Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode: Preprint

This paper explores the dispatch-ability of grid-forming (GFM) inverters in grid-connected and islanded mode. Grid-forming (GFM) inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generator (SG)) and follow the change of the load demand. However, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help the grid operator better manage their inverter-based resources (IBRs) for improved operation efficiency and reliability. Therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and SG) to output the target power for both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle of doing so is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, thus, dispatching active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one grid-following inverter and loads in both grid-connected and islanded mode. This pioneering work results in a practical guidance for power system energy management system (EMS) development to control a future grid with GFM and GFL inverters.

droop control↗

Performance Evaluation of Multi-Vendor Grid-Forming Inverters for Grid-Connected Operation Through Hardware Experimentation

This paper presents the functional performance evaluation tests of multiple (three) commercial grid-forming (GFM) inverters when they operate in parallel with the grid through hardware experiments. The goal of these tests is to explore and benchmark the GFM inverters' functionalities and dynamic response when they are operated in parallel with power grids. Both steady-state (changing the inverter's frequency and voltage droop) and transient (adding step changes to grid's frequency/voltage) tests are performed for each GFM inverter with the same testing circuit and testing protocol. The key findings are summarized as follows: 1) The GFM inverters can be dispatched through frequency and voltage droop intercepts to output the target power; and 1) the GFM inverters automatically respond to system frequency and voltage events to output the needed power; 3) all the GFM inviters shows stability issues when absorbing reactive power from the grid.

frequency droop↗

Performance Evaluation of a Single-Phase Grid-Forming Inverter Through Hardware Experiments: Preprint

Existing state-of-the-art of single-phase grid-forming (GFM) inverter are primarily focused on electromagnetic transient simulation, and there are very few works performing hardware test, and there is no clear understanding how the single-phase GFM inverter should behave from a hardware perspective. Therefore, this paper addresses the gap by performing hardware experiment to evaluate the performance of a single-phase GFM hardware inverter. We enrich the existing GFM testing protocols by investigating transient performance of GFM inverters under different grid dynamic events, and quantifiable performance metrics are made to have a common understanding of expected performance of single-phase GFM inverters. A commercial single-phase GFM inverter is used to verify the test protocols and understand the inverter's performance and functionalities.

dynamic events↗

A Large-Scale Hardware Experiment Demonstration of Operating High Inverter-Based Resource Power Systems With Grid-Forming Inverters

This paper presents experimental hardware results from a microgrid system as the penetration level of grid-forming (GFM) inverters increases. The experiment aims to showcase the advantages of GFM inverters in enhancing system stability and to investigate the operational challenges in systems relying entirely on inverter-based resources (IBRs). Five test scenarios are devised to progressively increase GFM inverter penetration levels: 0% (S1), 19% (S2), 37% (S3), 68% (S4), and 100% (S5). To ensure consistency, identical loading conditions and dynamic events are applied across all scenarios. The conducted tests include load step changes, output variation of grid-following (GFL) inverters during islanded mode, transition operations (such as synchronization to the grid and islanding), and rateof- change-of-frequency (ROCOF) and voltage jump tests during grid-connected mode. Key findings from the tests are summarized as follows: (1) Scenario S1 proved most challenging for load steps, and GFL variations because of insufficient GFM capacity, leaving the diesel generator unable to handle transient ridethrough; (2) Scenario S5 was the most difficult for transition operations, because the lack of a diesel generator to maintain stiff bus voltage resulted in unexpected reactive power flows during synchronization, causing the point of common coupling (PCC) breaker to trip; (3) Scenarios S4 and S5 were particularly challenging for ROCOF tests because of minimal system inertia, leading to large transients that triggered breaker trips; and (4) Scenario S4 exhibited the strongest voltage recovery capability because of the presence of the diesel generator and a higher number of GFM inverters, both of which possess the highest capacity for reactive power injection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Analysis of Grid-Forming Inverter Controls for Grid-Connected and Islanded Microgrid Integration

