DOE OSTI · 962615
Spinning Reserve from Responsive Load
Abstract
As power system costs rise and capacity is strained demand response can provide a significant system reliability benefit at a potentially attractive cost. The 162 room Music Road Hotel in Pigeon Forge Tennessee agreed to host a spinning reserve test. The Tennessee Valley Authority (TVA) supplied real-time metering and monitoring expertise to record total hotel load during both normal operations and testing. Preliminary testing showed that hotel load can be curtailed by 22% to 37% depending on the outdoor temperature and the time of day. The load drop was very rapid, essentially as fast as the 2 second metering could detect.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Kueck, John D, Kirby, Brendan J, Laughner, T, Morris, K. 2009-01-01. Spinning Reserve from Responsive Load. https://www.osti.gov/biblio/962615