Search NASA⌕ Search

DOE OSTI · 1994318

Resilient cooling through geothermal district energy system

Abstract

Decarbonization and resilience to heat waves have recently become high priorities for building and district energy systems. Geothermal coupled district heating and cooling systems that operate a water loop near ground temperature gain increasing adoption to support decarbonization. In these systems, vapor-compression machines, distributed in the energy transfer stations, lift the temperature up or down to the needs of the particular building. In principle, these systems can provide low-power, free cooling from the geothermal bore field during heat waves when electricity is often scarce. However, the performance of such a resilience operation mode and its implication on the energy system configuration and the sizing of the bore field and HVAC equipment is not yet understood. Consequently, we are assessing their resilience, power use and design implications under a scenario of a heat wave on five working days during which chillers are switched off to reduce electrical consumption. Our analysis is based on high-fidelity, coupled dynamic models of district energy, building-side HVAC and actual control logic, with whole building energy simulation used to assess thermal conditions in a 2004 vintage multi-zone office building in Chicago, IL. The results show that relying only on waterside economizer cooling, the indoor thermal conditions can be maintained in a tolerable range for the majority of the building zones with half the electrical energy compared to standard chiller operation. Thermal comfort in the hottest zones can be further improved by oversizing the cooling coil. However, the waterside economizer has significant implications on the system configuration and sizing: The geothermal bore field needs to be sized about 30% larger than the upper limit of the range observed for conventional geothermal systems. Nevertheless, if a central chiller plant is added, the bore field can be downsized to the typical design range. The latter configuration still allows compressor-less cooling during the heat wave with peak power reduced by 60% compared to the standard design and chiller operation.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Gautier, Antoine, Wetter, Michael, Sulzer, Matthias. 2022-09-07. Resilient cooling through geothermal district energy system. https://doi.org/10.1016/j.apenergy.2022.119880

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related reports

Technical, economic, and load-following capabilities assessment of grid-connected geothermal and geothermal-solar hybrid systems

The technical and economic performance as well as the load-following capabilities of grid-connected geothermal hybrid systems were assessed in this work. The analyzed geothermal hybrid configuration is composed of a binary geothermal plant integrated with a concentrating solar-thermal system and underground thermal energy storage (UTES) through a primary heat exchanger. Physics-based models for the hybrid system for plant generation capacities of 1, 25, and 50 MW were developed from validated models for each subsystem. Also, an economic model was developed that accounts for different hybrid system capabilities, solar field sizes, and thermal storage duration. The advantage of the geothermal hybrid system was assessed by comparing the performance with the baseline benchmark geothermal plant with a similar configuration and generation capacity. It was found that hybridizing geothermal plants with concentrating solar and thermal energy storage not only improves the thermal efficiency by up to 8 percentage points when additional heat from the solar-UTES loop rises the evaporator temperatures from 70 to 125 °C, but also enhances the load-following capability for the geothermal plant, which can meet a typical residential load profile with a power rate of change 0.25 kW/s with an absolute error under 13 kW for a 1 MW plant. Other benefits of hybridization include resource preservation and a potential LCOE reduction of up to 56% for a 50 MW geothermal hybrid plant having a 50% solar share, a 1.4 solar multiple, and 24-h storage capacity. The results presented in this work demonstrate that hybridizing geothermal systems transforms them into a flexible and cost-effective solution for addressing the dynamic requirements of modern electric grids.

15 GEOTHERMAL ENERGY↗

ResStock Measure Documentation: Residential Two-Stage Geothermal Heat Pump (4.0 COP, 20.5 EER) With Light Envelope Improvements

This report is part of series describing a variety of different ResStock(TM) measures. "Measures" refers to energy efficiency retrofits that can be applied to buildings during modeling. This documentation covers the "Residential Two-Stage Geothermal Heat Pump (4.0 COP, 20.5 EER) With Light Envelope Improvements" measure upgrade methodology and briefly discusses key results. All results can be accessed on the ResStock Open Energy Data Initiative "End-Use Load Profiles for the U.S. Building Stock" data lake and on the data viewer at resstock.nlr.gov.

15 GEOTHERMAL ENERGY↗

Impact of Space Heating Options on Electricity Rates and Affordability

Electricity prices have increased in many regions of the U.S., with a national average of 18 cents/kWh projected for 2026, up from 16 cents/kWh in 2020. While the increases can be attributed to a number of factors, increasing electricity use in an efficient and strategic manner - with energy efficient building envelope upgrades and high performance HVAC systems - has the potential to increase revenue for utilities without significantly increasing electricity demand, and therefore could help moderate rate increases. This effect has been studied for electric vehicle charging[1] and dual-fuel heat pumps in Minnesota[2]. Leveraging a recently developed system cost methodology and FERC data on utility revenue, spending, and profits, this poster will present the direction and relative magnitude of rate impacts for efficient space heating upgrades in utility balancing areas across the contiguous U.S., using current prices and showing how the rate impacts would evolve under future grid scenarios.

15 GEOTHERMAL ENERGY↗