Autonomous grid-forming (GFM) inverter testbeds with scalable platforms have attracted interest recently. In this study, a self-synchronized universal droop controller (SUDC) was adopted, tested, and scaled in a small network and a test feeder using a real-time simulation tool to operate microgrids without synchronous generators. We presented a novel GFM inverter control adoption to better understand the dynamic behavior of the inverters and their scalability, which can impact the distribution system (DS). This paper provides a steady-state and transient analysis of the GFM power inverter controller via simulation to better understand voltage and frequency stabilization and ensure that the critical electric loads are not affected during a prolonged power outage. The controllers of the GFM inverter are simulated in HYPERSIM to examine voltage and frequency fluctuations. This analysis includes assessing the black start capability for photovoltaic microgrids, both grid-connected and islanded, during transient fault conditions. The high photovoltaic PV penetration levels open exciting opportunities and challenges for the DS. The GFM inverter control demonstrated appropriate response times for synchronization, connection, and disconnection to the grid. The DS has become more resilient and independent of fossil fuels by increasing the penetration of inverter-based distributed energy resources (DERs).

Ward, Laura (ORCID:0000000345501581)↗

A Novel State-Constrained Primary Control for Grid-Forming Inverters

The problem of operating an AC microgrid with purely inverter-based generating units is considered, and a novel vector control for the constrained grid-forming (GFM) inverters is proposed. The design aims to achieve the primary control objectives of the GFM inverters: voltage establishment, synchronization, and voltage/frequency regulation. It is novel that the proposed control also ensures all operational variables constrained both real-time and for all the time except for low voltage during the period of grid forming. The constraints include frequency, output AC voltage, input DC power, and active/reactive power injections to the grid. Here, in this paper, outcomes of a detailed simulation are presented to demonstrated that the above design objectives are met and that the overall performance is superior due to its unique ability of simultaneously controlling the whole vectors of the inverter state and output.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A New Impedance-Based Modeling and Stability Analysis Approach for Power Oscillations Between Grid-Forming Inverters

This paper presents a new modeling and analysis approach to address the small-signal stability issues among interconnected grid-forming (GFM) inverters. A novel phasor domain “power impedance” model is developed to capture the terminal characteristics of GFM inverters. Based on the developed models, a sum-type impedance stability criterion is proposed to analyze the power oscillations between GFM Inverters. The developed models are validated with EMT simulations and the stability analysis results using the proposed stability criterion can match both EMT simulations and eigenvalue analysis. In addition, the application of the developed model can be extended to the stability analysis of large-scale power system with high penetration of GFM inverters.

Liu, Hanchao↗

Quantitative Small-Signal Stability Analysis of Grid-Forming Inverters in Large-Scale Power Systems

In this paper, the challenges induced by the integration of inverter-based resources (IBRs) into existing power systems are discussed. Although the grid-forming (GFM) control has been used to enhance system performance in multiple sections of electric power systems (e.g., transmission and distribution systems, microgrids, among others), the coupling mechanism between GFM inverter and various types of other components in modern power systems should be clearly explored. Existing analyses mainly focus on qualitative investigations that verify the effectiveness of deploying GFM inverters for stability enhancement. A holistic system-level quantitative analysis is still missing to verify the detailed benefits of GFM inverters and their interactions with other generation units (e.g., synchronous generators [SGs], conventional grid-following [GFL] inverters, synchronous condensers, among others). To fill in the technical gaps, a holistic small-signal model of the entire system with both rotating generation units and IBRs is established along with the customized power flow analysis for varying steady-state operating points. Further, a quantitative method is proposed to identify the impacts of GFM inverters on system performance with an emphasis on a quantifiable stability margin and a complete modal analysis at the system level. Finally, a realistic test system is used to verify the proposed approach.

grid-following↗

Small-Signal Stability of Grid-Forming Inverters Using Current-Limiting and Frequency Stabilization

