Search NASA⌕ Search

SEARCH · Search NASA

Results for “ride-through”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

Frequency Support From Electric Vehicles for Advancing Renewable Energy Integration

The integration of renewable energy resources (RERs) in the modern power grid is increasing rapidly because of aggressive decarbonization goals, lower costs, and increased government investment. However, higher penetrations of inverter-based generation can lead to frequency stability issues because of reduced system inertia. This paper develops a framework for quantifying the contribution of electric vehicles (EVs) toward providing frequency support to the grid and thus increasing the penetration limit of renewable energy resources (RERs). EVs are considered to provide both inertial response and primary frequency response support to the grid. A stochastic approach incorporating the uncertainties associated with the behavior of EVs is developed to derive the discharge limit of EV aggregators. A multi-machine system frequency response (MM-SFR) model is developed, which incorporates the dynamic virtual inertia and droop coefficients of EV aggregators derived from the EV control modules. Frequency security constraints are developed from this MM-SFR model, which, along with the converter voltage security and low voltage ride-through constraints, are integrated within a nonlinear optimization framework to determine the RER integration limit. Here, the efficacy of the proposed approach is validated using the RTS-GMLC test system.

25 ENERGY STORAGE↗

EMT data generation

The integration of inverter-based resources (IBRs) in power systems is accelerating, bringing with it significant benefits such as reduced greenhouse gas emissions, improved grid resilience, and increased energy independence. Despite these advantages, the widespread adoption of IBRs introduces several challenges, including issues related to grid stability, increased operational complexity, and the need for updated regulatory frameworks. To address these challenges, IEEE released Standard 2800 in 2022, which sets forth the necessary interconnection capabilities and performance criteria for IBRs connected to transmission and sub-transmission systems. This standard outlines the performance requirements to ensure the reliable integration of IBRs into the bulk power system. Furthermore, in 2023, the North American Electric Reliability Corporation (NERC) published a reliability guideline for electromagnetic transient (EMT) modeling of BPS-connected IBRs. This guideline provides recommendations for developing EMT model requirements, performing model quality checks, and implementing verification practices specifically for EMT models representing BPS-connected inverter-based resources in reliability studies conducted by transmission planners and planning coordinators. These standards and guidelines have a profound impact on EMT studies for transmission networks, influencing system stability analyses, grid recovery and resynchronization processes, fault ride-through evaluations, protection and coordination strategies, advanced control methodologies, and the inclusion of IBRs in transient models of transmission networks. As a result, the generation of EMT data is crucial for conducting various transient-based studies to understand the impact of IBRs. EMT data generation use cases serve as the basis for scenarios in event detection and identification use cases, providing comprehensive details about EMT data generation for transmission grids with inverter-based resources. These use cases supply sufficient training and validation datasets for subsequent EMT analysis algorithms.

Xia, Qianxue↗

Providencia Island White Papers: Overview of Technical Requirements for Interconnection

This issue brief provides an overview of key technical requirements for inverter-based resources - including distributed energy resources (DERs) - to support the reliable and safe operation of the Providencia Island electrical grid, and other island or isolated area mini-grid applications. With the planned increase in inverter-based resources and the introduction of energy storage, adopting Institute of Electrical and Electronics Engineers (IEEE) Std 1547-2018, including the more advanced performance capabilities for voltage and frequency ride-through, will simplify interconnection as well as help to maintain a safe, reliable grid on Providencia Island.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Interconnection of Distributed Energy Resources in the Indian Context: IEEE 1547-2018 Adaptation for Locally-Appropriate Grid Code Development

The rapid growth of distributed energy resources (DERs) in India and ambitious renewable energy goals set forth by the Indian government have created the need for appropriate distribution interconnection standards to ensure continued system stability, reliability, and resilience. Existing DER interconnection codes in India, at the time of publishing this report, lack many of the critical grid support functionalities for DERs which may protect bulk system stability, such as event ride-through provisions, frequency droop control, or appropriate trip thresholds given the increasing importance of distributed generation. The formal adoption of IEEE 1547-2018 by the Bureau of Indian Standards (BIS) marks a significant step towards achieving appropriate interconnection of DERs, though the implementation of such a standard must be accompanied with careful consideration of the current codes, regulations, and operation of the Indian power system. Studies on the performance of the functionalities within 1547-2018, which properly incorporate local operating conditions, can inform decisions related to the adoption and adaptation of the clauses present in the standard. This report outlines several of these key considerations for stakeholders and provides analyses illustrating the performance of grid support functionalities on typical Indian distribution feeders.

