Utilization of Battery Electric Buses for the Resiliency of Islanded Microgrids
Not provided.
SEARCH · Search NASA
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
Not provided.
Virtual-inertia and droop control methods are commonly used for grid-forming inverters. While the virtual inertia is used to emulate the equation of motion/frequency, if the inverter output voltage is emulated as in synchronous generators, then the method is known as the virtual synchronous generator. An inductive pulse-load, e.g., a relatively large induction motor, connection to a microgrid fed only by grid-forming inverters may lead to blackout due to high inrush currents. This article presents virtual reactance techniques to mitigate the inrush current effects and enhance the inverter’s robustness for the safe connection of inductive and dynamic loads. This article also compares the virtual inertia and droop control methods under switching inductive-dynamic loads while the proposed techniques are implemented. Experimental tests are performed considering the linear and nonlinear virtual reactance techniques, and the findings are discussed. The mitigation significantly suppresses the inrush currents while the inverters can perform a normal operation. Furthermore, the frequency and power response of the virtual inertia control with different inertia settings to a sudden change in the load is analyzed. The virtual reactance technique is tested in a laboratory-scale hardware setup of a 208V microgrid fed by 5kVA and 10kVA inverters, and the results are presented in this article.
Grid-forming inverters in a microgrid may trip due to high inrush current caused by a switched connection of an inductive load, e.g., a relatively large induction motor. The control scheme presented in this article includes virtual inertia control method superimposed on the cascaded controller. This article studies the impact of cascaded control scheme used for grid-forming inverter to mitigate the inrush current effects and enhance the inverter’s robustness for the safe connection of inductive and dynamic loads. Experimental tests are performed using the virtual inertia method for generating the reference angle for synchronous frame conversion. The experimental performance and sensitivity of the controller to different controller gain settings for a switched connection of an induction motor are discussed. The cascaded operation significantly mitigates the inrush currents while the inverters can perform a normal operation. The performance of the control method is tested in a laboratory-scale hardware setup of a 208V microgrid fed by 5kVA and 10kVA inverters, and the results are presented.
Not provided.
Not provided.
Abstract not provided.
Abstract not provided.
Abstract not provided.
This paper presents a universal controller to reduce the transient current during islanding of microgrid. In the proposed universal controller, two sets of semi-parallel paths are formed, where one set produces voltage and phase-angle references for the grid-following (GFL) mode, and the other set produces the voltage and phase-angle references for the grid-forming (GFM) mode of operation for the inverters. Herein, the controller enables an inverter to universally operate in GFL and GFM mode, whereas, only one set of voltage and phase-angle reference is engaged for PWM signal generation. When the microgrid is disconnected from the grid, the universal controller switches the voltage and phase-angle references from GFL to GFM mode. The proposed controller ensures lower transient current by keeping the two sets of semi-parallel paths synchronized throughout the operation of the inverter and enabling seamless transition between the modes. The proposed controller is verified through hardware experiments under different scenarios in a laboratory scale microgrid for inverters transitioning from GFL to GFM mode after islanding.
Microgrid connected building communities are projected to play an integral part in the clean energy transition. These types of systems, when integrated with distributed energy resources (DERs) such as combined heat and power (CHP), district heating and cooling, renewable generation, and energy storage, can provide clean, reliable power to critical facilities and vulnerable communities. The intermittent nature of renewable generation is a challenge when integrating renewables into any grid system, but particularly in islanded microgrids. The University of Texas at Austin (UT) operates an islanded microgrid powered by a CHP plant, while also utilizing district heating and cooling systems and thermal energy storage (TES). High fidelity operating data was used to develop a validated reduced order model of UT’s integrated campus energy systems to serve as a testbed for use in a case study. Hypothetical renewable energy installations on land owned by UT in west Texas were modeled and integrated into the validated campus models along with battery energy storage (BES). Simulations showed that a combination of renewable energy from wind, and optimally controlled 24-hour thermal and battery storage systems could reduce carbon dioxide emissions on campus by 45.4%. The additional retrofit of burner systems to utilize hydrogen natural gas blends resulted in an overall annual emissions reduction of 54.7%. Carbon capture and storage eliminated the majority of the remaining emissions with increased plant energy expenditure. The presented simulations display the practical limitations of a CHP system complemented by renewable generation and short-term storage in eliminating emissions. Furthermore, results highlight the need for further research and development in long duration storage technologies and hydrogen fueled turbines to increase penetration of renewable energy and reduce emissions.
