At least 271 records · Page 15

Solar PV and BESS Plant-Level Voltage Control and Interactions: Experiments and Analysis

In real world operation, low-frequency oscillations associated with plant-level voltage control of inverter-based resources (IBRs) have been a concern of grid operators. Here, this research aims to demonstrate and analyze the effect of plant-level voltage control on system stability and potential interactions among IBRs. The experiment results of a 13.2-kV system interconnected with two IBRs—a 1-MW battery energy storage system (BESS) and a 430-kW solar photovoltaic (PV) plant—are presented. Both 0.5-Hz and 3-Hz oscillations become visible at certain conditions. The phenomenon is further explained by use of a feedback system consisting of the plant-level droop control and the effect of reactive power or var injection on voltage. The main components of the block diagram are obtained via frequency scan measurements. The analysis offers an understanding of the main contributors and other influencing factors of the 3-Hz and 0.5-Hz modes. It also reveals the role of the volt-var droop gain, the low-pass filter time constant, and the system impedance in stability.

14 SOLAR ENERGY↗

Electrolytic Renewable Fuel Production Optimal Operation Investigation - H2@Scale: Cooperative Research and Development Final Report, CRADA Number CRD-19-00818

This work explored the optimal design and operation of electrolytic hydrogen production from renewable power. While there are many financial incentives for renewable hydrogen, this work investigated the effects of Low Carbon Fuel Standards (LCFS) on the hydrogen breakeven cost. To this end, this project developed optimized operational strategies for electrolytic hydrogen facilities in the California. Four specific model projects were used as the basis for the analysis. Three model projects will be located in California and one in Texas or the Midwest to be determined during the project. All projects include interconnection to the natural gas grid as a method of transport for the product fuel and the hydrogen cases will also consider alternative modes of transport. The operational optimization will maximize project return through fuel production and grid services based on future scenarios for the value of each. The effort will rely on modeling tools developed by NREL and the UCI for grid modeling as well as the integrated resource planning tool (IRP), RESOLVE, which is the official IRP tool used by the California Public Utility Commission (CPUC). The development of this project can help to inform future hydrogen deployment, policy and regulation makers, research and development decisions, and private and public investment.

08 HYDROGEN↗

Eastern Interconnection Wide-Area Oscillation Assessment and Study Report

To meet the government mandates such as Renewable Portfolio Standards (RPS), conventional synchronous generators with rotating mass are being displaced by inverter-based resources (IBRs), leading to high penetration of renewable energy sources (RES). As a result, the inherent properties and characteristics of the transformed generation mix may significantly impact the grid behaviour, and it is of paramount significance that the impact and the consequences of the resource mix change is thoroughly understood to adopt measures to maintain reliable grid operations. Of great concern is the inter-area low-frequency oscillation, which usually propagates through a large region and has a system-wide impact. Such oscillations may lead to unnecessary or inadvertent tripping of generators, that may be simply reacting to the oscillation originating from geographically remote sites. Such tripping of generators can lead to cascading outages, system split and load loss events. Over the years, several system-wide oscillation events have been observed across all three North American interconnections. This project titled Wide-area Oscillation Assessment and Trending Study, sponsored by the Office of Electricity (OE) of the Department of Energy (DOE), aims to conduct the required research to capture and investigate the potential changes in wide-area oscillatory performance of the system as a result of resource mix transition. The Pacific Northwest National Laboratory (PNNL) conducted this research and technical staff of Federal Energy Regulatory Commission (FERC) served as advisors to the project. The primary objective of this study is to assess whether there are significant trends in the power system wide-area oscillatory behaviours, as a result of the generation-mix changes due to the increased penetration of RES in the U.S. Eastern Interconnection (EI). The analysis presented in this report can serve as reference for future grid planning and operation of the EI system. This research conducted in this project evaluates the wide-area oscillatory behaviour of the EI, using a model-based approach for potential future resource mixes, and the measurement-based analysis with 21-month phasor measurement unit (PMU) time series. The oscillation modes in EI system along with the impact of the changes of the generation mix on the frequency and damping ratio (DR) of the oscillations have been studied.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Architecture for Co-Simulation of Transportation and Distribution Systems with Electric Vehicle Charging at Scale in the San Francisco Bay Area

