At least 73 records · Page 4

A Near-Real-Time Model for Predicting Electricity Disruptions in Texas During Winter Storms

There has been an increase in extreme weather events, posing a threat to power grid systems, potentially influenced by factors such as population growth, changes in ecosystems, land cover, and land use in the service area, as well as the growth of certain vegetation types. This research seeks to develop a predictive model to mitigate potential damages caused by future winter storms. This research utilizes the Light Gradient Boosting Machine (LightGBM), incorporating the number of power outages experienced at the county level, geographic details, weather information, and lagged outage and lagged weather data. The developed models were broadly divided into two groups, with six models in each group - one group without optimization and another with optimization, totaling 12 trained models. For model optimization, Bayesian optimization was employed using Root Mean Squared Error (RMSE) as the objective function. In results, when comparing Group 2 (the optimized group) with Group 1 (the non-optimized group), it was found that optimization did not always lead to a reduction in RMSE and Mean Absolute Error (MAE). However, in terms of Mean Directional Accuracy (MDA), while all results in Group 1 were below the baseline accuracy of 0.33, all results in Group 2 exceeded 0.33, with some cases showing an increase of more than three times the baseline. The results indicated that, in the optimized model group, Population and Pressure were the most influential factors when using current weather data and geographical information. When using lagged data, lagged recorded outages and lagged Pressure emerged as the most significant factors. Among the 12 developed models, the L-1-2-O model showed the lowest RMSE and MAE, as well as the highest accuracy, with values of 390.62 households and 168.13 households, respectively. To normalize the RMSE and MAE values, each metric was divided by the average number of households among the counties in Texas. For the L-1-2-O model, the scaled RMSE was 0.88% and the scaled MAE was 0.38%. In terms of MDA, which indicates the accuracy of the prediction direction, the L-1-O model achieved the highest score of 0.41. Although this study focused on Texas, which suffered the greatest impact from the winter storms in 2021, with additional validation, the methodology used in this research could be applied to other regions.

Lee, Jangjae [Texas A & M Univ., College Station, ↗

Dispatch analysis of flexible power operation with multi-unit small modular reactors

The relevance of nuclear power plant flexible power operation (FPO) is rising due to increased penetration of variable renewables. Small Modular Reactors (SMRs) such as NuScale are envisaged to have multiple units on one site. This provides opportunities for coordinating FPO between units, but also introduces challenges as common services (e.g., refueling equipment) must be shared between units and fuel loadings may be standardized. It is therefore important to quantify whether FPO with SMRs is economically beneficial. Here, this paper quantifies the economics of FPO on different timescales to analyze refueling outages of such multi-unit SMRs. A 24-h price-taker profit maximization of SMR operation is first solved considering revenues from wholesale power and ancillary service (AS) markets. The results are then used to find the most profitable operation strategy over several years for multiple units at the site accounting for the physics and materials limits on NPP operation, including refueling outages. Results show a small but appreciable participation of nuclear into AS, contributing 4% of revenues. Due to the longer fuel cycle, over a decade of operation the units’ refueling outages drifted by 3 months, ultimately leading to refueling during summer.

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

Beaconless Optical Communication System Constraints

Deep-space optical communication will enable increased science return and public engagement for robotic and manned missions. The IROC project is studying a beaconless optical communication system for Mars data downlink. A star tracker provides the optical communications pointing information in place of an uplink targeting beacon. The configuration presented in this paper includes a star tracker that is aligned co-boresighted with the optical communication axis. This co-boresight configuration was not discussed in prior work, as it was assumed that large Sun-Probe-Earth keep-out angle requirements for operation of the star tracker would cause significant communication outages. In this paper it is shown that the use of an optimal mechanical mounting angle combined with an advanced star tracker has the capability to yield up to 92% communication availability for an example five-year Mars mission.

Aretskin-Hariton, Eliot D.↗

Data Analytics Methods to Measure Plant Outage Resilience

Every 18 or 24 months nuclear power plants (depending on plant configuration, pressurized or boiling water reactor respectively) undergo a period of outage where the plant is taken offline and a large number of maintenance and surveillance activities (that cannot be performed while plant is running) are performed in typically 2–3 weeks. Planning of a plant outage is very challenging since all the activities are required to be performed in the shortest amount of time given available resources (typically contractor crews hired for the duration of the outage). Consequently, plant outages can be costly due the actual loss of power generation and crew costs and, because of it, there is a need to maximize resource usage in the outage planning phase and reduce the risk of outage delays. This paper is addressing these needs by providing a set of analytical methods designed to analyze plant outage schedule and identify critical elements based on available resources (time and crews). These methods are based on natural language processing and optimization algorithms. In this respect, two classes of methods have been developed: one that focuses on the time resource and how variability in the time to complete outage tasks may impact outage delays, and one that minimizes the risk of outage delays by integrating available resources to assess when daily activities should be performed.

