Search NASA⌕ Search

SEARCH · Search NASA

Results for “grid following (GFL)”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 73 records · Page 4

Study of Inverter Control Strategies on the Stability of Low-Inertia Microgrid Systems

This paper investigates the stability of low-inertia microgrid systems with two control strategies that have different percentages of grid-forming (GFM) inverters. The first control strategy has approximately 50% GFM inverters, and all the battery inverters are working in GFM control mode. Originally, the second control strategy has approximately 10% GFM inverters, with only two battery inverters working in GFM control mode and the rest working in grid-following (GFL) PQ control mode based on current control, which cannot stabilize the microgrid system. Then, the second control strategy is modified to change the GFM inverters from droop control to isochronous control and the GFL battery inverters from traditional current control to voltage control for power control. Both control strategies can maintain system stability; however, the first control strategy can better handle contingency events. The study indicates that 1) a microgrid system with a higher percentage of GFM inverters has better stability; and 2) a microgrid with a lower percentage of GFM inverters can have poor stability, but improved control strategies in inverters can improve system stability. This study improves the understanding of how different percentages of GFM inverters and inverter control strategies affect the system stability of low-inertia microgrids.

droop control↗

Inverter Controls for Smooth Transition Operation of Networked Microgrids

Islanding sections of a distribution grid as microgrids and networking these microgrids offer promising opportunities for improving system reliability; however, this approach may need distributed energy resources (DERs) to switch between grid-connected and islanded operation without affecting the system stability. The Thevenin impedance of the power system at the DER point of common coupling changes due to networking actions. It is critical to have smooth transitions between modes to ensure stable system operation and to avoid nuisance tripping. This paper presents the design of a grid-forming (GFM)-capable inverter control scheme to reliably operate in distribution systems with networked microgrids. Control mechanisms for smooth transitions between grid-following (GFL) and GFM inverter modes are presented. First, we test the control mechanism on a simple two-source power system through electromagnetic transient (EMT) simulations using a digital real-time simulator. Then, we add multiple such DERs to the EMT model of a real-world distribution feeder and demonstrate stable operation between mode transitions during the networking of the microgrids.

grid forming controls↗

Interoperable, Inverter - Based Distributed Energy Resources Enable 100% Renewable and Resilient Utility Microgrids

As microgrids transition away from use of conventional generating resources and increasingly rely on renewable resources towards decarbonization goals, it is crucial to evaluate the capability inverter-based resources to provide microgrid stability and resilience. Particularly, microgrids with a high contribution of intermittent solar photo voltaic generation and higher load variability present unique challenges requiring fast voltage and frequency support. At the San Diego Gas & Electric Company(R) (SDG&E(R)) Borrego Springs Microgrid, a battery inverter was upgraded with grid-forming (GFM) capability to serve as island leader, transitioning responsibility away from diesel generators. An interoperable microgrid control scheme was developed, coordinating GFM and grid-following (GFL) inverters. Hardware-in-the-loop (HIL) simulations using relevant power and controller HIL interfaces between real-time simulators and field equipment are being conducted to de-risk field deployment.

battery energy storage↗

A Generic and Multifunctional Electromagnetic Transient Model for Grid-Following Inverters

This article presents a generic and multi-functional electromagnetic transient (EMT) dynamic model of grid following (GFL) inverter-based resource (IBR) using the PSCAD software platform. The features of the developed model includes the flexibility in selecting various types and combinations of DC sources covering PV modules, battery modules, ideal DC source module, as well as flexibility in selecting either switched or averaged model of inverter. This model also covers exhaustive lists of controller logic covering open-loop/closed-loop PQ dispatch control, DC voltage and AC terminal voltage control along with the conventional current control designed in dq-domain, ate- domain and positive-negative sequence domain. Moreover, this model is equipped with the flexibility in selecting various types of current limiting schemes that includes saturation-based as well as latching-based current limiter, anti-windup protection. Moreover, the EMT model is agnostic to the MVA rating and is suitable for interfacing transmission systems by being complaint with the IEEE Std. 2800. The generality in the power circuits and the multi-functional options in operation and control of the developed EMT model makes it suitable for both academia and industry to study various power system aspects not limited to but such as fault behavior of GFL IBR and impacts on protection system, transient stability of a system interfaced with large number of GFL IBRs etc.

14 SOLAR ENERGY↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters: Preprint

This paper investigates operational techniques to achieve smooth microgrid (MG) transitions by dispatching the grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control mode during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worthy to explore how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. As expected, the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires the GFM inverter(s) to maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-following control↗

Transient Stability Study of a Real-World Microgrid with 100% Renewables: Preprint

This paper performs a transient stability study of a real-world microgrid with 100% renewables to fully understand the stability and reliability of the microgrid under various dynamic scenarios. In particular, the operation of multiple grid-forming (GFM) and grid-following (GFL) inverters in such a power system is not well understood under dynamic operation conditions, such as islanding and black start; therefore, in this paper, the full-scale electromagnetic transient modeling of the microgrid is developed to investigate the stability of the system under various dynamic operating conditions and to identify potential reliability risks. The PSCAD/EMTDC simulation with the high-fidelity model provides helpful insights into the optimal operation modes of GFM and GFL inverters as well as the stability and reliability of the microgrid, which gives good references for the field deployment in terms of inverter configuration and coordination as well as the capabilities of black start and unplanned islanding.

