DOE OSTI · 1261233
System Study: Emergency Power System 1998-2014
Abstract
This report presents an unreliability evaluation of the emergency power system (EPS) at 104 U.S. commercial nuclear power plants. Demand, run hours, and failure data from fiscal year 1998 through 2014 for selected components were obtained from the Institute of Nuclear Power Operations (INPO) Consolidated Events Database (ICES). The unreliability results are trended for the most recent 10 year period while yearly estimates for system unreliability are provided for the entire active period. An extremely statistically significant increasing trend was observed for EPS system unreliability for an 8-hour mission. A statistically significant increasing trend was observed for EPS system start-only unreliability.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Schroeder, John Alton. 2015-12-01. System Study: Emergency Power System 1998-2014. https://doi.org/10.2172/1261233. https://searchnasa.com/record/osti%3A1261233/system-study-emergency-power-system-1998-2014