97 - MATHEMATICS AND COMPUTING↗

Hierarchical Resilience Planning for Networked Microgrids: A Case Study of Puerto Rico

Microgrids can be designed to enhance the energy resilience of communities and critical infrastructures, such as hospitals, data centers, and communication networks, which are vulnerable to frequent weather-related disruption. Coordinating multiple microgrids in a network can leverage the geographical diversity of load and generation resources while enabling resilient and cost-effective planning of the distribution system. Designing a networked microgrid is complex, involving intricate technical assessment, cost-benefit analysis, site-specific requirements, and the evaluation of existing resources. Therefore, this paper proposes a hierarchical resilience planning framework and performs an extensive techno-economic analysis for the design of a networked microgrid. Hierarchical resilience planning involves technology sizing at an individual community level to meet the critical load and satisfy resilience criteria, and resource optimization at networked microgrid level to provide a higher level of resilience and energy adequacy. A real-world case of Puerto Rico's cooperative microgrid “Microrred de la Montaña” is investigated considering localized electricity tariffs, site-specific demand profiles, solar generation, and existing hydro resources. Multiple optimization scenarios are developed based on the resiliency requirement to estimate the capacity of solar photovoltaic and battery energy storage (BES) to be installed at each substation. The results provide the optimal sizing for individual community and networked microgrid to withstand 1day and 3-day outages along with the criteria for critical load.

13 - HYDRO ENERGY↗

Optimal Network Reconfiguration and Scheduling With Hardware-in-the-Loop Validation for Improved Microgrid Resilience

With the increased occurrence of various major extreme weather events, power outages and prompt power system restorations have recently drawn more attention to the resilience and recovery of power systems. From the perspective of a more resilient power delivery at the distribution grid, system restoration using network topology reconfiguration together with optimal scheduling of distributed energy resources are adopted in this paper. The proposed optimization model aims at minimizing the total load shedding cost and other operational costs, in which linearized topological constraints borrowed from graph theory and linearized DistFlow models are respectively used to maintain the radial network topology and power flow balance after system contingencies. To demonstrate the applicability of the proposed strategy, a real-world case study of a networked three-microgrid system in Adjuntas, Puerto Rico, is used with the consideration of different independent/interconnected microgrid scenarios, contingencies, and fairness settings. Furthermore, hardware-in-the-loop testing is conducted for the same three-microgrid network, where the closely matched results with the simulated ones have validated the effectiveness of the proposed restoration strategy, which is now ready to move one step forward towards field deployment. Finally, to test the proposed restoration strategy in a larger networked system, the modified IEEE-33 bus test distribution system is considered, and the results show a more resilient power delivery for critical loads under three and four line outages.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A sequential Attacker-Defender game for distribution systems resilience enhancement against extreme weather events

Improving distribution system resilience against frequent extreme weather events is important for reliable power system operations. Especially when dealing with events such as hurricanes that have short-term predictions, proactive pre-event preparedness plays a vital role in system resilience performance. In this paper, we propose a novel approach to construct pre-event resource allocation plans for system operators to cope with upcoming threats through a sequential attacker-defender game framework. The sequential attacker-defender game is designed to model the interaction between the extreme weather and the system operator. In each round of the game, the attacker and the defender sequentially update their current strategies by accounting for the opponent’s action set. The attacker model is formulated as a bi-level problem to identify the severe outage scenarios, and the defender model is formulated as a two-stage optimization problem to determine the allocation of restoration resources including mobile responsive resources and repair crews. Two scale-reduction strategies are proposed to ensure the scalability of the game scheme. Finally, case studies on the IEEE 33-bus and a 7149-node practical utility system validate the effectiveness of the proposed sequential game and the efficiency of the scale-reduction strategies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modeling Combined Heat and Power Systems in REopt

This webinar will explore how the National Laboratory of the Rockies' REopt(R) web tool can evaluate the techno-economics of combined heat and power (CHP) technologies and systems to assess performance and financial viability. REopt can analyze both standalone CHP systems, and systems paired with other on-site energy resources. Participants will gain practical insights into using REopt to optimize site energy strategies, reduce energy costs, and improve site energy security and outage recovery.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

