Virtual Cable Impedance based Load Sharing in a Microgrid for Parallel Connected Grid Forming Converters

This paper presents a novel approach to power sharing between direct connected grid-forming converters, utilizing virtual cable impedance and droop-based outer loop control. To enhance stability, resistive droop is implemented, while virtual cable impedance with non-zero resistive and inductive components ensures improved power sharing. The inner loop controller employs a Lyapunov energy function to achieve superior dynamic performance. The proposed control architecture is validated through comprehensive modeling and real-time processor-in-the-loop simulations, demonstrating its robustness and efficiency under various operating conditions. The results highlight the potential of this control strategy to improve the reliability and efficiency of renewable energy systems. Additionally, a comparative analysis with traditional methods underscores the advantages of the proposed approach in terms of stability and performance. The proposed control architecture offers a scalable and flexible solution for grid-forming converters, enabling seamless integration of renewable energy sources. Its robustness and adaptability make it an attractive solution for real-world applications. Furthermore, the approach can be extended to other power electronic systems, enhancing overall system performance and efficiency. By providing a reliable and efficient control strategy, this paper contributes to the advancement of renewable energy systems and their adoption in the energy sector. The proposed control strategy has far-reaching implications for the widespread adoption of renewable energy sources, enabling a more sustainable and efficient energy future. The overall system is modeled in MATLAB/Simulink and PLECS software domain.

grid forming converters (GFM)↗

Optimal Renewable Resource Allocation and Load Scheduling of Resilient Communities

This paper presents a methodology for enhancing community resilience through optimal renewable resource allocation and load scheduling in order to minimize unserved load and thermal discomfort. The proposed control architecture distributes the computational effort and is easier to be scaled up than traditional centralized control. The decentralized control architecture consists of two layers: The community operator layer (COL) allocates the limited amount of renewable energy resource according to the power flexibility of each building. The building agent layer (BAL) addresses the optimal load scheduling problem for each building with the allowable load determined by the COL. Both layers are formulated as a model predictive control (MPC) based optimization. Simulation scenarios are designed to compare different combinations of building weighting methods and objective functions to provide guidance for real-world deployment by community and microgrid operators. The results indicate that the impact of power flexibility is more prominent than the weighting factor to the resource allocation process. Allocation based purely on occupancy status could lead to an increase of PV curtailment. Further, it is necessary for the building agent to have multi-objective optimization to minimize unserved load ratio and maximize comfort simultaneously.

model predictive control↗

Power-Hardware-in-the-Loop Experiments of a Microgrid With a Grid-Forming Battery Inverter: Preprint

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Agent-based microgrid architecture for generation following protocols

A system for predicting power and loads over a single, relatively short time horizon. More specifically, a system comprising a Storage Agent (S-agent) Cohort within a grid control society, wherein the system expands G and L intra-cohort protocols to allow the S-cohort to participate in power management of the grid by scheduling storage components in source or load roles as determined by the time-varying state of the power imbalance and by the risk-adjusting capacity margin relationship between the G and L cohorts.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power-Hardware-in-the-Loop Experiments of a Microgrid with a Grid-Forming Battery Inverter

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Improving Primary Frequency Response in Networked Microgrid Operations using Multilayer Perceptron-Driven Reinforcement Learning

Individual microgrids can improve the reliability of power grids during extreme events, and networked microgrids can further improve efficiency through resource sharing and increase the resilience of critical end-use loads. However, networked microgrid operations are subject to large switching transients, which can cause dynamic instability and lead to system collapse. These transients are especially prevalent in microgrids with high penetrations of inverter-connected renewable energy resources, which do not provide the system inertia needed to mitigate the transients. Existing generator controls can be modified to invoke a drop in terminal voltage in response to a frequency deviation, thereby reducing load and improving frequency response. This paper investigates the use of a reinforcement-learning--based controller trained over several switching transient scenarios to modify generator controls during large frequency deviations. Compared to previously used proportional integral controllers, the proposed controller can improve primary frequency response while adapting to changes in system topologies and events.

Radhakrishnan, Nikitha↗

Demonstrating Distribution System Resiliency through Grid-Edge Microgrids, on a Multi-Site Networked Hardware-in-Loop Platform

With the increasing penetration of Distributed Energy Resources (DERs) at the grid-edge, power systems include more energy storage, remote switches, relays, voltage regulators, and other intelligent electronic devices (IED). Effective control of these grid-edge devices by using Advanced Distribution Management Systems (ADMS) can yield substantial improvements to the resiliency and power quality of distribution systems. In this paper, improvements to the resiliency of a distribution system are demonstrated using a multi-site evaluation environment consisting of a real-time Hardware-in-Loop (HIL) setup in which DERs and other IEDs are modeled; and an ADMS which monitors and is able to control the distribution system assets. The HIL model and the ADMS are located 2400 km away, with communication between the sites enabled by a data manager using Distributed Network Protocol 3 (DNP3), demonstrating the system's capabilities even over long distances. After a simulated transmission system failure in the HIL demonstration setup, DERs and other devices are operated to restore critical loads and node voltage profile (to within the 'nominal +/-5%' band) in the distribution system.

