Abstract
Grid-forming inverters in a microgrid may trip due to high inrush current caused by a switched connection of an inductive load, e.g., a relatively large induction motor. The control scheme presented in this article includes virtual inertia control method superimposed on the cascaded controller. This article studies the impact of cascaded control scheme used for grid-forming inverter to mitigate the inrush current effects and enhance the inverter’s robustness for the safe connection of inductive and dynamic loads. Experimental tests are performed using the virtual inertia method for generating the reference angle for synchronous frame conversion. The experimental performance and sensitivity of the controller to different controller gain settings for a switched connection of an induction motor are discussed. The cascaded operation significantly mitigates the inrush currents while the inverters can perform a normal operation. The performance of the control method is tested in a laboratory-scale hardware setup of a 208V microgrid fed by 5kVA and 10kVA inverters, and the results are presented.
Keep this discovery
Explore connections, maps & timelines
Gursoy, Mehmetcan, Mirafzal, Behrooz. 2022-10-15. Dynamic Load Inrush Current Mitigation in Islanded Microgrids Powered by Grid-Forming Inverters. https://doi.org/10.1109/icidea53933.2022.9970083
Cite the original work for its findings. Save a collection to share your selection of sources.