High-Burnup BWR LOCA Burst Analysis Framework Development and Demonstration

Nuclear power currently contributes approximately 20% of total electricity generation in the United States and more than 10% globally. Given the increasing reliance on nuclear energy to achieve our nation’s goal of reaching net-zero carbon emissions by 2050, there is significant pressure on the existing nuclear industry to extend plant operational licenses and improve efficiency. This is crucial as the existing nuclear fleet serves as a vital bridge until new light water and advanced reactors can be developed and deployed, bolstering the supply of carbon-free energy to meet domestic demands. Operational costs primarily consist of plant operation and maintenance and fuel costs, influenced by materials and reactor core designs. These factors, coupled with heavily subsidized renewable energy markets, create a challenging economic environment for the existing light water reactor fleet, as well as for new build projects. To address these economic challenges, the nuclear industry has developed a strategic blueprint aimed at enhancing nuclear power’s economic sustainability. Past initiatives, such as efforts to eliminate fuel failures by 2010 and reduce operating costs by 30% before 2020, have laid the groundwork. Optimizing core design parameters, including burnup limits and enrichment levels, can lengthen cycles, reduce outages, reduce batch reload batch fractions and spent fuel storage requirements, and lower maintenance and operating expenses, thereby enhancing economic viability. In the United States, boiling water reactors (BWRs) comprise approximately one-third of the fleet, although much of the research and development focus has traditionally been on pressurized water reactors (PWRs). Advances in modeling and simulation, particularly through the Nuclear Energy Advanced Modeling and Simulation (NEAMS) program, are crucial to the long-term viability of BWRs, just as they are for PWRs. A key research area of the high burnup/increased enriched fuel initiative is focused on addressing loss-of-coolant-accident (LOCA)-related issues. NEAMS has dedicated significant effort to enhancing tools to better support BWRs, with a current focus on showcasing the BWR framework for high-burnup LOCA analysis. This high-fidelity work will demonstrate a best estimate pin-by-pin high-burnup BWR LOCA analysis to assess full-core cladding rupture behavior. This modeling capability will help with better understanding and realistic evaluation of fuel fragmentation, relocation, and dispersal (FFRD) phenomena at BWRs, which then could be used to prevent FFRD at BWRs without penalizing operational parameters. In addition, the results of this work will help identify strategies to identify additional margins or to potentially limit cladding rupture through core design optimizations.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

High-burnup boiling water reactor steady-state operating conditions and fuel performance analysis

The primary operational costs for existing nuclear reactors are plant operation costs, maintenance costs, and fuel costs, all of which are influenced by the materials used and the design of the reactor core. Optimizing core design parameters—including burnup limits and enrichment levels—can lengthen cycles, reduce outages, reduce reload batch fractions and spent fuel storage requirements, and lower maintenance and operating expenses, thereby enhancing economic viability. Furthermore, developing higher-fidelity tools to simulate these parameters enables better identification of the available margin, improves overall plant safety, and improves the understanding a given plant’s responses to accident scenarios. Here, in the US, much of the research and development focus has traditionally been on pressurized water reactors (PWRs), but boiling water reactors (BWRs) comprise approximately one-third of the US reactor fleet. Modeling and simulation advances for BWRs and PWRs—particularly those achieved through the Nuclear Energy Advanced Modeling and Simulation (NEAMS) program—are crucial to the long-term viability of the light–water reactor industry. A key research area of the high burnup and increased enriched fuel initiative is focused on addressing issues related to postulated loss-of-coolant accident (LOCA) scenarios. NEAMS has dedicated significant effort to enhancing tools to better support BWRs. A current focus is showcasing the BWR framework for high-burnup LOCA analysis. This high-fidelity steady-state analysis is a first step toward demonstrating a best-estimate, pin-by-pin high-burnup BWR LOCA analysis to assess full-core cladding rupture behavior for a representative BWR. The objective of this effort is to provide a modeling capability that will help elucidate and provide a best-estimate evaluation for cladding rupture susceptibility in BWRs. This modeling capability could then be used to prevent and/or mitigate cladding ruptures in postulated accident scenarios without penalizing operational parameters. Additionally, the results of this work will help identify strategies for finding additional margins or potentially limiting cladding ruptures through core design optimizations to enable more efficient core designs.

