Role of Renewables in Grid Resilience

This chapter focuses on revealing the impact of renewable energies, especially distributed energy resources, on modern power system resilience. It is widely recognized that the increasing adoption of renewable energy is bringing more uncertainty and variability, posing new challenges to grid resilience. However, both supply and demand are becoming more active in grid resilience management. The communities themselves would benefit from the utilization of local resources and flexible management to gain resilience during the extreme events.

grid resilience↗

Development of near-optimal advanced control sequences for chiller plants with water-side economizers in U.S. Climates (ASHRAE RP-1661)

Various advanced control sequences for chiller plants with water-side economizers (WSE) have been proposed in literature, but the evaluation and optimization of those controls is limited. It is possible to maximize energy savings by selecting different sequences and related parameters based on the plant configuration, load, and climate. This paper addresses this gap by developing near-optimal advanced control sequences for chiller plants with WSEs. First, advanced control sequences for chiller plants with WSEs are categorized into condenser water, chilled water, and hybrid controls and representative sequences from each category are identified. Next, 504 different scenarios are optimized. These scenarios represent all possible combinations of two plant configurations, a constant or variable load profile, three advanced control sequences, and seven optimization parameter combinations in six climate zones. The results show the recommended near-optimal sequences can reduce energy consumption by up to 15% relative to the baseline depending on the configuration, load profile, and climate. Specifically, the CW-CHW sequence is recommended for the majority of systems because it is often the most energy efficient and/or reduces the runtime of chillers. The methodology in this paper provides practical guidance for achieving energy savings through near-optimal control of chiller plants with WSEs.

42 ENGINEERING↗

Ecosystem-Level Biomimicry for the Built Environment: Adopting Systems Ecology Principles for the Control of Heterogeneous Energy Systems

This paper presents, to our knowledge, the first system-level engineering study to bio-mimic the cybernetics and flow dynamics of energy resources in natural ecosystems for the control of heterogeneous energy infrastructures in the built environment. To this end, we introduce a novel Biomimetic Pulsing State (BPS) control that functionally mimics mature ecosystems. A preliminary Modelica-based case study features a single-family residential building with electrical and HVAC subsystems. The BPS control objective is to minimize the energy exchange between the building and the grid for the purposes of future self-supporting buildings and grid stability. The building contains PV, a wind turbine, a battery storage system, and a fan coil/heat pump HVAC system served by an ambient district energy network. Evaluating the control performance (BPS vs. constant setpoint) over several renewable energy scenarios (net importer, net zero, net exporter), simulation results show how the building's HVAC system can dynamically adjust its electrical load and temperatures to the electrical system's net energy status in real-time with BPS control. As a net importer, the heat pump consumed 29% less energy and its peak power reduced by 15% with BPS control compared to the constant setpoint case, with the zone air temperature 1 degree C lower on average. As a net exporter, the heat pump effectively consumed the same energy, but the peak power increased by 34% with BPS control, while the zone air temperature was 1 degree C higher when renewable energy was abundant, preheating the home. BPS and constant setpoint control produced comparable results under a net zero scenario. While further evaluation is essential, BPS control may help communities meet their sustainability and resiliency targets as they transition towards fully distributed and renewable energy grids.

biomimicry↗

Simulation-based assessment of ASHRAE Guideline 36, considering energy performance, indoor air quality, and control stability

This study assesses American Society of Heating, Refrigerating and Air-Conditioning Engineers Guideline 36 (G36) with a typical medium office building. Specifically, this study employed a Modelica model of a variable air volume (VAV) system that serves this building, which includes components for representing indoor virus transmission and filtration. It then implemented the G36 control sequences for both water-side and air-side equipment in Python. After that, this study conducted the assessment by co-simulating G36 and the Modelica model using the Building Operations Testing Framework. Unlike existing works, this work has three unique features: (1) It considers the interactions between control sequences for water-side and air-side equipment of the studied VAV system. (2) It assesses the performance of G36 from the perspective of IAQ. (3) It examines the short-term behaviors of the studied building under G36 to understand the control stability. This assessment confirms significant energy savings from G36, largely because of the interaction between supply air temperature and hot water controls. It also reveals a trade-off between the ability to slow the spread of virus and the energy performance via demand controlled ventilation. Lastly, it emphasizes the necessity of tuning local feedback control when implementing G36.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Comprehensive Analysis of Model Parameter Uncertainty Influence on Evaluation of HVAC Operation to Mitigate Indoor Virus: A Case Study for an Office Building in a Cold and Dry Climate

Simulation-based studies of HVAC operation to mitigate indoor virus have been conducted to understand tradeoffs between indoor air quality (IAQ) and energy consumption. However, the influence of model parameter uncertainty in these studies has not been systematically quantified, which is critical when providing guidance to building operators. To address this gap, we identify 20 model parameters for a typical medium office building system in a cold and dry climate that can influence IAQ and energy consumption for indoor virus scenarios. Next, the distributions of the parameter values are estimated from literature and a set of simulation samples for three representative days is generated that simultaneously sample all of the parameters from their distributions. Two HVAC virus mitigation strategies are studied: increased filtration using MERV 13 filters and increased ventilation, via supply of 100% outdoor air into buildings. The model parameter uncertainty leads to significant variability in the results, particularly for the IAQ because of the highly uncertain virus generation rate. Use of 100% outdoor air can be beneficial for some uncertain scenarios on the hot day, but shows less IAQ improvement and/or significant energy increases on the other days. The virus removal efficiency and pressure drop of the HVAC filter, fan efficiency, and internal heat gain are the most important parameters to determining the tradeoffs of the two strategies. Our results demonstrate how this model parameter uncertainty analysis methodology can provide practical guidance to building operators.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