This paper presents a small-signal stability analysis of grid-forming (GFM) inverters under current-limiting conditions. It examines how adjustments in virtual impedance angles, implemented through advanced current-limiting and frequency stabilization techniques, influence small-signal stability. This paper studies a GFM inverter control integrating a fictitious power technique stabilizing primary control by adding a virtual power term and a hybrid current limiter integrating virtual impedance in the anti-wind-up feedback with current reference saturation limiting. A small-signal model is developed to assess the impact of virtual impedance angles on GFM inverter dynamics during grid disturbances, such as voltage drops. The findings indicate that although increasing the virtual impedance angle (to make it more inductive) enhances large-signal stability and voltage support during faults, it can induce oscillations and lead to instability if the angle exceeds certain thresholds. Based on the small-signal models, this paper provides design considerations for the current-limiter impedances to ensure reliable GFM inverter behavior under grid disturbances while maintaining small-signal stability.

current limiting↗

Improved Control Strategy of Grid-Forming Inverters for Fault Ride-Through in a Microgrid System

This paper develops an improved control strategy of grid-forming (GFM) inverters with fault ride-through capabilities to guarantee the stable operation of microgrids under fault conditions, especially islanded microgrids and asymmetrical faults. The proposed control strategy includes the dual control of positive-sequence and negative-sequence control as well as the adaptive virtual impedance (VI) control. Unlike existing works, the proposed strategy applies the VI control for only the d component of the positive-sequence control and leaves the q component of the positive-sequence control and the dq component of the negative-sequence control as zero, thus achieving improved stability and balanced three-phase voltages under asymmetrical faults. The adaptive feature of the VI control guarantees the stability of the GFM inverter under severe faults, which could cause the saturation of the inner current loop and instability if the VI is not adaptive. Simulation results of various unbalanced faults with high- and low-fault impedances show that the proposed control strategy improves the stability of the GFM inverter and achieves stable and balanced output voltages in islanded microgrids. And the algorithm also improves the stability of GFM inverters under balanced faults with high- and low-fault impedances.

adaptive virtual impedance control↗

Improved Control Strategy of Grid-Forming Inverters for Fault Ride-Through in a Microgrid System

This paper develops an improved control strategy of grid-forming (GFM) inverters with fault ride-through (FRT) capabilities to guarantee the stable operation of microgrids under fault conditions, especially islanded microgrids and asymmetrical faults. The proposed control strategy includes the dual control of positive-sequence and negative-sequence control as well as the adaptive virtual impedance (VI) control. Unlike existing works, the proposed strategy applies the VI control for only the d component of the positive-sequence control and leaves the q component of the positive-sequence control and the dq component of the negative-sequence control as zero, thus achieving improved stability and balanced three-phase voltages under asymmetrical faults. The adaptive feature of the VI control guarantees the stability of the GFM inverter under severe faults, which could cause the saturation of the inner current loop, and the instability if the VI is not adaptive. Simulation results of various unbalanced faults with high and low fault impedances show that the proposed control strategy improves the stability of the GFM inverter and achieves stable and balanced output voltages in islanded microgrids. And the algorithm also improves the stability of GFM inverters under balanced faults with high and low fault impedances.

adaptive virtual impedance control↗

Power Flow Models of Grid-Forming Inverters in Unbalanced Distribution Grids

Load unbalance in electric distribution systems is unavoidable. Unbalanced load currents will lead to negative sequence (NS) voltages that may damage electric equipment. Unbalanced power flow analysis is a common tool to detect and mitigate NS voltage issues and requires accurate models of grid components. While traditional source models are available, grid-forming (GFM) inverter models are not well developed. GFM inverters implement various control strategies, which affect their power flow models. Here, in this paper, a novel GFM inverter model considering control effects is proposed. We show that for some control methods, unbalanced system loading will lead to unbalanced terminal voltages of the GFM inverters, which are modeled through an equivalent negative sequence impedance. The proposed models are initially validated using a simple test circuit. Then, they are applied in the power flow analysis on the IEEE 13-bus and 34-bus systems to demonstrate the accuracy improvement over the state-of-the-art. Using time-domain simulations as benchmarks, we show that the proposed models reduce the calculation error of negative sequence voltages by at least 25% in unbalanced distribution systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Droop Control-Based Dispatch of an Islanded Microgrid with Multiple Grid-Forming Sources: Preprint