This work describes the Grid-Enhanced, Mobility-Integrated Network Infrastructures for Extreme Fast Charging (GEMINI) architecture for the co-simulation of distribution and transportation systems to evaluate EV charging impacts on electric distribution systems of a large metropolitan area and the surrounding rural regions with high fidelity. The current co-simulation is applied to Oakland and Alameda, California, and in future work will be extended to the full San Francisco Bay Area. It uses the HELICS co-simulation framework to enable parallel instances of vetted grid and transportation software programs to interact at every model timestep, allowing high-fidelity simulations at a large scale. This enables not only the impacts of electrified transportation systems across a larger interconnected collection of distribution feeders to be evaluated, but also the feedbacks between the two systems, such as through control systems, to be captured and compared. The findings are that with moderate passenger EV adoption rates, inverter controls combined with some distribution system hardware upgrades can maintain grid voltages within ANSI C.84 range A limits of 0.95 to 1.05 p.u. without smart charging. However, EV charging control may be required for higher levels of charging or to reduce grid upgrades, and this will be explored in future work.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Use of DAGMan in CRAB3 to improve the splitting of CMS user jobs

CRAB3 is a workload management tool used by CMS physicists to analyze data acquired by the Compact Muon Solenoid (CMS) detector at the CERN Large Hadron Collider (LHC). Research in high energy physics often requires the analysis of large collections of files, referred to as datasets. The task is divided into jobs that are distributed among a large collection of worker nodes throughout the Worldwide LHC Computing Grid (WLCG). Splitting a large analysis task into optimally sized jobs is critical to efficient use of distributed computing resources. Jobs that are too big will have excessive runtimes and will not distribute the work across all of the available nodes. However, splitting the project into a large number of very small jobs is also inefficient, as each job creates additional overhead which increases load on infrastructure resources. Currently this splitting is done manually, using parameters provided by the user. However the resources needed for each job are difficult to predict because of frequent variations in the performance of the user code and the content of the input dataset. As a result, dividing a task into jobs by hand is difficult and often suboptimal. In this work we present a new feature called “automatic splitting” which removes the need for users to manually specify job splitting parameters. We discuss how HTCondor DAGMan can be used to build dynamic Directed Acyclic Graphs (DAGs) to optimize the performance of large CMS analysis jobs on the Grid. We use DAGMan to dynamically generate interconnected DAGs that estimate the processing time the user code will require to analyze each event. This is used to calculate an estimate of the total processing time per job, and a set of analysis jobs are run using this estimate as a specified time limit. Some jobs may not finish within the alloted time; they are terminated at the time limit, and the unfinished data is regrouped into smaller jobs and resubmitted.

72 PHYSICS OF ELEMENTARY PARTICLES AND FIELDS↗

Developing IEEE Std 2800-Compliant Algorithms for Transmission-Connected Inverter-Based Resources: Preprint

This study addresses the compliance of Inverter-based Resources (IBRs) with the IEEE Std 2800, a leading standard that defines interconnection and interoperability requirements for IBRs integrated into transmission systems. Focusing on abnormal grid scenarios, the research evaluates the specific demands on IBRs, proposing a comprehensive controller development framework. This framework caters to maintaining ride-trhough operation or implementing strategic disconnections in line with IEEE Std 2800, alongside managing currents during voltage ride-through scenarios. The effectiveness of this proposed controller framework is rigorously validated through case studies, employing a MATLAB/Simulink model of an IBR to test its performance under diverse grid fault conditions, ensuring the IBRs' alignment with standard requirements and their robust performance in enhancing grid reliability.

IEEE Std 2800↗

Digital Assurance for Grid Reliability in the Era of Large Load Growth

The rapid expansion of large electric loads is reshaping the operational and regulatory landscape of the U.S. electric grid. These facilities are reaching new scales of expansion, now exceeding a gigawatt per site, and their highly sensitive, digitally driven behaviors introduce new reliability risks. Recent grid events, including large load losses following routine transmission disturbances, highlight the consequences of limited ride-through capability, inconsistent protection settings, inadequate modeling, and lack of behind-the-meter visibility. Parallels to earlier integration challenges of new grid technologies suggest that the grid’s existing processes, standards, and interconnection frameworks are no longer adequate for emerging large loads. This brief synthesizes lessons from the evolution of inverter-based resource regulation and applies them to large-load integration. It identifies critical gaps in modeling accuracy, interconnection processes, performance standards, and compliance mechanisms. Technical recommendations emphasize advanced monitoring, improved modeling, coordinated communication protocols, modernized substations, and structured behind-the-meter control schemes. Collectively, these measures provide a roadmap to maintain bulk power system reliability while enabling the continued growth of large, electrified digital infrastructure.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