An open-source framework for simulation-based testing of buildings control strategies

Here this paper presents a simulation framework for evaluating building control strategies (BCSs), developed with VOLTTRON, an opensource platform that integrates data, devices, and systems for sensing and control applications, and is based on co-simulation interfaces. It realizes an integrated environment for both testing and deploying BCSs, thereby eliminating the need for having a dedicated implementation of BCS for testing. For the first time, this framework provides critical functionalities, including scalable communication management and time-drive simulation advance, i.e., advancing the simulation based on clock time. We applied this framework to evaluating two BCSs from ASHRAE Guideline 36-2008 and ASHRAE Standard 90.1-2019. The evaluation results show that those BCSs primarily benefit the heating operation by reducing gas usage but yield insignificant savings in electricity consumption. The results also emphasize the importance of tuning the parameters of the BCSs to achieve better performances.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Quantifying spatiotemporal variability in occupant exposure to an indoor airborne contaminant with an uncertain source location

Well-mixed zone models are often employed to compute indoor air quality and occupant exposures. While effective, a potential downside to assuming instantaneous, perfect mixing is underpredicting exposures to high intermittent concentrations within a room. When such cases are of concern, more spatially resolved models, like computational-fluid dynamics methods, are used for some or all of the zones. But, these models have higher computational costs and require more input information. A preferred compromise would be to continue with a multi-zone modeling approach for all rooms, but with a better assessment of the spatial variability within a room. Here to do so, we present a quantitative method for estimating a room's spatiotemporal variability, based on influential room parameters. Our proposed method disaggregates variability into the variability in a room's average concentration, and the spatial variability within the room relative to that average. This enables a detailed assessment of how variability in particular room parameters impacts the uncertain occupant exposures. To demonstrate the utility of this method, we simulate contaminant dispersion for a variety of possible source locations. We compute breathing-zone exposure during the releasing (source is active) and decaying (source is removed) periods. Using CFD methods, we found after a 30 minutes release the average standard deviation in the spatial distribution of exposure was approximately 28% of the source average exposure, whereas variability in the different average exposures was lower, only 10% of the total average. We also find that although uncertainty in the source location leads to variability in the average magnitude of transient exposure, it does not have a particularly large influence on the spatial distribution during the decaying period, or on the average contaminant removal rate. By systematically characterizing a room's average concentration, its variability, and the spatial variability within the room important insights can be gained as to how much uncertainty is introduced into occupant exposure predictions by assuming a uniform in-room contaminant concentration. We discuss how the results of these characterizations can improve our understanding of the uncertainty in occupant exposures relative to well-mixed models.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

System modeling for grid-interactive efficient building applications

Despite the abundance of research applications of system modeling in grid-interactive efficient buildings (GEBs), the transfer of those applications to real-world practices is still in its early stages. This is partially due to the lack of a summary on how system modeling should be established for a given application of GEBs. Here, we fill this gap by providing an extensive survey of the literature on system modeling for different GEBs that have been produced in the past decade. This survey involves over 300 relevant journal articles from the building community, the power system community, and the society of control. Specifically, we first identified key requirements of system modeling for GEBs based on various types of applications discussed in those publications. We then summarized the system modeling applications from those publications, in terms of their assumptions, modeling approach, and simulation. After that, we analyzed different assumptions made for various applications, the extent to which those modeling approaches satisfied the key requirements, and how those approaches can be scaled up for large-scale applications, which are quite common in GEBs. In addition, we gave insights on how to use system modeling for different applications in GEBs. At the end, we provided recommended directions for future studies to fully unleash the potentials of system modeling to support GEBs.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Long-term carbon intensity reduction potential of K-12 school buildings in the United States

School buildings have a great potential for carbon emission reduction since their annual emission is about 72 million metric tons. Currently, more than 30% of school buildings were built before 1960 and are underperforming. To effectively reduce carbon emissions via school building retrofits, it is critical for policymakers to understand the carbon intensity reduction potential of retrofitting school buildings in different regions. Hence, this study develops a method to comprehensively assess the long-term carbon intensity reduction potential of aggregated commercial buildings on a county-by-county basis in the continental U.S. We apply this method to the K-12 school buildings including primary and secondary school buildings. Here, this paper predicts the carbon intensity reduction potential of K-12 school buildings with eight building retrofit measures from 2022 to 2050 in the continental U.S. The results reveal several interesting findings: (1) In the approximately 3,000 counties of the U.S. from 2022 to 2050, the carbon intensity reduction potential of retrofitting K-12 school buildings in each county ranges from 0.41 kg/m 2 to 40.00 kg/m 2 . (2) Even in the same climate zone, the trends of carbon intensity reduction potential from 2022 to 2050 are different depending on their electricity sources. For example, in a hot and humid climate zone, the carbon intensity reduction potential in Florida will decrease from 2044 to 2048. However, in Mississippi, the carbon intensity reduction potential from 2044 to 2046 will increase due to the termination of the nuclear energy usage. (3) Generally, reducing lighting power density leads to more carbon intensity reduction in most states, but it might not be applicable for states with high clean energy penetration, such as Washington.