Search NASASearch

SEARCH · Search NASA

Results for “GFM”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 73 records · Page 4

Testing and Analysis of Grid Forming Inverter Control for Achieving Resilient and Economic Operation of an Islanded Microgrid

This investigation examines the feasibility of operating a battery energy storage system (BESS) in parallel with synchronous generation by using grid forming (GFM) control in order to achieve frequency control objectives while mitigating increases to operating costs in the context of an islanded microgrid. The BESS GFM control system, which is based on conventional droop techniques, is modeled along with the overall microgrid using the Real Time Digital Simulator (RTDS) to allow for integration of genset controller hardware. A series of simulations are performed to test the voltage and frequency regulation capability of the BESS control system when the primary frequency regulating genset is tripped offline. The results of the simulations suggest that the GFM control scheme will successfully maintain frequency and voltage stability, which will enable operation without a back-up genset while not compromising the microgrid resiliency to contingencies.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI

Optimal Droop Setting for Congestion Reduction in a 100% Grid-Forming Inverter-based Power System

he high penetration of inverter-based resources (IBRs) introduces new challenges to power systems due to the complex inverter control. However, IBRs can be configured to maximize their benefits to improve system resilience and reliability. This paper proposes a steady-state optimization model that aims to mitigate transmission congestion in a 100% grid- forming (GFM) IBR-based power system. This goal is achieved by determining the optimal droop settings for the GFM IBRs under different congestion conditions due to renewable energy and load variations. The numerical solution is rigorously verified by a high-fidelity model of the IEEE 39-bus test system with detailed GFM IBR control in the time-domain electromagnetic transient (EMT) simulation tool PSCAD. The numerical solution and simulation results show a significant congestion reduction while meeting all other operating requirements. It is also observed that the numerical solving time is substantially less compared to the EMT simulation time.

Nguyen, Quan H.

Transient Stability Analysis of Direct Droop-Controlled Grid-Forming Inverter with Current Clipping as Current Limiting Control

This paper investigates the transient stability of the direct droop-controlled grid-forming (GFM) inverter which employs the current clipping-based approach for overcurrent limitation. An equivalent circuit model of the direct-droop GFM inverter with current clipping is developed for this purpose. It is shown that during overcurrent conditions, the GFM inverter with current clipping acts as a voltage source with a virtual resistance behind the inverter filters. To compute the parameters of this virtual resistance an analytical expression is given in the paper. Then utilizing the developed circuit, a criteria to exit current limiting during post-fault conditions is given. The developed analytical approaches are then validated through electromagnetic transient (EMT) simulation results in PSCAD software and finally concluding remarks are drawn.

Mohiuddin, Sheik Mohammad

Experiences and Lessons from Field Demonstration of Grid-forming Inverter in An AC Microgrid

The validation of GFM control strategies through simulation and hardware demonstration is important before their large-scale deployments in the real grid. Considering the importance of testing and validation, several works have explored the GFM inverter’s capability to blackstart a microgrid, synchronize and share loads, and interact with various types of generation sources and loads present in the grid. Herein, this paper complements the existing works by presenting the results and analysis of a field demonstration in an actual AC microgrid. The capability of a three-level neutral point clamped (NPC) GFM inverter equipped with a recursive feedback type of non-linear device level control to operate with PV source on its DC input and off-the-shelf PVGFL inverters and EV chargers of different kinds on the AC side is explored. The analysis and conclusions drawn would inform the readers to make better decisions during the field demonstration process.

24 POWER TRANSMISSION AND DISTRIBUTION

Holistic Small-Signal Stability Analysis for Large-Scale Inverter-Intensive Power Systems with Coupled and Full-Order Dynamics from Control Systems and Power Networks