Catalina Repower Feasibility Study: NREL Phases I & II Summary Report

Engineers at the National Renewable Energy Laboratory (NREL) supported Southern California Edison (SCE) and the United States Environmental Protection Agency (EPA) by conducting technical and economic analyses for energy systems at Santa Catalina (Catalina) Island, which is located 22 miles off the coast of Long Beach, California. This effort was part of a broader Repower Catalina Feasibility Study that was also supported by NV5, an engineering consulting firm and project partner to NREL for this analysis. This document describes NREL’s techno-economic modeling and optimization analysis for the first two phases of this project which focus on supply-side generation and energy storage options for Catalina. SCE’s goal for this analysis is to determine a strategy for electricity generation on Catalina Island that results in lower energy costs, improved energy resiliency, and reduced air emissions. EPA goals for this effort are to reduce emissions of air pollution and encourage renewable energy development on contaminated and formerly contaminated lands when such development is aligned with the community’s vision for the site. Currently, an on-island SCE power plant serves the Catalina Island electrical load with 6 reciprocating diesel generators totaling 9.4 MW; 23 propane-fueled microturbines totaling 1.5 MW; and a 1-MW, 7.2-MWh sodium sulfur battery energy storage system (BESS). In 2017, the electricity consumption on the island was 29.1 GWh, with an average load of 3.3 MW and peak load of approximately 5.5 MW. Considering new environmental standards on diesel generator emissions from California’s South Coast Air Quality Management District, a 60% renewable energy target for 2030 laid out in California’s Senate Bill 100, SCE’s Clean Power Electrification Pathway, and the characteristics of the island’s existing diesel generators, SCE is seeking to evaluate the technical and economic implications of different energy technology options to determine a path forward. Phases I and II of the Repower Catalina Feasibility Study, summarized in this document, evaluated the following: Interconnection with the mainland via an undersea cable; On-island fossil fuel generation, including diesel, propane, and/or liquified natural gas (LNG); On-island renewable energy (RE) technologies, including solar photovoltaics (PV), wind turbines, and wave energy devices; BESS to support the above generation technologies; Initial analysis of the potential impacts of implementing energy efficiency measures. Results indicate strong techno-economic potential for a mix of on-island diesel and/or propane generators, solar PV, BESS, and energy efficiency measures to help SCE and Catalina achieve their goals compliant with California’s emissions and clean energy standards while minimizing electricity life cycle costs (LCC) over the 30-year analysis period. This document summarizes the considerations and findings of Phases I and II, focusing on high-level takeaways from Phase I and more detailed results from Phase II, and discusses a potential path forward for Phase III.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Aggregation of Inverter-Based Resources for Modeling and Simulation

In order to conduct system dynamic studies, it is necessary to have dynamic models of both inverter and plant levels. Detailed and aggregated modeling approaches are two essential options. The detailed modeling method involves capturing the dynamic characteristics of each individual device (e.g., wind turbine or PV array), as well as their interconnections. However, as the scale of the IBR plant increases, the complexity and computation time required for detailed modeling also increase. On the other hand, aggregated modeling offers a more efficient way of representing large-scale IBRs in power system dynamic studies. This approach involves aggregating a large number of wind turbines, PV arrays, inverters, and/or plant controllers into one or a smaller number of equivalent models. In order to analyze the impact of a high-level IBR penetration in power systems, it is important to develop accurate and computationally efficient models for both the detailed and aggregated methods.

14 SOLAR ENERGY↗

Integration Study of Converter-Interfaced Combined Heat and Power Plants

Combined Heat and Power (CHP) systems, as a proven technology, provide numerous benefits to the plant owner by saving electricity bill, reducing carbon dioxide emissions, and improving electricity service reliability. However, their integration into the distribution grid faces many barriers including the complexity of grid code requirements and the lack of technical expertise in commercial and small industrial plants to interface with the utility and accelerate the interconnection process. To solve these issues, this study proposes a converter-interfaced solution for CHP integration. Simulations including various fault scenarios and load flow under different grid conditions are carried out to compare technical performances of the proposed solution with directly-coupled CHP. Results show that the generator size of converter-interfaced CHP can be reduced by approximately 25% and it also provides advantageous features such as reduced stress level under fault conditions and a better dynamic stability margin. In addition, a power factor controller is designed and reactive power from CHP is dispatched in such a way that the CHP plant is compliant with power factor requirements from utilities under all operating conditions.