Capps, Nathan [Oak Ridge National Laboratory (ORNL↗

Resilience Assessment Framework For Electric Distribution Systems Performance Under Extreme Conditions

The devastating impact of extreme weather-related events is increasingly evident on power grids, especially on distribution grids. The severity of their potential impact calls for 1) developing a suitable resilience assessment framework to capture the system performance and 2) assessing relevant mitigative strategies to lessen the impact of such events. This paper proposes a framework to identify grid vulnerabilities using the energy-at-risk concept to select, disconnect and isolate grid portions due to a resilience event. The proposed framework mainly consists of two steps; i) processing the utility's available infrastructure, i.e., a network model, possible switching combinations, and outage information for those combinations, as a graph-based database, and ii) implementing a novel optimal switching algorithm leveraging database and grid simulated metrics. These switching actions are generated to implement load curtailment in a rolling manner during anticipated grid scarcity conditions. In this study, a test case is created using two taxonomy feeders and is simulated against an extreme temperature event, e.g., a long, relatively cold, and prolonged freeze peak, thereby creating stress on the grid. It is demonstrated that the proposed framework allows utilities to predict the energy-at-risk during such resilience events and design suitable outage management strategies.

Poudel, Shiva↗

Project Planning for Community Resilience: Aquinnah and Chilmark, Massachusetts

This report presents the findings of an energy system planning study for the towns of Aquinnah and Chilmark, MA, on the island of Martha’s Vineyard, conducted under the U.S. Department of Energy ETIPP program. The study used the DER-CAM model to optimize the deployment of PV and battery microgrids to enhance energy resilience against power outages, particularly winter storms. Key findings show that PV is highly cost-effective and delivers net annual savings. However, due to limited rooftop space and low winter solar output, PV and battery storage alone cannot support the full critical load during outages. Solutions incorporating conventional backup generators were found to be more economically viable for achieving 100% critical load support.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Community Resilience Through Rapid Restoration Leveraging Distributed Energy Resources (DERs) and Low-Cost Sensors

Equitable and automated bottoms-up power restoration following an extreme event will be demonstrated at a site in Puerto Rico. To do so, the team will develop enhanced grid situational awareness techniques integrating behind-the-meter (BTM) distributed energy resources (DER) discovery, impedance sweeping based outage boundary detection, and feasible restoration path identification algorithms. Resilience metric will be developed and incorporated along with situational awareness information in a distributed Model Predictive Control (MPC)-based restoration optimization algorithm to control and mobilize grid assets. These algorithms will be validated through power hardware-in-the-loop experiments and ultimately, a site demonstration to show that outage recovery time and total recovered load could be improved by >20% over the baseline.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Designing for Zero Energy and Zero Carbon on a Multi-Building Scale Using URBANopt: Preprint

Groundbreaking efforts are necessary to mitigate contributors increasing impacts of climate change. In parallel to inventing pioneering clean energy technologies it is even more fundamental to rethink designing energy systems within a singular facility and collectively to function as a district. Facilities should not be continuously passive by just consuming; there is a need to shift to perform more dynamically. Designing for zero energy and zero carbon on a multi-building scale can uncover opportunities for building energy efficiency, decarbonization, demand flexibility, and resiliency that are not accessible at an individual building scale. This approach can be challenging without innovative tools to evaluate the multitude of possibilities. As an investigated result, we highlight the use of a campus-scale energy modeling platform - URBANopt™ - for the expansion of the National Renewable Energy Laboratory's (NREL's) South Table Mountain campus in Golden, Colorado. Programmatic growth included the design of three new all-electric, zero-energy, and zero-carbon, mixed used buildings (a combination of research laboratories and office space). This investigation is critical to NREL reaching net-zero emissions for its operational footprint, which will occur in phases over the next decade. Leveraging URBANopt's capabilities, we evaluate 1) high-performance building energy efficiency and decarbonization measures, 2) 4th generation district heating and cooling (4th GDHC) systems, 3) optimized onsite generation and energy storage assets that meet zero-energy and zero-carbon targets at minimum life-cycle costs, and 4) cost-optimal distributed energy technology mixes, dispatch strategies, and associated capacities that increase resiliency to grid outages. This work demonstrates the use and capabilities of URBANopt through a real-world case study on a multi-building scale.

community energy model↗

Machine Learning for Scalable and Optimal Load Shedding Under Power System Contingency