The increasing penetration of inverter-based resources (IBRs) into the existing power systems introduces tremendous benefits for enhanced sustainability but also poses inevitable challenges in terms of insufficient inertia, potential instability, and complex network dynamics, among others. However, the additional coupling introduced by the interactions among gridfollowing (GFL) and grid-forming (GFM) IBRs and the other components (i.e., synchronous generators [SGs], loads, and network, etc.) has not been clearly explored. A holistic, scalable, and quantitative stability analysis framework with the control systems and power networks is still missing. Here, in this paper, to fill in the technical gaps, a holistic small-signal model of the entire system with both rotating generation units and IBRs is established. An extended power flow model with operation dynamics from both generator control schemes and power networks is proposed to provide the varying steady-state operating points for small-signal modeling. The proposed method is compared with MATLAB solvers, and the results show that the proposed approach has a minimum calculation time, which can be less than 12 seconds for a large-scale power system with up to 2,000 buses. Furthermore, a quantitative method is developed to identify the impacts of IBRs on system performance with emphases on the potential stability issues with GFL IBRs, additional benefits of employing GFM IBRs, the feasibility of replacing SGs with GFM IBRs, and the impact of penetration level of different kinds of generation units. Finally, a field island power system is used to verify the proposed approach, and hardware-in-the-loop (HIL) tests are provided to further demonstrate the effectiveness of the proposed analysis.

14 SOLAR ENERGY

A Two-Stage Current Limiting Control Strategy for Direct-Droop-Controlled Grid-Forming Inverters

This paper presents a two-stage current limiting control strategy with fault ride-through capability for the direct-droop-controlled grid-forming (GFM) inverters. The proposed approach comprises Stage 1 and Stage 2 current limiting controls. During faults, Stage 1 current limiting control instantly clamps the inverter output current magnitude to its maximum transient limit by blocking the switching pulses to the insulated-gate bipolar transistors (IGBTs) with the help of a hysteresis loop control, and Stage 2 current limiting control limits the inverter output current magnitude to its steady-state limit by regulating the amplitude and frequency of the modulating waveform utilizing the active and reactive current limiting control loops. By implementing the current limiting actions in two stages, this approach can effectively limit the over-current within a few cycles after the fault occurrence and ensure synchronism to the grid after long-term fault events. The efficacy of the proposed control approach is validated through electromagnetic transient (EMT) simulation results conducted on a single GFM inverter-based test system and the IEEE 39-bus test system with multiple GFM inverters in the PSCAD platform.

Mohiuddin, Sheik Mohammad

Critical Clearing Time for Droop-Controlled Grid-Forming Inverters With Circular Current Limiting and Virtual Impedance Current Limiting

The critical clearing time is a crucial parameter for assessing the large-signal stability of grid-forming (GFM) inverters. Variations in current limiters can significantly impact an inverter's transient behavior during large disturbances. Here, this letter introduces a method based on the power-angle relationship to evaluate the fault recovery of a droop-controlled GFM inverter under a three-phase bolted fault scenario, considering both the circular current limiter and the virtual impedance method. High-fidelity simulations validate the accuracy of the proposed formulas in estimating the critical clearing time of the GFM inverter.

42 ENGINEERING

A Novel Design for Switchable Grid-Following and Grid-Forming Control

This paper presents the design of a novel grid- forming (GFM) control structure adapted from a typical grid- following (GFL) control structure with minimal edits, thereby enabling a switchable control structure for voltage sourced converters (VSCs) to operate in either GFL or GFM mode by simply switching a flag manually. The VSC is shown to be able to operate in the GFL control mode synchronizing to the main grid through a phase-locked-loop (PLL) and operate as a GFM controller with power-based synchronization for both grid-connected and islanded conditions. To guarantee smooth operation, the control schemes and the mode switching logic have been carefully designed and examined via a series of experiments. Here, the experiment results show that the switchable control structure can fulfill the desired control and operation functions and enable smooth transition between control modes.

14 SOLAR ENERGY

Small Hydro Power Plants with Integrated BESS for Enhance Resiliency

Battery energy storage systems (BESS) are an important asset for power systems with high integration levels of renewable energy, and they can be controlled to provide various services to the grid. This paper presents the hardware demonstration and characterization of using a utility-scale BESS with grid-following (GFL) and grid-forming (GFM) controls and a run-of-river (ROR) hydropower plant to perform a bottom-up power system black start that enhances power systems' resiliency. ROR hydropower plants are generally not used for power system restoration due to their frequency instability during islanded operation; however, BESS with droop control can provide critical damping to convert a ROR hydropower generator into a black start- capable unit. To demonstrate this, we carry out hardware experiments at the megawatt-scale integrating a synchronous generator driven by a dynamometer, an actual GFL/GFM BESS, a medium-voltage impedance network, and a load bank. The demonstration shows the different roles of BESS with GFL and GFM control in power system restoration. GFL BESS can suffer from high-frequency oscillations, even instability, depending on the droop control gain and loading condition. The results provide further insights for system operators on how GFL- or GFM controlled BESS can enhance grid stability and how hydro-BESS hybrids can operate as a black-start-capable unit. The presented experimental results are also a valuable resource to understand the different stability characteristics of real-world BESS with different control modes.

