Search NASA⌕ Search

SEARCH · Search NASA

Results for “microgrids”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 397 records · Page 22

Modeling of Microgrid for Critical Data Center Applications

As part of continuing efforts to develop support, understanding, and infrastructure of data center integration onto the electric grid, our work aims to model and analyze the behavior of data center loads in a microgrid power system. Our model consists of renewable energy sources, batteries, and a nuclear reactor-steam Rankine cycle to power data center loads. The simulation studies investigate the electrical behavior of the microgrid system to assess its ability in supporting large data center electrical demands.

14 - SOLAR ENERGY↗

Droop-Free Distributed Control for AC Microgrids

In this chapter, droop-free distributed control for AC microgrids is discussed. The hierarchical structure of microgrid control is first introduced. Secondary level controls both with and without droop are discussed. Then two droop-free distributed controls are presented: one achieves average voltage regulation and perfect power sharing, and the other one achieves average voltage regulation, voltage variance regulation, and relaxed reactive power sharing. For the latter droop-free control, the relaxed reactive power sharing is achieved through a special distributed generator (DG) that will not participate in reactive power sharing.

Mohiuddin, Sheik Mohammad↗

A physics‐informed learning technique for fault location of DC microgrids using traveling waves

Abstract Fast and accurate fault location in DC power systems is of particular importance to ensure their reliable operation. One of the approaches for implementing a fast‐tripping protection scheme is to use Traveling waves (TW) initiated by a fault scenario. This paper proposes a physics‐informed machine learning approach that utilizes TWs for fault location in DC microgrids. TWs are extracted by the so‐called multiresolution analysis which identifies the TW's wavelet coefficients for multiple frequency ranges. This paper deploys Parseval's theorem to find the energy of wavelet coefficients as a quantitative metric for describing TWs. The hypothesis of this paper is that once the Parseval energy curves for a specific cable are extracted, they can be utilized to locate faults along with that cable regardless of the DC system in which the cable is deployed. The fault location algorithm uses Parseval energy curves to train a Gaussian Process (GP) estimator. With the Parseval energy values of measured current at the protection device location, the GP estimator is able to estimate fault locations with high accuracy. The effectiveness of the proposed algorithm is verified by simulating a DC microgrid system in PSCAD/EMTDC.

Paruthiyil, Sajay Krishnan↗

Control coordination in inverter‐based microgrids using AoI‐based 5G schedulers

Abstract A coordinated set point automatic adjustment with correction enabled (C‐SPAACE) framework that uses 5G communication for real‐time control coordination between inverter‐based resources (IBR) in microgrids is proposed. Utilising slicing capability, 5G offers low‐latency communication to C‐SPAACE under normal conditions. However, given the multitude of power grid use cases, a certain 5G slice for C‐SPAACE may have access only to limited radio spectrum resources, which if not managed well, greatly undermines the communication needs of C‐SPAACE framework. Thus, optimally scheduling the available spectrum resources among IBRs in a sliced 5G network‐based C‐SPAACE framework becomes a critical problem. To address this issue, the authors utilise a novel age of information (AoI) metric and designs an AoI‐based 5G scheduler to provide low‐latency communication to C‐SPAACE. Following this, a co‐simulation environment is designed using PSCAD/EMTDC and Python to simulate a microgrid supported by 5G communication. Time‐domain simulation case studies are performed using the proposed co‐simulation environment to evaluate the performance of C‐SPAACE using 5G with both AoI‐based and other baseline (non‐AoI) schedulers.

Choudhury, Biplav↗

Travelling wave‐based fault detection and location in a real low‐voltage DC microgrid

Abstract This paper discusses a device‐level implementation of a travelling wave (TW) protection device (PD) designed for a real low‐voltage DC microgrid. The TWPD fault detection and location algorithm is executed on a commercial digital signal processor (DSP) board, involving signal sampling at 1 MHz via the DSP board's analog‐to‐digital converter (ADC). The analogue input card measures positive pole, negative pole and pole‐to‐pole voltages at the TWPD location. Upon a successful fault detection using a second‐order high‐pass filter, the voltage data is normalised and multi‐resolution analysis (MRA) is performed on a 128‐sample buffer around the TW arrival time. MRA employs the discrete wavelet transform (DWT) to capture high‐frequency voltage patterns, and then the Parseval's energy theorem quantifies these TW characteristics by computing the energy of reconstructed wavelet coefficients. These energy values per decomposed frequency band are the basis for training a random forest classifier that predicts fault location and type. The TWPD is fully implemented and connected to a real DC microgrid in Albuquerque, NM, USA, for validation, and results are shown for field tests verifying the performance under faults.