1547↗

Bill Savings vs. Backup Power: Evaluating operational tradeoffs for home solar+storage systems [Slides]

This study explores tradeoffs between the use of home solar+storage systems for backup power versus day-to-day utility bill savings. The study focuses specifically on the “reserve setting” available with most home battery storage systems, which allow the customer to maintain some minimum level of storage in reserve in case of an unforeseen power interruption. The more capacity that is held in reserve, the greater the customer’s ability to ride-through possible power interruptions, but less capacity is then available to manage utility bills on a day-to-day basis. This study evaluates this operational tradeoff across a diverse set of locations and residential electricity tariff structures, relying on Berkeley Lab’s PRESTO model to stochastically simulate power interruption events, and exploring a range of sensitivities, including variations in customer value of lost load (VoLL), interruption frequency, and other key drivers. The results show that, in most circumstances, the opportunity cost of holding storage capacity in reserve, in terms of foregone bill saving, tends to outweigh any gains in reliability value associated with mitigated power interruptions. This finding is robust across tariff structures and across most of the sensitivities considered, including those related to rate level, customer load level, and storage sizing. There are a limited set of circumstances where raising the reserve setting improves the overall customer value (comprised of bill savings plus reliability value). Specifically, that exception occurs when all of the following conditions apply: (a) the customer resides in a location with exceptionally poor reliability, (b) the customer has exceptionally high VoLL; (c) the customer is on a net billing rate or on a TOU rate that allows grid discharging but not grid charging; and (d), depending on the location, the price arbitrage differential on that rate is relatively small. In all other circumstances analyzed, total customer value declines with reserve level.

14 SOLAR ENERGY↗

Digital Assurance for Grid Reliability in the Era of Large Load Growth

The rapid expansion of large electric loads is reshaping the operational and regulatory landscape of the U.S. electric grid. These facilities are reaching new scales of expansion, now exceeding a gigawatt per site, and their highly sensitive, digitally driven behaviors introduce new reliability risks. Recent grid events, including large load losses following routine transmission disturbances, highlight the consequences of limited ride-through capability, inconsistent protection settings, inadequate modeling, and lack of behind-the-meter visibility. Parallels to earlier integration challenges of new grid technologies suggest that the grid’s existing processes, standards, and interconnection frameworks are no longer adequate for emerging large loads. This brief synthesizes lessons from the evolution of inverter-based resource regulation and applies them to large-load integration. It identifies critical gaps in modeling accuracy, interconnection processes, performance standards, and compliance mechanisms. Technical recommendations emphasize advanced monitoring, improved modeling, coordinated communication protocols, modernized substations, and structured behind-the-meter control schemes. Collectively, these measures provide a roadmap to maintain bulk power system reliability while enabling the continued growth of large, electrified digital infrastructure.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

Transient Stability Study of IEEE 2800-2022 Standard Negative-Sequence-Current Compliant GFM IBRs

The primary function of grid-forming (GFM) inverter-based resources (IBRs) is to maintain voltage and fre- quency/phase angle stability; however, during unbalanced grid faults, IEEE Std. 2800-2022 requires IBRs to inject both positive- and negative-sequence reactive current. Enforcing compliance with this standard could compromise the stability of GFM IBRs under such fault conditions. This paper presents a preliminary transient stability study focused on the power angle stability of GFM IBRs operating in compliance with IEEE Std. 2800 during unbalanced faults. The goal is to assess potential stability issues associated with the standard's current injection requirements under fault ride-through conditions. The results show that injecting positive-sequence current with d-axis priority during unbalanced faults better preserves the power angle stability than the q-axis priority while still enabling negative-sequence current injection. These findings suggest that, to ensure stability, GFM IBRs might need to partially comply with IEEE Std. 2800 by prioritizing positive-sequence current injection along the d-axis.