Prompt and effective corrective actions in response to unexpected contingencies are crucial for improving power system resilience and preventing cascading blackouts. The optimal load shedding (OLS) accounting for network limits has the potential to address the diverse system-wide impacts of contingency scenarios as compared to traditional local schemes. However, due to the fast cascading propagation of initial contingencies, real-time OLS solutions are challenging to attain in large systems with high computation and communication needs. In this paper, we propose a decentralized design that leverages offline training of a neural network (NN) model for individual load centers to autonomously construct the OLS solutions from locally available measurements. Our learning-for-OLS approach can greatly reduce the computation and communication needs during online emergency responses, thus preventing the cascading propagation of contingencies for enhanced power grid resilience. Numerical studies on both the IEEE 118-bus system and a synthetic Texas 2000-bus system have demonstrated the efficiency and effectiveness of our scalable OLS learning design for timely power system emergency operations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Enhancing Distribution Grid Resilience Through Model Predictive Controller Enabled Prioritized Load Restoration Strategy

Effective resilience improvement strategies enable the power grid to cope with disruptive extreme events. Most power grid outages are caused by disruptions in distribution grids. Motivated by the urgent need for power system resilience research, this paper proposes a priority-weighted optimal load restoration technique to enhance the resilience of distribution grids against extreme events. The proposed technique is based on smart distribution technology and framed as sequential multi-step decision process (MDP) and mixed integer linear program (MILP). It is formulated as optimal control problem with a model predictive control (MPC) approach. We applied the devised MILP-MPC-based load restoration technique to a simplified single-bus version of the IEEE 13-bus distribution system with integrated distributed energy resources (DERs) such as wind turbine, photovoitaic array, microturbine, and energy storage device. The technique executes a reducing and rolling horizon optimization in each control step in real-time using the forecasted information of the renewables, the fuel status of the microturbine and the state of charge of the energy storage device. We consider an extreme event which triggered outage of the upstream utility grid and caused islanded operation of the distribution grid. We demonstrated the effectiveness of the proposed MPC approach in restoring the distribution grid loads based on their priority during the main grid outage-caused islanded operation.

61 RADIATION PROTECTION AND DOSIMETRY↗

Enhancing Distribution Grid Resilience Through Model Predictive Controller Enabled Prioritized Load Restoration Strategy: Preprint

Effective resilience improvement strategies enable the power grid to cope with disruptive extreme events. Most power grid outages are caused by disruptions in distribution grids. Motivated by the urgent need for power system resilience research, this paper proposes a priority-weighted optimal load restoration technique to enhance the resilience of distribution grids against extreme events. The proposed technique is based on smart distribution technology and framed as sequential multi-step decision process (MDP) and mixed integer linear program (MILP). It is formulated as optimal control problem with a model predictive control (MPC) approach. We applied the devised MILP-MPC-based load restoration technique to a simplified single-bus version of the IEEE 13-bus distribution system with integrated distributed energy resources (DERs) such as wind turbine, photovoltaic array, microturbine, and energy storage device. The technique executes a reducing and rolling horizon optimization in each control step in real-time using the forecasted information of the renewables, the fuel status of the microturbine and the state of charge of the energy storage device. We consider an extreme event which triggered outage of the upstream utility grid and caused islanded operation of the distribution grid. We demonstrated the effectiveness of the proposed MPC approach in restoring the distribution grid loads based on their priority during the main grid outage-caused islanded operation.

61 RADIATION PROTECTION AND DOSIMETRY↗

Enhancing Distribution Grid Resilience Through Model Predictive Controller Enabled Prioritized Load Restoration Strategy

Effective resilience improvement strategies enable the power grid to cope with disruptive extreme events. Most power grid outages are caused by disruptions in distribution grids. Motivated by the urgent need for power system resilience research, this paper proposes a priority-weighted optimal load restoration technique to enhance the resilience of distribution grids against extreme events. The proposed technique is based on smart distribution technology and framed as sequential multi-step decision process (MDP) and mixed integer linear program (MILP). It is formulated as optimal control problem with a model predictive control (MPC) approach. We applied the devised MILP-MPC-based load restoration technique to a simplified single-bus version of the IEEE 13-bus distribution system with integrated distributed energy resources (DERs) such as wind turbine, photovoltaic array, microturbine, and energy storage device. The technique executes a reducing and rolling horizon optimization in each control step in real-time using the forecasted information of the renewables, the fuel status of the microturbine and the state of charge of the energy storage device. We consider an extreme event which triggered outage of the upstream utility grid and caused islanded operation of the distribution grid. We demonstrated the effectiveness of the proposed MPC approach in restoring the distribution grid loads based on their priority during the main grid outage-caused islanded operation.

61 RADIATION PROTECTION AND DOSIMETRY↗