24 POWER TRANSMISSION AND DISTRIBUTION

UNIFI Specifications for Grid-Forming Inverter-Based Resources: Version 3

The UNiversal Interoperability for grid-Forming Inverters (UNIFI) Consortium addresses fundamental challenges facing the integration of grid-forming (GFM) inverters in electric grids alongside rotating machines and other inverter-based resources (IBRs). This document defines a set of UNIFI specifications for GFM IBRs that provides requirements from both a power system level as well as functional requirements at the inverter level that are intended to provide means for the vendor-agnostic operation of GFM IBRs at any scale in electric power systems.

14 SOLAR ENERGY

Control Parameter Sensitivity Study for Inverter-Based-Resource Dominated Grids: A Small Signal Stability Approach and Framework

The growing adoption of renewable energy is driving the prevalence of inverter-based resources (IBRs) within power grids. Future power grids will integrate both grid-following IBRs (GFM-IBRs) and grid-forming IBRs (GFL-IBRs) alongside synchronous generators. Therefore, it is crucial to perform stability studies that account for all components and especially control interactions related to IBRs. Extensive research has performed to study the IBR-related stability, however, the sensitivity study of IBRs' control parameters on system stability has not been adequately studied yet, especially from a systematic way. Therefore, this paper conducts a small signal stability analysis for a generic grid with multiple types of resources and develops an analytical framework for assessing the sensitivity of control parameters affecting stability margins. To achieve that, the non-autonomous reduced-order non-linear dynamic model is developed for a generic power system with multiple synchronous generator-based resources (SGBRs), GFM-IBRs, and GFL-IBRs. Based on the analytic model, a systematic framework for parametric sensitivity on systems' asymptotic stability is developed. A parameter sensitivity analysis based on eigenvalue methods is proposed. The impact of the droop controllers of GFM-IBRs, PQ-dispatch and the PLL controller of GFL-IBR on the system asymptotic stability is discussed. This sensitivity study is aiming to provide deep insights on control parameters' impact on system stability, and gives direction for parameter tuning in case of instability.

24 POWER TRANSMISSION AND DISTRIBUTION

Demonstrating the Need for Adaptive Droop Control for Grid-Forming Inverters in Islanded and Grid-Connected Modes

This paper demonstrates the need of adaptive droop of grid-forming (GFM) inverters operating in different operation modes (grid-connected and islanded). A pure hardware microgrid comprising multiple grid-forming (GFM) inverters from different vendors, multiple grid-following inverters, and a diesel generator is used for the demonstration. The key findings are summarized as follows: Tighter droop slope should be used in the islanded mode, and looser droop slope should be used in the grid-connected mode to ensure stability. It is important to have adaptive droop control in GFM inverters to ensure stable and reliable microgrid operation.

14 SOLAR ENERGY

An Innovative Energy Management System for Microgrids with Multiple Grid-Forming Inverters: Preprint

As more and more grid-forming (GFM) inverter-based resources replace traditional fossil-fueled synchronous generators as the GFM sources in microgrids, the existing microgrid energy management systems (EMSs) need to be updated to control and coordinate multiple GFM inverters that consider system control objectives under different microgrid connection states. For each state, we formulate an optimization problem and apply a real-time feedback-based control algorithm; all together, the control algorithms seamlessly connect the states into a generic EMS. We showcase the EMS on a real-world simulation of a microgrid under the different states to demonstrate its operational effectiveness.

energy management system

Modeling and Power-Hardware-in-the-Loop Validation of Synchronous Wind: An Inverterless Grid-Forming Wind Power Plant: Preprint