14 SOLAR ENERGY↗

Studying the Impact of Momentary Cessation of IBRs Compliant With IEEE Std. 2800-2022 on Transmission Line Protection Elements

This paper examines the impact of inverter-based resource (IBR) momentary cessation timing on transmission system protection relays. IEEE Std. 2800 mandates voltage ride-through, requiring IBRs to remain online during voltage disturbances. However, for severe voltage dips (|V| = 0.1 p.u.), the standard permits current blocking. In practice, vendors implement momentary cessation with varying delays, potentially affecting relay operation if IBRs cease too early. This article studies the impact of the time IBRs enter momentary cessation on transmission line protective relays. Using an electromagnetic transient (EMT) simulation, this study models IBR momentary cessation with tunable delays in a realistic transmission network. COMTRADE files generated from EMT simulations are analyzed in MATLAB using detailed protective relay models. Results indicate that IBRs must sustain operation for at least one cycle to ensure proper relay response; otherwise, relays may fail to oper- ate. These findings guide IBR vendors in optimizing momentary cessation settings to enhance transmission line protection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Summary of GFL Inverter Capability and Performance: Malawi [Slides]

This presentation provides a comprehensive comparison of inverter-based resource (IBR) technical requirements across multiple international grid codes - including IEEE 2800, ESO, EirGrid, and Malawi's evolving regulatory framework - to support capacity building for electricity-sector institutions in Malawi. It highlights key performance expectations for grid-following (GFL) inverters across critical domains such as primary and fast frequency response, ramping behavior, frequency and voltage ride-through capabilities, reactive power and voltage control, ROCOF withstand, phase jump tolerance, system strength considerations, protection schemes, and dynamic modeling requirements. Emphasizing a "Do no harm, do something, do more" philosophy, the document synthesizes best practices and operational benchmarks to guide the integration and stability of inverter-based resources within Malawi's power system. The presentation forms part of the SABESS Center of Excellence initiative supported by the Global Energy Alliance for People and the Planet.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Advanced-Research-on-Integrated-Energy-Systems-Based Analysis to Support Resilient System Upgrades: Energy to Communities Energyshed In-Depth Partnership with Molokai, Hawaii

The Molokai, Hawaii, Energy to Communities (E2C) Energyshed project represents a collaborative effort between the National Laboratory of the Rockies, Shake Energy Collaborative, the Molokai Clean Energy Hui, Sustainable Molokai, and Ho'ahu Energy Cooperative Molokai to advance Molokai's Community Energy Resilience Action Plan (CERAP). Supported by Hawaiian Electric Company and the Hawaii State Energy Office, the initiative aims to develop a community-defined portfolio of renewable energy solutions that enhance energy resilience while aligning with the Hawaiian Electric Integrated Grid Plan (IGP) and Molokai's energy goals. Phase 1 focused on technical analyses and community engagement to co-design feasible energy scenarios. Challenges such as grid upgrades, storage sizing, and inverter ride-through standards were addressed to align technical and operational requirements with community preferences. The project equips Molokai with actionable data and insights to implement energy initiatives while ensuring resilient and culturally informed solutions. Future efforts aim to finalize project designs, secure interconnection agreements, and deploy energy projects that reflect community priorities and technical feasibility.

24 POWER TRANSMISSION AND DISTRIBUTION↗

PV Inverter Testing for Momentary Cessation and Rate-of-Change-of-Frequency Events: Preprint

To understand the power system stability and develop better electromagnetic transient (EMT) models of field deployed photovoltaic (PV) inverters, it is important to characterize inverters' response to abnormal voltage and frequency scenarios. Because EMT models are not typically available for small distribution-connected PV inverters, and because inerterconnection standards historically did not specify desired ride-through behaviors, we tested two such inverters in the lab to characterize their responses to severe undervoltage events and high rate-of-change-of-frequency (ROCOF) conditions. The inverters tested were pre-IEEE 1547-2018 residential PV inverters widely used in the Hawaiian Electric territory and many other areas. The testing results for undervoltage scenarios showed that the inverter from one vendor exhibited momentary cessation while the inverter from the other vendor did not exhibit momentary cessation behavior or tripping for most of the events below the 120 ms undervoltage trip threshold duration set by IEEE 1547-2003. The testing results for ROCOF scenarios showed that the inverter from one vendor temporarily lost synchronization during ROCOF conditions while the inverter from the other vendor did not lose synchronization or cease generation for any ROCOF conditions. Both the inverters were also tested for EMT-simulated grid events with severe changes in frequency and voltage. The observed responses of the inverters were different from the simulated response of PV inverters represented the best available assumptions from pre-existing information. The results from these experiments can be used to update the inverter models used in bulk power system studies.

