DOE OSTI · 1025675
Deriving Optimal Operational Rules for Mitigating Inter-area Oscillations
Abstract
This paper introduces a new method to mitigate inter-area oscillations of a large scale interconnected power system by means of generation re-dispatch. The optimal operational control procedures are derived as the shortest distance from the current operating condition to a desired damping ratio of the oscillation mode by adjusting generator outputs. A sensitivity based method is used to select the most effective generators for generation re-dispatch and decision tree is trained to approximate the security boundary in a space characterized by the selected generators. The optimal operational rules can be found by solving an optimization problem where the boundary constraints are provided by the decision tree rules. This method is tested on a Western Electricity Coordinating Council (WECC) 179-bus simplified network model and simulation results have demonstrated the proof of concept and shown promising application in real time operation.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Diao, Ruisheng, Huang, Zhenyu, Zhou, Ning, Chen, Yousu, Tuffner, Francis K, Fuller, Jason C, Jin, Shuangshuang, Dagle, Jeffery E. 2011-05-23. Deriving Optimal Operational Rules for Mitigating Inter-area Oscillations. https://doi.org/10.1109/psce.2011.5772564
Cite the original work for its findings. Save a collection to share your selection of sources.