Islanding sections of a distribution grid as microgrids and networking these microgrids offer promising opportunities for improving system reliability; however, this approach may need distributed energy resources (DERs) to switch between grid-connected and islanded operation without affecting the system stability. The Thevenin impedance of the power system at the DER point of common coupling changes due to networking actions. It is critical to have smooth transitions between modes to ensure stable system operation and to avoid nuisance tripping. This paper presents the design of a grid-forming (GFM)-capable inverter control scheme to reliably operate in distribution systems with networked microgrids. Control mechanisms for smooth transitions between grid-following (GFL) and GFM inverter modes are presented. First, we test the control mechanism on a simple two-source power system through electromagnetic transient (EMT) simulations using a digital real-time simulator. Then, we add multiple such DERs to the EMT model of a real-world distribution feeder and demonstrate stable operation between mode transitions during the networking of the microgrids.
Unintentional islanding (UI) of a circuit of distributed energy resources (DERs) may leave area electrical power systems (EPS), external to the DER circuit, energized. Thus, UI detection methods have been developed to detect unintentional islanding and trigger a UI response. However, individual UI detection methods have various deficiencies. Thus, a consensus-based UI detection process is disclosed that builds a consensus from multiple UI detection sources, optionally implementing different UI detection methods. The redundancy in this consensus-based UI detection process provides robust, sensitive, selective, and cybersecure UI detection for the entire DER circuit. For example, the consensus-based UI detection process may eliminate or reduce non-detection zones, avoid false positives, thwart cyber-attacks, and/or the like.
An islanded microgrid can be used to serve critcal load as a resiliency source when a severe outage occurs. In an islanded mode, control of a microgrid relies on the communication system significantly. Hence, microgrids are cyberphysical systems and, therefore, the cyber system plays a crucial role in the performance of the cyber-power system. A microgrid control scheme is proposed for power dispatch and regulation based on the droop and proportional-integral (PI) feedback control. The proposed control strategy is validated for transient stability following dynamic events. To evaluate the impact of a networked control system on control performance, a cyber model is developed to represent data acquisition periods and communication delays. An analytical method is proposed to determine the critical values for the data reporting periods and communication delays. The analytical method based on a state space model of a networked control system is applicable for large-scale systems. A 2-dimensional stability region of a microgrid in the space of cyber parameters can be obtained by the proposed method, and the critical values of cyber parameters are determined based on the stability region. Simulation results validate that the design of a microgrid as a cyber-physical system needs to be guided by critical values for the data reporting period and communication delay to prevent system instability.
