Abstract
As hydrogen storage facilities increase in size and capacity, it may be necessary to evaluate codes and standards that regulate hydrogen, especially in relation to allowable aggregate quantities. Existing regulations for other substances with comparable hazards such as oxygen, natural gas, and petroleum were reviewed; most fuels do not have aggregate quantity limits despite sometimes having individual tank capacity restrictions or limits for certain non-industrial, indoor, or small-scale applications. This precedent suggests that specifying a hydrogen quantity limit may not be necessary. Several possible methods for identifying an appropriate limit are presented to illustrate different approaches for a limit basis. These methods are based on overall risk, or the specific consequences inflicted by a jet fire or an explosion on people and infrastructure. However, these example metrics tend to require assumptions about potential leak sizes, suggesting that a general aggregate quantity limit would be difficult to justify without more system-specific requirements.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Louie, Melissa Sui-hui, Schroeder, Benjamin B., Ehrhart, Brian David. 2024-08-01. Evaluation of Hydrogen Storage Quantity Limits for Safety Requirements. https://doi.org/10.2172/2429928