DOE OSTI · 1914317
PV inverter experimental data
Abstract
The increase in power electronic based generation sources require accurate modeling of inverters. Accurate modeling requires experimental data over wider operation range. We used 20 kW off-the-shelf grid following PV inverter in the experiments. We used controllable AC supply and controllable DC supply to emulate AC and DC side characteristics. The experiments were performed at NREL's Energy Systems Integration Facility. Due to the limitations of the DC supply used, inverter is tested under 75%, 50%, 25% load conditions (This dataset does not contain 100% load condition). In the first dataset, for each operating condition, controllable AC source voltage is varied from 0.88 to 1.09 per unit (p.u) with a step value of 0.025 p.u while keeping the frequency at 60 Hz. In the second dataset, under similar load conditions (75%, 50%, 25% ), the frequency of the controllable AC source voltage was varied from 59.4 Hz to 60.45 Hz with a step value of 0.2 Hz. Voltage and frequency range is chosen based on inverter protection. Voltages and currents on DC and AC side are included in the dataset.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Prabakar, Kumaraguru, Ganguly, Subhankar, Velaga, Yaswanth Nag, Vaidhynathan, Deepthi. 2023-01-06. PV inverter experimental data. https://doi.org/10.7799/1914317
Cite the original work for its findings. Save a collection to share your selection of sources.