Paruthiyil, Sajay Krishnan [Department of Electric↗

Rotated-Droop Control for Enhanced Stability and Power Decoupling in Microgrids With Complex Line Impedances

Classical droop control in microgrids predominantly assumes inductive line impedance, which simplifies implementation but causes power coupling and steady-state errors in systems with resistive and inductive lines. This paper proposes a rotated-droop control strategy for grid-forming inverters that reformulates the power equations by incorporating the magnitude and angle of the line impedance within a rotated reference frame. This method enhances the decoupling of active and reactive power dynamics without increasing complexity or requiring communication links. A small-signal state-space model was created to capture the dynamic behavior of the system under varying impedance parameters, preserving the original droop gains by rotating the power control structure. This allows eigenvalue-based stability analysis and enhances damping and transient performance. Simulation and experimental results validated the improved power-sharing performance, faster response, and robustness of the proposed method under different impedance conditions. This approach maintains the decentralized structure of the conventional droop control while enabling greater adaptability and scalability, making it suitable for modern inverter-based microgrids with dynamic topologies.

Campo-Ossa, Daniel Dario [Univ. of Puerto Rico, Ag↗

Inrush Current Mitigation for Grid-Forming Inverters in Islanded Microgrids

Virtual-inertia and droop control methods are commonly used for grid-forming inverters. While the virtual inertia is used to emulate the equation of motion/frequency, if the inverter output voltage is emulated as in synchronous generators, then the method is known as the virtual synchronous generator. An inductive pulse-load, e.g., a relatively large induction motor, connection to a microgrid fed only by grid-forming inverters may lead to blackout due to high inrush currents. This article presents virtual reactance techniques to mitigate the inrush current effects and enhance the inverter’s robustness for the safe connection of inductive and dynamic loads. This article also compares the virtual inertia and droop control methods under switching inductive-dynamic loads while the proposed techniques are implemented. Experimental tests are performed considering the linear and nonlinear virtual reactance techniques, and the findings are discussed. The mitigation significantly suppresses the inrush currents while the inverters can perform a normal operation. Furthermore, the frequency and power response of the virtual inertia control with different inertia settings to a sudden change in the load is analyzed. The virtual reactance technique is tested in a laboratory-scale hardware setup of a 208V microgrid fed by 5kVA and 10kVA inverters, and the results are presented in this article.

Gursoy, Mehmetcan↗

Dynamic Load Inrush Current Mitigation in Islanded Microgrids Powered by Grid-Forming Inverters

Grid-forming inverters in a microgrid may trip due to high inrush current caused by a switched connection of an inductive load, e.g., a relatively large induction motor. The control scheme presented in this article includes virtual inertia control method superimposed on the cascaded controller. This article studies the impact of cascaded control scheme used for grid-forming inverter to mitigate the inrush current effects and enhance the inverter’s robustness for the safe connection of inductive and dynamic loads. Experimental tests are performed using the virtual inertia method for generating the reference angle for synchronous frame conversion. The experimental performance and sensitivity of the controller to different controller gain settings for a switched connection of an induction motor are discussed. The cascaded operation significantly mitigates the inrush currents while the inverters can perform a normal operation. The performance of the control method is tested in a laboratory-scale hardware setup of a 208V microgrid fed by 5kVA and 10kVA inverters, and the results are presented.

Gursoy, Mehmetcan↗

Evaluation of Optimal Net Load Management in Microgrids Using Hardware-in-the-Loop Simulation

This paper presents the performance evaluation of a net load management (NLM) engine that balances load and generation in an isolated community to power a critical facility after a grid interruption event (e.g., the loss of a large generation unit). This NLM engine is particularly important for microgrid systems because it provides a high-speed, cost-optimal control solution to coordinate grid-forming inverters and to dispatch grid-following inverters and deferrable loads in microgrid systems to enhance grid resilience and reliability. The NLM algorithm cost-optimally dispatches the grid-following inverters and deferrable loads based on the demanded power and load priorities, and the grid-forming inverters use droop control to form system voltages and share active and reactive power. A controller-hardware-in-the-loop platform is developed to evaluate the control performance of the NLM algorithm with two sequential contingency events of lost generation units. The experimental results indicate that the NLM engine can maintain system stability, achieve the targeted system voltage and frequency, and balance load and generation to serve the critical facility with improved system resilience and reliability.

grid-following inverter↗

Microgrid Frequency Stability: A Proactive Scheme Based on Dynamic Predictions

The dynamic nature of microgrids introduces challenges in the context of frequency stability. This work presents a framework where the future state of microgrid frequency is predicted and corrective actions are optimized. Predictions are generated through Bayesian filters leveraging synchronized data acquired via PMUs. Taking a proactive approach makes it possible to optimize corrective actions considering dynamic system conditions. Testing is conducted via Matlab simulations. The performance of the solution presented in this work is compared to traditional load-shedding schemes and to predictive solutions found in literature. The results indicate that the proposed framework outperforms both. Some of the advantages of this framework include a reduction in amount of load dropped during compensation, the use of adaptive parameters which eliminates the need to simulate contingency conditions, and dynamic uncertainty quantification provided the particle filter.