ADMS↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters

This paper investigates operational techniques to achieve seamless (smooth) microgrid (MG) transitions by dispatching a grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control modes during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worth exploring how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. The results show that the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires that the GFM inverter(s) maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-forming control↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters

This paper investigates operational techniques to achieve seamless (smooth) microgrid (MG) transitions by dispatching a grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control modes during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worth exploring how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. The results show that the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires that the GFM inverter(s) maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-forming↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters: Preprint

This paper investigates operational techniques to achieve smooth microgrid (MG) transitions by dispatching the grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control mode during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worthy to explore how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. As expected, the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires the GFM inverter(s) to maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-following control↗

A Bilevel Voltage Regulation Operation for Distribution Systems With Self-Operated Microgrids

The emerging of microgrids in distribution systems has significantly enhanced the resilience of power grids. However, the operators of a distribution system and microgrids therein can be different and have accessibility to different devices. To model the operation of such a grid, this work proposes a bilevel formulation and probes into the voltage regulation operation, considering the interaction between different systems. The proposed bilevel formulation considers the cooperation of active energy resources (AER), transformer tap-changers, and capacitor banks that are controlled by different operators. To facilitate the solution time of the target bilevel optimization, the lower-level problems with different objectives are modeled using deep neural networks (DNNs) which are then converted into a set of constraints. Hence, the bilevel problem can be reformed to a single-level problem. Lastly, the proposed solution procedures are validated using a customized joint system constructed by the IEEE 123-bus system and a real distribution system in Iowa. According to the numerical validation results, the solution time of the proposed nonlinear activation function based DNN model is 69 times faster than other methods in solving voltage regulation with a bilevel structure.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Framework for the Evaluation of the Cost and Benefits of Microgrids

A Microgrid is recognized as an innovative technology to help integrate renewables into distribution systems and to provide additional benefits to a variety of stakeholders, such as offsetting infrastructure investments and improving the reliability of the local system. However, these systems require additional investments for control infrastructure, and as such, additional costs and the anticipated benefits need to be quantified in order to determine whether the investment is economically feasible. This paper proposes a methodology for systematizing and representing benefits and their interrelationships based on the UML Use Case paradigm, which allows complex systems to be represented in a concise, elegant format. This methodology is demonstrated by determining the economic feasibility of a Microgrid and Distributed Generation installed on a typical Canadian rural distribution system model as a case study. The study attempts to minimize the cost of energy served to the community, considering the fixed costs associated with Microgrids and Distributed Generation, and suggests benefits to a variety of stakeholders.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Quantifying the Protectability of Power Systems for Restoration Applications

With the increasing availability of distributed energy resources, controllable switches, and advanced metering infrastructure, distribution systems are exploring opportunities for improving system reliability through fault location, isolation, and service restoration. During permanent outages, this requires islanding microgrids and/or reconfiguration of the feeders; however, it is critical to assess the protection of the islanded/reconfigured networks before transition because the rated load and fault current conditions change. This paper presents a novel “protectability” metric that quantifies the protection performance and allows the operators to compare the effectiveness of the protection between two or more possible reconfiguration and islanding approaches. We present the mathematical formulation and assumptions for the metric. Multiple configurations of the Electric Power Research Institute J1 feeder, both in grid-connected and weak-sourced islanded operation, are used to demonstrate the performance of the metric with reference to overcurrent protection. Takeaways for future studies on system planning integration are provided.

distributed energy resources↗

Ensemble voting-based fault classification and location identification for a distribution system with microgrids using smart meter measurements

This study presents an ensemble learning approach for fault classification and location identification in a smart distribution network containing photovoltaics (PV)-based microgrid. Lack of available data points and the unbalanced nature of the distribution system make fault handling a challenging task for utilities. The proposed method uses event-driven voltage data from smart meters to classify and locate faults. The ensemble voting classifier is composed of three base learners; random forest, k-nearest neighbours, and artificial neural network. The fault location (FL) task has been formulated as a classification problem where the fault type is classified in the first step and based on the fault type, the faulty bus is identified. The method is tested on IEEE-123 bus system modified with added PV-based microgrid along with dynamic loading conditions and varying fault resistances from 0 to 20 Ω for both unbalanced and balanced fault types. A further sensitivity analysis has been done to test the robustness of the proposed method under various noise levels and data loss errors in the smart meter measurements. The ensemble method shows improved performance and robustness compared to some previously proposed FL methods. Finally, the proposed method has been experimentally validated on a real-time simulation-based testbed using a state-of-the-art digital real-time simulator, industry standard DNP3 communication protocol and a cpu-based control centre running the FL algorithm.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Self-healing, self-assembling islanded power systems using only local measurements