San Diego Gas & Electric Company (SDG&E) installed America’s first and largest utility-scale microgrid in Borrego Springs in 2013. The first generation Borrego Springs Microgrid utilized diesel generators to form and stabilize the microgrid island, with support from grid-scale batteries and local solar photovoltaic (PV) generation. In this project, SDG&E in partnership with National Renewable Energy Laboratory (NREL) demonstrated through modeling, simulation and utility field testing that blackstart and islanding of the microgrid can be led with 100% renewable, inverter based resources (IBRs), to help reduce community reliance on conventional generation resources. Through equipment upgrades, grid-forming island leader capability was transitioned to a battery IBR instead of the Borrego Springs Microgrid diesel generators. A new microgrid controller was integrated to the microgrid and programmed to control and manage multiple energy storage systems. Synchrophasor and other power quality data verified autonomous, high-speed response of the IBRs through blackstart, islanding, and load step testing. Results of project field evaluations provide distribution systems operators (DSO) with increased confidence that renewable, IBR can replace traditional generators to blackstart and island microgrids and rapidly establish stable island frequency with rapid changes in peak power demand. Importantly, the project validated the integration feasibility of a distributed energy resource management system (DERMS) controller that manages multiple grid-forming and grid-following IBRs, establishing a standard design interface to reduce the complexity of integrating new DERs in the future and supporting replication by the industry. As a result of learnings in this project, SDG&E has implemented the microgrid controller strategy at multiple other microgrid sites, thereby validating the replicability of the solution. Hardware-in-the-loop (HIL) simulations including power and controller HIL hardware — along with electromagnetic transient (EMT) simulations of Borrego Springs Microgrid —informed adjustments to inverter parameters and were important to characterize the performance of the IBRs in relevant operating conditions before deployment. The EMT and HIL simulations of islanding the entire community are important contributions in providing confidence in IBR performance prior to future islanding of the community in the field. High-fidelity EMT and/or HIL simulation of IBRs can de-risk field operations, and its relevance and importance as a tool is increasing as distribution grids and microgrids become more complex and dynamic with an increasing proportion of renewable generation, distributed energy storage, and two-way power and energy flows.
This paper develops improved control strategy of GFM inverter with fault ride-through (FRT) capabilities to guarantee stable operation of microgrid under fault conditions especially islanded microgrid and asymmetrical faults. The proposed control strategy includes dual control of positive-sequence and negative-sequence control, and the adaptive virtual impedance (VI) control. Unlike the existing works, the proposed strategy only applies the VI control for the d-component of the positive-sequence control and leaves the q-component of positive-sequence control and dq-component of negative-sequence control zero, thus achieving the improved stability and balanced three-phase voltage under asymmetrical faults. The adaptive feature of the VI control guarantees the stability of the GFM inverter under severe faults which could cause saturated inner current loop and instability if the VI is not adaptive. Simulation results of a phase-to-phase-ground fault show that the proposed control strategy improves the stability of GFM and achieves the stable and balanced output voltages in islanded microgrid.
This paper develops an improved control strategy of grid-forming (GFM) inverters with fault ride-through capabilities to guarantee the stable operation of microgrids under fault conditions, especially islanded microgrids and asymmetrical faults. The proposed control strategy includes the dual control of positive-sequence and negative-sequence control as well as the adaptive virtual impedance (VI) control. Unlike existing works, the proposed strategy applies the VI control for only the d component of the positive-sequence control and leaves the q component of the positive-sequence control and the dq component of the negative-sequence control as zero, thus achieving improved stability and balanced three-phase voltages under asymmetrical faults. The adaptive feature of the VI control guarantees the stability of the GFM inverter under severe faults, which could cause the saturation of the inner current loop and instability if the VI is not adaptive. Simulation results of various unbalanced faults with high- and low-fault impedances show that the proposed control strategy improves the stability of the GFM inverter and achieves stable and balanced output voltages in islanded microgrids. And the algorithm also improves the stability of GFM inverters under balanced faults with high- and low-fault impedances.
This paper develops an improved control strategy of grid-forming (GFM) inverters with fault ride-through (FRT) capabilities to guarantee the stable operation of microgrids under fault conditions, especially islanded microgrids and asymmetrical faults. The proposed control strategy includes the dual control of positive-sequence and negative-sequence control as well as the adaptive virtual impedance (VI) control. Unlike existing works, the proposed strategy applies the VI control for only the d component of the positive-sequence control and leaves the q component of the positive-sequence control and the dq component of the negative-sequence control as zero, thus achieving improved stability and balanced three-phase voltages under asymmetrical faults. The adaptive feature of the VI control guarantees the stability of the GFM inverter under severe faults, which could cause the saturation of the inner current loop, and the instability if the VI is not adaptive. Simulation results of various unbalanced faults with high and low fault impedances show that the proposed control strategy improves the stability of the GFM inverter and achieves stable and balanced output voltages in islanded microgrids. And the algorithm also improves the stability of GFM inverters under balanced faults with high and low fault impedances.