Before rotating fossil-fuel based synchronous generators (SGs) are phased out in line with renewable goals, grid-forming (GFM) inverters are expected to parallel with SGs. Primary droop control allows them share power without communication, however, it is necessary to dispatch GFM inverters and/or SG with desired output power for better energy management (e.g., one GFM inverter needs to charge the battery due to low state-of-the charge). Therefore, this paper develops analytic approach to dispatch GFM inverters and SG with desired output power by shifting the droop intercept up/down while maintain the same frequency operating point for improved transient stability. This concept is demonstrated through pure hardware setup with two off-the-shelf inverters and one diesel generator under islanded microgrid, and we also provide insight on real-world implementation of the proposed concept.

droop control↗

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode

This paper explores the dispatchability of grid-forming (GFM) inverters in grid-connected and islanded mode. An innovative concept of dispatching GFM sources (inverters and synchronous generators) is proposed to output the target power by adjusting their droop intercepts. The fundamental principle is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, and thus dispatching the active and reactive power of a GFM inverter can be achieved through dispatching its frequency and voltage. The concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one GFL inverter, and the load in both grid-connected and islanded mode. This pioneering work results in practical guidance for the development of energy management systems for future electric grids with GFM and GFL inverters. The key findings are summarized as follows: 1) The GFM inverters can be dispatched through frequency and voltage droop intercepts to output the target power; 2) The dispatch rule for grid-connected and islanded mode is slightly different.

dispatch GFM inverter↗

How a Large-Scale Deployment of Grid-Forming Inverters May Impact Inter-Area Oscillation Modes: An Investigation in the US Western Interconnection

This report describes work performed to evaluate the impact of high grid-forming (GFM) inverter penetration on the inter-area oscillation mode characteristics of the Western Interconnection. Using simulations, this work analyzes how: a) replacing fossil-fuel-based synchronous generators by GFM inverters will impact properties of the North-South mode, and b) replacing the Colstrip power plant by grid-following (GFL) and GFM inverters will change the characteristics of the Montana mode. Results obtained indicate that high penetration of GFM inverters will significantly alter inter-area oscillation characteristics in interconnections. Low frequency oscillations in the 0.11 Hz range will be predominantly driven by remaining synchronous machines, and hence their relative distribution in the interconnection will impact mode characteristics and observability.

20 FOSSIL-FUELED POWER PLANTS↗

Autonomous Microgrid Restoration Using Grid-Forming Inverters and Smart Circuit Breakers

The proliferation of distributed inverter-based resources (IBRs) raises the questions if these IBRs can be used to blackstart microgrids and distribution feeders after major outages. In this paper, we propose and evaluate an autonomous microgrid restoration concept using grid-forming (GFM) IBRs and smart circuit creakers (SCBs). The concept is first explored in simulation platform and then a hardware testbed containing actual GFM inverters is developed to demonstrate these functionalities. A combination of dispatchable virtual oscillator control (dVOC) and droop-based control schemes have been designed for GFM inverter controls in the software simulations and hardware testbed. Subsequently, operation of SCBs using two distinct principles have been demonstrated that can restore or connect portions of the network.

black start↗

Demonstrating the Need for Adaptive Droop Control for Grid-Forming Inverters in Islanded and Grid-Connected Modes

This paper demonstrates the need of adaptive droop of grid-forming (GFM) inverters operating in different operation modes (grid-connected and islanded). A pure hardware microgrid comprising multiple grid-forming (GFM) inverters from different vendors, multiple grid-following inverters, and a diesel generator is used for the demonstration. The key findings are summarized as follows: Tighter droop slope should be used in the islanded mode, and looser droop slope should be used in the grid-connected mode to ensure stability. It is important to have adaptive droop control in GFM inverters to ensure stable and reliable microgrid operation.

14 SOLAR ENERGY↗