Converter, Combined heat and power, Distributed en↗

Use of Power Hardware-in-the-Loop and Controller Hardware-in-the-Loop to De-Risk the Use Of Grid-Forming Fuel Cell Inverters in Microgrids

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such interfaces are particularly challenging when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This presentation shows the use of PHIL interfaces for such microgrids and the preliminary experimental results.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Uncertainty-Informed Operation Coordination in a Water-Energy Nexus

The widespread deployment of smart heterogeneous technologies and the growing complexity in our modern society calls for effective coordination of the interdependent lifeline networks. In particular, operation coordination of electric power and water infrastructures is urgently needed as the water system is one of the most energy-intensive networks, an interruption in which may quickly evolve into a dramatic societal concern. This paper develops a novel analytic for uncertainty-aware day-ahead operation optimization of the interconnected power and water systems (PaWS). Joint probabilistic constraint (JPC) programming is employed to capture the uncertainties in wind resources and water demand forecasts. The proposed integrated stochastic model is presented as a non-linear non-convex optimization problem, where the non-linear hydraulic constraints in the water network are linearized using piece-wise linearization technique, and the non-convexity is efficiently tackled with a solution methodology to convert the proposed model with JPCs to a tractable mixed-integer linear programming (MILP) formulation that can be quickly solved to optimality. Here, the suggested framework is applied to a 15-node commercial-scale water network jointly operated with a power transmission system using a modified IEEE 57-bus test system. The numerical results demonstrate the of the proposed stochastic framework, resulting in cost reduction (13% on average when compared to the traditional setting) and energy saving of the integrated model under different realizations of uncertain renewable energy sources (RESs) and water demand scenarios. Additionally, the scalability of the proposed model is tested on a modified IEEE 118-bus test system connected to five water networks.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grand Challenges of Hydrologic Modeling for Food-Energy-Water Nexus Security in High Mountain Asia

Climate-influenced changes in hydrology affect water-food-energy security that may impact up to two billion people downstream of the High Mountain Asia (HMA) region. Changes in water supply affect energy, industry, transportation, and ecosystems (agriculture, fisheries) and as a result, also affect the region's social, environmental, and economic fabrics. Sustaining the highly interconnected food-energy-water nexus (FEWN) will be a fundamental and increasing challenge under a changing climate regime. High variability in topography and distribution of glaciated and snow-covered areas in the HMA region, and scarcity of high resolution (in-situ) data make it difficult to model and project climate change impacts on individual watersheds. We lack basic understanding of the spatial and temporal variations in climate, surface impurities in snow and ice such as black carbon and dust that alter surface albedo, and glacier mass balance and dynamics. These knowledge gaps create challenges in predicting where and when the impact of changes in river flow will be the most significant economically and ecologically. In response to these challenges, the United States National Aeronautics and Space Administration (NASA) established the High Mountain Asia Team (HiMAT) in 2016 to conduct research to address knowledge gaps. This paper summarizes some of the advances HiMAT made over the past 5 years, highlights the scientific challenges in improving our understanding of the hydrology of the HMA region, and introduces an integrated assessment framework to assess the impacts of climate changes on the FEWN for the HMA region. The framework, developed under a NASA HMA project, links climate models, hydrology, hydropower, fish biology, and economic analysis. The framework could be applied to develop scientific understanding of spatio-temporal variability in water availability and the resultant downstream impacts on the FEWN to support water resource management under a changing climate regime.

54 ENVIRONMENTAL SCIENCES↗

Developing a Power Plant Suitability Model for the Energy Zones Mapping Tool

This report provides an example of designing, developing, and running a power plant suitability model in the Energy Zones Mapping Tool (EZMT), a public, web-based mapping tool with a large spatial database focused on energy infrastructure, energy resources, and related siting factors. The example focuses on natural gas combined cycle (NGCC) power plants, which have several unique and interesting characteristics. NGCC plants typically provide peaking power to the electrical grid. Such plants can be started or stopped relatively quickly and are often used to supplement base load plants (such as nuclear or coal) during times of peak electrical consumption or to counterbalance lulls in variable power generation (such as wind or solar). Due to these and other factors, NGCC plants have been projected to increase in number under energy planning studies such as Hadley et al. The scope of the Hadley et. al. study is the Eastern Interconnection (EI), the electrical transmission grid serving much of the United States and Canada east of the Rocky Mountains. Results in the study are organized according to 22 Multi-region National—North American Electricity and Environment Model (NEEM) regions within the EI. NGCC plants usually have lower water requirements than other thermoelectric power plants they may replace; therefore, they are expected to have an interesting role in reducing the overall water requirements of energy generation.

