurement data of U.S. power systems from FNET/GridEye. Comparison results show that the proposed event identification algorithm can achieve better performance than existing approaches.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Time-frequency based cyber security defense of wide-area control system for fast frequency reserve

Global power systems are transiting from conventional fossil fuel energy to renewable energies due to their environmental benefits. The increasing penetration of renewable energies presents challenges for power system operation. The efficiency and sufficiency of responsive reserves have become increasingly important for power systems with a high proportion of renewable energies. The Fast Frequency Reserve (FFR), especially the Wide-area Monitoring System (WAMS)-based FFR, is a promising and effective solution to secure and enhance the stability of power systems. However, cyber security has become a new challenge for the WAMS-based FFR system. Cyber attacks on the FFR control system may threaten the safety of power system operation due to the rapid power controllability requirement of FFR. Therefore, to address this problem, a time-frequency based cyber security defense framework is proposed to detect the cyber spoofing of synchrophasor data in WAMS-based FFR control systems. This paper first introduces the Continuous Wavelet Transforms (CWTs) to decompose spoofing signals. Then, the Dual-frequency Scale Convolutional Neural Networks (DSCNN) is proposed to identify the time-frequency domains matrix from two frequency scales. Integrating CWTs and DSCNN, an identification framework called CWTs-DSCNN is further proposed to detect the spoofing attacks in the WAMS-based FFR system. Multiple experiments using the actual data from FNET/GridEye are performed to verify the effectiveness of the framework in securing WAMS-based FFR systems.

25 ENERGY STORAGE↗

Frequency Injection Based HVDC Attack-Defense Control Via Squeeze-Excitation Double CNN

Due to the independent controllability and fast power regulation capability, the High Voltage Direct Current (HVDC) system could be a prospective technology to provide multiple ancillary services to the system besides conventional bulk power transmission. However, with the increase of False Data Injection Attacks (FDIAs) on PMU data, the HVDC system could have the wrong response once the collected data that the HVDC system relied on is attacked, thus threatening the system operating security. How to ensure the security of the PMU-based HVDC ancillary service control become an urgent issue. To mitigate the risk, this paper proposed an HVDC attack-defense control based on the FDIAs detection method. Firstly, the Squeeze-Excitation based Double Convolutional Neural Networks (SE-DCNN) is proposed to realize fast identification of the attacking frequency type based on the time and frequency domain signals. Furthermore, the duration time of FDIAs is detected by the local outlier factor. Then, utilizing the results from SE-DCNN, HVDC ancillary service control framework is reorganized and an HVDC attack defense control is proposed for suppressing the potential influence of various types of FDIAs on the HVDC system ancillary service. Different experiments results demonstrate that the proposed method has the ability to significantly mitigate the frequency deviation and oscillation under the FDIA.

42 ENGINEERING↗

Data source authentication of synchrophasor measurement devices based on 1D-CNN and GRU

Synchrophasor measurement devices (SMDs) have been widely deployed to support real-time monitoring and control of power systems. In the meantime, data spoofing has emerged in recent years. Therefore, it is of great importance to study data authentication algorithms for detecting and defending the data spoofing effectively. Here, a one-dimensional convolutional neural network (1D-CNN) is utilized to extract temporal signatures hidden in frequency, voltage angle and amplitude data; then the gated recurrent unit (GRU) employs these temporal signatures for data source authentication. In case studies, the performances of different algorithms are tested in large-scale power systems with numerous SMDs for the first time, and comparisons among different algorithms show that the proposed algorithm can achieve a higher accuracy of data source authentication with a shorter time window.

47 OTHER INSTRUMENTATION↗

Adaptive PV Frequency Control Strategy Based on Real-time Inertia Estimation

The declining cost of solar Photovoltaics (PV) generation is driving its worldwide deployment. As conventional generation with large rotating masses is being replaced by renewable energy such as PV, the power system’s inertia will be affected. As a result, the system’s frequency may vary more dramatically in the case of a disturbance, and the frequency nadir may be low enough to trigger protection relays such as under-frequency load shedding. The existing frequency-watt function mandated in power inverters cannot provide grid frequency support in a loss-of-generation event, as PV plants usually do not have power reserves. Here, a novel adaptive PV frequency control strategy is proposed to reserve the minimum power required for grid frequency support. A machine learning model is trained to predict system frequency response under varying system conditions, and an adaptive allocation of PV headroom reserves is made based on the machine learning model as well as real-time system conditions including inertia. Case studies show the proposed control method meets the frequency nadir requirements using minimal power reserves compared to a fixed headroom control approach.

14 SOLAR ENERGY↗