Paramo, Gian↗

Resilient Microgrid Scheduling Considering Multi-Level Load Priorities

In this paper, we propose a novel resilient microgrid scheduling model considering the multi-level load priorities. The resiliency of the microgrid is guaranteed by quickly adjusting the output of committed local resources and shedding the loads with low priorities when the power supply from the main grid is interrupted. Considering the uncertainty of renewable energy resources and loads as well as exchanged power at PCC, the probability of successful islanding (PSI) is used to quantify the resiliency of electricity supply for various loads with different priorities. Then, the multi-level priorities are enforced through chance constrains. Results of numerical simulation validate the proposed resilient scheduling model. In addition, the impacts of resiliency requirement of loads with high priority on the resiliency of loads with low priority are analyzed as well.

Liu, Guodong↗

Using Distributed Dynamic Voltage Restorers to Improve the Frequency Stability of Low-Inertia Networked Microgrids

This paper elucidates the novel concept of using distributed dynamic voltage restorers (DVRs), which are traditionally used to compensate for voltage sags, to improve the frequency stability of low-inertia networked microgrids. During frequency transients, the distributed DVRs rapidly regulate load voltages within an acceptable range, resulting in a fast change of load power consumption and helping improve frequency stability. To enable large-scale network simulation, a phasor-based model of DVRs is developed and validated against real data from a commercially available device. Finally, simulation results of a modified IEEE 123-node test feeder that comprises three microgrids and six DVRs verify the effectiveness of the proposed method.

Du, Wei↗

A Load Switching Group based Feeder-level Microgrid Energy Management Algorithm for Service Restoration in Power Distribution System

This paper presents a load switching group based energy management system (LSG-EMS) for operating microgrids on a distribution feeder powered by one or multiple grid-forming distributed energy resources. Loads on a distribution feeder are divided into load switching groups that can be remotely switched on and off. The LSG-EMS algorithm, formulated as a mixed-integer linear programming (MILP) problem, has an objective function of maximizing the served loads while minimizing the total number of switching actions. A new set of topology constraints are developed for allowing multiple microgrids to be formed on the feeder and selecting the optimal supply path. Customer comfort is accounted for by maximizing the supply duration in the customer preferred service period and enforcing a minimum service duration. The proposed method is demonstrated on a modified IEEE 33-bus system using actual customer data. Simulation results show that the LSG-EMS successfully coordinates multiple grid-forming sources by selecting an optimal supply topology that maximizes the supply period of both the critical and noncritical loads while minimizing customer service interruptions in the service restoration process.

Hu, Rongxing↗

Experiences and Lessons from Field Demonstration of Grid-forming Inverter in An AC Microgrid

The validation of GFM control strategies through simulation and hardware demonstration is important before their large-scale deployments in the real grid. Considering the importance of testing and validation, several works have explored the GFM inverter’s capability to blackstart a microgrid, synchronize and share loads, and interact with various types of generation sources and loads present in the grid. Herein, this paper complements the existing works by presenting the results and analysis of a field demonstration in an actual AC microgrid. The capability of a three-level neutral point clamped (NPC) GFM inverter equipped with a recursive feedback type of non-linear device level control to operate with PV source on its DC input and off-the-shelf PVGFL inverters and EV chargers of different kinds on the AC side is explored. The analysis and conclusions drawn would inform the readers to make better decisions during the field demonstration process.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Black Start of Unbalanced Microgrids Harmonizing Single- and Three-Phase Grid-Forming Inverters