Grid-forming (GFM) control of Type-3 and Type-4 wind turbine generators has attracted substantial attention in power systems research; however, the limited over-current capability of power electronics converters continues to deteriorate the grid strength of the evolving power systems. Synchronous wind, also known as Type-5 wind turbine generator (WTG), offers a unique GFM solution to address grid integration and grid strength issues by keeping the grid largely synchronous at very high penetration levels of renewable generation. A Type-5 WTG interfaces to the electric grid via a synchronous generator (SG) driven by a variable-speed hydraulic torque converter; hence, the wind rotor operates in variable-speed mode for maximum power generation and the generator shaft remains synchronous to the grid. This paper developed and tested a high-fidelity model of Type-5 WTG under power-hardware-in-the-loop (PHIL) testing environment. The PHIL demonstration showed that a Type-5 WTGs inherently behaves as a GFM unit and can obtain similar performance in terms of power responses, wind rotor dynamics, and efficiency compared to Type-3 WTG in high wind conditions. The developed model also provides further insight on how Type-5 WTGs can benefit the smooth transition to power systems with high integration level of inverter-based resources.

grid strength

Grid-Forming and -Following Background, Future, and Strategies

This paper reviews current grid forming (GFM) and grid following (GFL) inverter control strategies and explores the optimized ratio between these assets in high-penetration inverter-based resource (IBR) grids. Two case studies demonstrate that an insufficient GFM ratio leads to instability, while increasing GFM participation improves fault recovery, voltage stability, and frequency regulation.

14 - SOLAR ENERGY

Virtual Synchronous Machine Grid-Forming Inverter Model Specification (REGFM_B1)

This report describes a generic virtual synchronous machine (VSM) grid-forming inverter (GFM) model - REGFM_B1. The initial model specification was proposed by Pacific Northwest National Laboratory (PNNL), General Electric (GE), and Electric Power Research Institute (EPRI). Siemens Gamesa Renewable Energy (SGRE) also provided inputs to the specification. The model specification has been revised multiple times based on the discussions between all the contributors listed in this report. This work was funded by the Universal Interoperability for Grid-Forming Inverters (UNIFI) Consortium. This generic model is developed to help the utility industry understand the concept of VSM GFMs. The model could be used to represent equipment for long-term planning studies where vendor-specific models are not available. As equipment mature and improve, generic models will be updated to capture the new functionalities of GFMs. It is not intended that these models will always remain representative of all future GFM technologies.

24 POWER TRANSMISSION AND DISTRIBUTION

A Guide to Current Limiting and Stability with Grid-Forming Inverters

The electric power grid is changing. For many decades, the synchronous generator - an electromechanical device invented in 1887 - has been the workhorse and backbone of power grids across the globe. Our entire infrastructure is built around it. But times change, and so does the power grid. Since the early 21st century, we have seen a gradual shift in modern power grids away from synchronous generators to ones dominated by power electronic inverter-based resources (IBRs). Sources such as photovoltaics, wind turbines, battery storage, fuel cells, and other technologies like high-voltage DC transmission interconnections all rely on an inverter to connect and interface with the grid. They are increasingly being installed on the grid to augment, or even replace, traditional energy sources. This change is a fundamental shift that brings tremendous technical challenges and questions: Can a power grid remain stable with many more inverter-based resources? How do we avoid more blackouts on the grid? How do we keep the grid secure and resilient during disturbances? After all, power electronic inverters are nothing like the big, rotating, iron-and-copper machines that the grid heavily relies on. Many of these questions can be answered by using grid-forming (GFM) inverters, yet many research challenges remain. This document explores GFM inverters and how they can help stabilize the future grid, especially during disturbances and contingencies. It summarizes a two-year research and development fellowship program at NREL. We point interested readers to more detailed works developed during the project along the way. Let's dive in

24 POWER TRANSMISSION AND DISTRIBUTION

Grey-Box System Identification of Grid-Forming Inverters

This paper demonstrates the use of grey-box system identification methods for simplifying and understanding the nonlinear power dynamics of grid-forming inverters (GFMs). The power and frequency outputs of complex high-order GFM models are fed into system identification software in order to fit them to a predetermined LTI system and learn system parameters such as (synthetic) inertia and droop constants. The same process is then run for a high-order synchronous generator model, and the outputs are fit to the same set of LTI equations. Simulation of a network of GFM inverters with diverse control architecture is also performed for the same process. The intent is threefold: first, to demonstrate the appropriateness of unified LTI models for describing the power and frequency dynamics of individual resources and connected networks, in order to facilitate analysis of larger heterogeneous networked systems; second, to discover the relationship between internal control parameters of GFMs and their externally observed values; and third, to validate that grey-box data-driven system identification techniques can be a valuable tool to discover the values of important parameters in the absence of explicit vendor models.

analytical models