Assessment of the 3430 Building Filtered Exhaust Stack Sampling Probe Location: Stack Verification Following Fan and Air Blender Additions

Abstract

The velocity uniformity and flow angle results from the 3430 stack verification tests, performed in April 2023, demonstrated that the CFD model results may be used to support the qualification of the stack sampling location. The measured velocity uniformity verification test result was 2.1 %COV. This value is well within the uniformity criterion, which is that the velocity uniformity be =20 %COV. Additionally, this value is well within the criterion that the actual stack measurement must be within 5% of the surrogate stack (i.e., CFD modeled stack); in this case the CFD modeled average result of 2.85 %COV for the nominal operating range of 22,800 cfm to 62,400 cfm. Additionally, the measured average flow angle at the 3430 stack monitor location was 5.6 degrees. The result is =20 degrees, so the criterion is met.