As power systems are transforming with increasing penetrations of inverter-based resources (IBRs), system restoration using IBRs has drawn attention. Using distributed grid-forming (GFM) assets located near critical loads, either three-phase or single-phase, to establish microgrid voltages in the absence of a bulk grid, a distribution system could obtain high system survivability. For swift and secure recovery of a critical load in a single-phase lateral, local single-phase GFM inverters can form a microgrid, and then it can be combined with a neighbouring grid with the inverters remaining in GFM mode for voltage and frequency regulation until the bulk grid comes online. It leads to dynamic interoperation of single-phase GFM inverters with three-phase ones in the black start process. This paper studies the novel approach with electromagnetic transient (EMT) simulations. To evaluate the potential and the technical challenges of the heterogeneous IBR-driven black start, three-phase and single-phase GFM inverter models are developed, including negative-sequence control for voltage balance and a phase-by-phase current limiter (three-phase) and current magnitude limiter (single-phase). To examine dynamic aspects of the black-start process, the EMT simulation also models transformer and motor dynamics emulating their inrush and startup behavior as well as network dynamics. Involvement of grid-following assets to facilitate the black-start process is also modeled. By allowing multiple GFM inverters to collectively black start without leader-follower coordination, regardless of phases, a system can achieve extreme resilience. An inverter-driven black start of a heavily unbalanced 2-MVA distribution feeder using 1 three-phase and 3 single-phase GFM inverters is demonstrated. The simulation shows the heterogeneous system can maintain stability with the single-phase GFM dynamics coupled with the three-phase one.

grid-forming inverter↗

Modeling and Analysis of DC Microgrids as Stochastic Hybrid Systems

This study proposes a method of predicting the influence of random load behavior on the dynamics of dc microgrids and distribution systems. This is accomplished by combining stochastic load models and deterministic microgrid models. Together, these elements constitute a stochastic hybrid system. The resulting model enables straightforward calculation of dynamic state moments, which are used to assess the probability of desirable operating conditions. Specific consideration is given to systems based on the dual active bridge (DAB) topology. Bounds are derived for the probability of zero voltage switching (ZVS) in DAB converters. A simple example is presented to demonstrate how these bounds may be used to improve ZVS performance as an optimization problem. In conclusion, predictions of state moment dynamics and ZVS probability assessments are verified through comparisons to Monte Carlo simulations.

42 ENGINEERING↗

Current-Source Solid-State DC Transformer Integrating LVDC Microgrid, Energy Storage, and Renewable Energy Into MVDC Grid

Solid-state DC transformer to integrate low-voltage DC (LVDC) microgrid, wind turbine (WT) generator, photovoltaic (PV), and energy storage (ES) into medium-voltage (MV) direct-current (MVDC) distribution grids is attractive. This paper proposes current-source DC solid-state transformer (SST) for MVDC collection system in WT, PV, and ES farms or as an interface between the MVDC grid and the LVDC microgrid. Compared to conventional current-source converter (CSC) based SSTs, a switch reduction scheme on reverse-blocking device bridges is proposed to reduce device count and the number of devices on the DC-link current path. Importantly, the proposed switch reduction scheme is generic and can be applied to the DC ports of DC-AC, AC-DC, or DC-DC hard-switching or soft-switching CSC-based SSTs. Based on this scheme, the proposed current-source DC SSTs are derived, which have reduced electrolytic-capacitor-less DC-link. The proposed DC SSTs also achieve single-stage isolated DC-DC or DC-AC conversion, full-range zero-voltage switching (ZVS) for main switches, zero-current switching (ZCS) for resonant switches, and controlled dv/dt. The proposed DC SSTs, operating principles, predictive control method, the ZVS, and the controlled dv/dt under voltage buck-boost ranges are verified with MV simulations and an experimental prototype based on SiC MOSFETs, diodes, and a nanocrystalline transformer.

14 SOLAR ENERGY↗

Microgrid Modeling for Stability Analysis

Here this document is a summary of a report prepared by the IEEE PES Task Force (TF) on Microgrid (MG) Dynamic Modeling, IEEE Power and Energy Society, Tech. Rep. PES-TR106, 2023. In this paper, the major issues and challenges in microgrid modeling for stability analysis are discussed, and a review of state-of-the-art modeling approaches and trends is presented. In the context of the IEEE 1547 standard, the document covers issues associated with component models for MG dynamic studies and simulations, including generator and grid modeling, full and average converter models, unbalanced and balanced system conditions, dynamic and static loads, protection requirements, and detailed and simplified controls considering communications delays, packet losses, and security issues. Considering the future integration of grids and MGs to form broad integrated networks, a discussion is presented of the use of phasor vis-à-vis electromagnetic transient simulation tools for MG dynamic stability studies, as well as modeling scale-up issues and MG equivalent models. Specifically white-, grey-, and black-box models, are presented. This TF paper and companion report constitute a modeling guide for R&D groups working on developments and standards of MGs with a focus on stability issues.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