20 FOSSIL-FUELED POWER PLANTS↗

Emissions implications of downscaled electricity generation scenarios for the western United States

This study explores how emissions from electricity generation in the Western Interconnection region of the U.S. might respond in circa 2030 to contrasting scenarios for fuel prices and greenhouse gas (GHG) emissions fees. We examine spatial and temporal variations in generation mix across the region and year using the PLEXOS unit commitment and dispatch model with a production cost model database adapted from the Western Electricity Coordinating Council. Emissions estimates are computed by combining the dispatch model results with unit-specific, emissions-load relationships. Wind energy displaces natural gas and coal in scenarios with relatively expensive natural gas or with GHG fees. Correspondingly, annual emissions of NOx, SO2, and CO2 are reduced by 20-40% in these cases. NOx emissions, which are a concern as a precursor of ground-level ozone, are relatively high and consistent across scenarios during summer, when peak electricity loads occur and wind resources in the region are comparatively weak. Accounting for the difference in start-up versus stabilized NOx emissions rates for natural gas plants had little impact on region-wide emissions estimates due to the dominant contribution from coal-fired plants, but would be more important in the vicinity of the natural gas units.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modified Andronov-Hopf Oscillator-Based Grid-Forming Converter with Emulated Virtual Cable for Enhanced Power Sharing Performance

Nonlinear oscillator-based grid-forming converters offer superior dynamic and steady-state performance, making them an attractive solution for interconnecting renewable resources. This paper proposes a novel modified Andronov-Hopf oscillator to enhance the operating spectrum and facilitate the integration of renewable energy sources. An inner loop controller based on the Lyapunov energy function is implemented to achieve robust stability and performance, while a virtual cable emulation strategy enables seamless parallel operation. Comprehensive modeling and simulation studies validate the effectiveness of the proposed system, demonstrating its capabilities in addressing diverse operating scenarios, including grid faults, renewable energy fluctuations, and parallel operation. The proposed solution exhibits fast transient response, robust stability, and flexible operation, making it a valuable contribution to the field of renewable energy integration. The results of this study can be used to inform the design and implementation of next-generation grid-forming converters, enabling a more sustainable and reliable energy future. Additionally, the proposed system's ability to operate in both grid-connected and islanded modes makes it an ideal candidate for remote and off-grid renewable energy applications. The proposed solution's scalability and modularity also make it suitable for large-scale renewable energy integration. The proposed system is verified through MATLAB/Simulink and PLECS simulations, demonstrating its effectiveness in ensuring robust and efficient operation.

Andronov-Hopf Oscillator (AHO)↗

Voices from Rural Electric Cooperatives: A Call for a DER Integration Playbook for Rural and Agricultural Income & Savings from Renewable Energy (RAISE)

Rural-serving electric utilities (RSEUs)—including electric cooperatives, municipal systems, and small investor-owned utilities—are essential players in the evolving energy landscape. These community-focused entities are increasingly being asked to consider distributed energy resources (DERs) such as rooftop and ground-mounted solar, wind, battery storage, smart water heaters, and demand response programs (NRECA 2025; Lenhart et al. 2020). Yet the path to DER adoption is far from straightforward in the rural context. This report is based on in-depth interviews with managers of rural electric cooperatives across the United States. These conversations offer a grounded, unvarnished look at how DERs are perceived, what barriers exist, and what conditions might enable integration and adoption. While the utilities interviewed vary in geography, size, and DER experience, several clear and common themes emerged across electric cooperatives such that the report recommends the development of a DER Integration Runbook to help utilities assess readiness, define local use cases, engage stakeholders, pilot projects, and iterate, expanding over time.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Deep Factorization Machine Learning for Disaggregation of Transmission Load Profiles with High Penetration of Behind-The-Meter Solar

The ever-growing integration of distributed energy resources (DERs), especially behind-the-meter (BTM) solar generations, poses imperative operational challenges to system operators such as regional transmission organizations (RTOs). It is important for RTOs to effectively and accurately extract actual load profiles at the transmission level for a single node with significant BTM solar injection. This paper first illustrates the necessity of disaggregating the daily actual load profile of a single node. Furthermore, by segmenting nodes with selected timeseries features, nodes with significant BTM solar generation are identified. Lastly, a bi-level framework is proposed, comprising reference node disaggregation and DeepFM nodal disaggregation, aimed at disaggregating the nodal load profiles from which system operators require more information. By adopting a hybrid Deep Factorization Machine (DeepFM) model, the model achieve accurate results by extracting both linear and nonlinear relations between nodes in the same region and the zonal load and nodal load profile. To overcome the lack of ground truth, this paper segments the load profile into daytime, nighttime, and zero-crossing points and utilizes the latter two for evaluation purposes. The proposed disaggregation procedure is validated using real world, minute-level, normalized, and anonymized nodal data in the PJM service territory.