IEEE 1547 2018↗

Developing IEEE Std 2800-Compliant Algorithms for Transmission-Connected Inverter-Based Resources: Preprint

This study addresses the compliance of Inverter-based Resources (IBRs) with the IEEE Std 2800, a leading standard that defines interconnection and interoperability requirements for IBRs integrated into transmission systems. Focusing on abnormal grid scenarios, the research evaluates the specific demands on IBRs, proposing a comprehensive controller development framework. This framework caters to maintaining ride-trhough operation or implementing strategic disconnections in line with IEEE Std 2800, alongside managing currents during voltage ride-through scenarios. The effectiveness of this proposed controller framework is rigorously validated through case studies, employing a MATLAB/Simulink model of an IBR to test its performance under diverse grid fault conditions, ensuring the IBRs' alignment with standard requirements and their robust performance in enhancing grid reliability.

IEEE Std 2800↗

EMT Model Validation of a 2 MVA PV Inverter Using Transient and Frequency-Domain Hardware Testing: Preprint

This paper presents results and new insights gained from a hardware test campaign on a 2 MVA PV inverter for validating its vendor-supplied EMT model. The test campaign was conducted using a 7 MVA grid simulator and a 2 MW PV emulator. It considered both time-domain transient tests and frequency-domain impedance scan tests. The paper highlights the inadequacy of transient tests in capturing all critical resonance modes of the inverter, and the effectiveness of the frequency scan testing in addressing this problem. The paper shows the frequency scan testing as an effective tool for EMT model validation of IBR units which can highlight inaccuracies in the EMT models that are easy to overlook when model validation is performed using only the time-domain transient tests such as voltage ride-through and phase jump tests.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Enabling Grid-Forming Control Under Unbalanced Conditions

Standalone microgrids often experience unbalanced loading and faults, which can cause grid-forming control designed for balanced conditions to produce oscillatory responses. To address this issue, a compact time-domain transformation appropriate for inverter control is proposed, allowing the conversion of unbalanced three-phase signals to positive and negative synchronous reference frames. This transformation supports the development of a grid-forming control with fault ride-through, featuring frequency and voltage droop controllers and nested current and voltage control loops that seamlessly integrate an enhanced current limiter. The effectiveness of the proposed control and transformation is demonstrated through analytical results and electromagnetic transient simulation.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

Small-Signal Stability of Grid-Forming Inverters Using Current-Limiting and Frequency Stabilization

This paper presents a small-signal stability analysis of grid-forming (GFM) inverters under current-limiting conditions. It examines how adjustments in virtual impedance angles, implemented through advanced current-limiting and frequency stabilization techniques, influence small-signal stability. This paper studies a GFM inverter control integrating a fictitious power technique stabilizing primary control by adding a virtual power term and a hybrid current limiter integrating virtual impedance in the anti-wind-up feedback with current reference saturation limiting. A small-signal model is developed to assess the impact of virtual impedance angles on GFM inverter dynamics during grid disturbances, such as voltage drops. The findings indicate that although increasing the virtual impedance angle (to make it more inductive) enhances large-signal stability and voltage support during faults, it can induce oscillations and lead to instability if the angle exceeds certain thresholds. Based on the small-signal models, this paper provides design considerations for the current-limiter impedances to ensure reliable GFM inverter behavior under grid disturbances while maintaining small-signal stability.

current limiting↗

Searching for Grid-Forming Technologies That Do Not Impact Protection Systems: A promising technology

The design of legacy-line protection elements has been guided by the behavior of synchronous machines during faults. Because of the significant field-winding inductance and rotating mass, the magnitude, angular frequency, and phase angle of the back-electromotive force (EMF) voltage waveforms of synchronous machines remain practically constant for several hundreds of milliseconds after a fault occurs. Furthermore this has facilitated the engineering of the memory-polarization technique in mho distance elements, which has been effective for machine-dominant power grids. However, this assumption is no longer held for inverter-based resources (IBRs) because of the lack of field winding and moment of inertia in power electronics devices. Notably, the negative-sequence directional overcurrent protection and the quadrilateral distance elements have been impacted by early IBRs with grid-following (GFL) controls because they did not inject negative-sequence currents during asymmetrical faults.

24 POWER TRANSMISSION AND DISTRIBUTION↗