This SAND report collects the results from the LDRD project “SHAZAM”, which aimed to push the limits of performance for self-healing, self-assembling power systems whose sectionalizing and load-control agents rely on local measurements only (i.e., only what they can measure at their own terminals, with no data sharing between agents). This work includes self-networking microgrids. The key objectives of this work were a) to demonstrate how high the performance of local-measurement-only self-assembling power systems can be; and b) to solve certain technical problems associated with such systems, such as their inability to prevent the accidental formation of closed loops and their tendency to thermally overload some conductors. “SHAZAM” investigators a) demonstrated that the performance of such systems can be surprisingly high, b) demonstrated that such systems are quite robust to all kinds of variations, and c) developed and demonstrated solutions to several key challenges associated with this type of system.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distributed Barrier Certificates for Safe Operation of Inverter-Based Microgrids

Inverter-interfaced microgrids differ from the traditional power systems due to their lack of inertia. Vanishing timescale separation between voltage and frequency dynamics makes it critical that faster-timescale stabilizing control laws also guarantee by-construction the satisfaction of voltage limits during transients. In this article, we apply a barrier functions method to compute distributed active and reactive power setpoint control laws that certify satisfaction of voltage limits during transients. Using sum-of-squares optimization tools, we propose an algorithmic construction of these control laws. Numerical simulations are provided to illustrate the proposed method.

Kundu, Soumya↗

Introducing the 9500 Node Distribution Test System to Support Advanced Power Applications: An Operations-Focused Approach

The 9500 Node Test System is a representative section of distribution power system model developed as a part of the GridAPPS-D™ project, an effort funded by DOE as a part of the Grid Modernization Lab Consortium (GMLC) program. The test system was developed to fulfill a growing need to represent the rapidly evolving state of electric distribution systems by combining elements of legacy infrastructure systems, modern feeder topologies, and an anticipated future with smart grid technologies. It also provides a network model capable of supporting the simulation of operational scenarios such as the ones in a utility distribution control center. This test system allows the evaluation of the performance of advanced power applications in real-time, such as one that simulates the operations of an Advanced Distribution Management Systems (ADMS), Distributed Energy Resource Management Systems (DERMS), etc. in a Distribution control center. This model is an extension of the widely used IEEE 8500 Node Test Feeder and is currently being validated to become an IEEE test case to help increase adoption and widespread usage among both academia and industry. It is a full-size model representative of a section of a utility’s distribution system with multiple feeders fed from different substations. The model includes multiple distribution circuits, a sub-transmission system, multiple substations, behind the meter customer rooftop photovoltaics (PV), and multiple utility-scale distributed energy resources. To enable accurate simulations of operational scenarios, the 9500 Node Test System is designed to support procedure-based operations, with the ability to realistically demonstrate switching operations, feeder reconfiguration, adjustment of volt-var control equipment, dispatch of distributed generation, and response to planned and unplanned outages. The 9500 Node Test System includes three radial distribution feeders with 12.3 MVA of average load, consisting of both medium voltage and low voltage equipment each supplied by a different distribution substation. The three distribution feeders are connected to each other through Normally-Open switches which can be closed when needed to simulate restoration scenarios due to a fault. One feeder represents today’s grid with low penetration of customer-side renewables. The second represents a potential future grid with microgrids and 100% renewable penetration. The third has no customer generation resources, a district steam plant, and a utility-scale solar farm. The three diverse circuits were created to allow the simulation of both today’s situation as well as potential future scenarios. All three feeders have customers connected by low-voltage secondary triplex lines. This test system meets all requirements outlined in the report for creating a simulation environment that would enable discussion between key technical stakeholders as well as having the potential to accelerate operational application development and their subsequent testing and integration. The new model is a possible representation of what we believe the distribution grid may look like in the future: a high penetration of renewables, reconfigurable radial and mesh topology, numerous DERs, islanded microgrids, and significantly increased data and measurement density. The system supports both the solution of existing and newer algorithms but also enables the evaluation of applications in a realistic operational environment defined by task oriented procedural steps that represent the interaction between the control center operator and field personnel.