100% renewable microgrid↗

UNIFI's Grid-Forming (GFM) Inverter Reference Design: A Tutorial on Modeling, Control, and Experimental Implementation of GFM Inverters

The UNIFI Consortium's tutorial on grid-forming (GFM) inverters provides a comprehensive guide to the modeling, control, and experimental implementation of GFM inverters. As the integration of renewable energy accelerates, the transition from traditional grid following (GFL) to GFM inverters is crucial to ensure stable and sustainable power systems. This document outlines a reference design for three-phase and single-phase GFM inverters developed at the University of Texas at Austin. The tutorial also provides step-by-step guidance for accessing and using UNIFI’s GitHub repository, enabling users to design, build, and test GFM inverters efficiently. By fostering collaboration and equipping users with accessible resources, this initiative aims to drive widespread adoption of GFM technology across academia, utilities, and industries.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters

This paper investigates operational techniques to achieve seamless (smooth) microgrid (MG) transitions by dispatching a grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control modes during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worth exploring how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. The results show that the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires that the GFM inverter(s) maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-forming control↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters

This paper investigates operational techniques to achieve seamless (smooth) microgrid (MG) transitions by dispatching a grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control modes during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worth exploring how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. The results show that the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires that the GFM inverter(s) maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-forming↗

Standard Library Grid-Forming Hybrid Control Inverter-Based Resource Model Specification (REGFM_C1)

This document describes a standard library grid-forming (GFM) hybrid control inverter-based resource (IBR) model. The GFM hybrid control approach implements both a typical GFM control and a typical grid-following (GFL) control inside one single inverter simultaneously, so that it can take advantage of both methods without comprising the benefits of a typical GFM. The initial version of model specification was jointly developed by Pacific Northwest National Laboratory (PNNL), Tesla Energy, and EPRI, and it was revised multiple times later to incorporate suggestions from WECC MVS members. Tesla Energy provided main control blocks to support the development of this model specification. This standard library model is developed to help the utility industry better understand the GFM technology. The model could be used to represent equipment for long-term planning studies where vendor-specific models are not available. As equipment matures and improves, standard library models will be updated to capture the new functionalities of GFMs. It is not intended that these models will always remain representative of all future GFM technologies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Reinforcement Learning‐Based Adaptation of Grid Following Inverter's Internal Controller to Networked Microgrids' Strengths

The varying topological configurations, generator commitments and dispatches, and dynamic load demand lead to changing system's strengths during the operations of networked microgrids. When the system's strengths significantly change, the fixed control gains at large devices may result in unsatisfactory system performance; this necessitates the tuning of the control gains at large devices to adapt to the changing system's strengths. In this paper, observer-based reinforcement learning (RL) is utilised to automatically tune the proportional-integral (PI) gains of phase lock loop (PLL) controller of grid-following (GFL) inverters to adapt to the changing strengths of microgrids and networked microgrids. The RL agent in this framework augments an observer predicting system's strengths, from which the RL control policy will adjust accordingly to tune the PLL controller's gains towards the system's strengths. Also, to enhance the control performance, the recently introduced Barrier function-based RL framework is leveraged for the design of reward function to prevent the high frequency nadir. An operational 26 kV electric distribution system, which is modelled as networked microgrids, is used to illustrate the need and effectiveness of the proposed RL-tuned control.

frequency response↗

High-Performance Transmission and Distribution Co-simulation with 10,000+ Inverter-Based Resources

The inverter-based resource (IBR) has become avery important component in the distribution system. The impacts on system transient stability introduced by high IBR penetration are not fully addressed because of the lack of high-fidelity models. The aggregate IBR model at the transmission level cannot precisely reproduce the dynamics of distributed IBR at the distribution system because of the oversimplification. In this paper, we will develop a high-penetration fully-connected transmission and distribution (T&D) co-simulation platform that supports the simulation of 10,000+ dispersed IBR models. The interfacing and iterative initialization techniques for the co-simulation have been implemented to maintain stable operation and simulation of large-multitude of IBR models. The phasor-domain IBR models with grid-forming (GFM) and grid-following (GFL) control are implemented in the distribution systems simulators. The developed platform is tested on high-performance computing (HPC) resources and can be utilized to explore the hierarchical control strategies of IBRs for the large-scale T&D hybrid system.

Liu, Yuan↗

Searching for Grid-Forming Technologies That Do Not Impact Protection Systems: A promising technology

The design of legacy-line protection elements has been guided by the behavior of synchronous machines during faults. Because of the significant field-winding inductance and rotating mass, the magnitude, angular frequency, and phase angle of the back-electromotive force (EMF) voltage waveforms of synchronous machines remain practically constant for several hundreds of milliseconds after a fault occurs. Furthermore this has facilitated the engineering of the memory-polarization technique in mho distance elements, which has been effective for machine-dominant power grids. However, this assumption is no longer held for inverter-based resources (IBRs) because of the lack of field winding and moment of inertia in power electronics devices. Notably, the negative-sequence directional overcurrent protection and the quadrilateral distance elements have been impacted by early IBRs with grid-following (GFL) controls because they did not inject negative-sequence currents during asymmetrical faults.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Efficient Topology Assessment for Integrated Transmission and Distribution Network with 10,000+ Inverter-based Resources

The renewable energy proliferation calls upon the grid operators and planners to systematically evaluate the potential impacts of distributed energy resources (DERs). Considering the significant differences between various inverter-based resources (IBRs), especially the different capabilities between grid-forming inverters and grid-following inverters, it is crucial to develop an efficient and effective assessment procedure besides available co-simulation framework with high computation burdens. This paper presents a streamlined graph-based topology assessment for the integrated power system transmission and distribution networks. Graph analyses were performed based on the integrated graph of modified miniWECC grid model and IEEE 8500-node test feeder model, high performance computing platform with 40 nodes and total 2400 CPUs has been utilized to process this integrated graph, which has 100,000+ nodes and 10,000+ IBRs. The node ranking results not only verified the applicability of the proposed method, but also revealed the potential of distributed grid forming (GFM) and grid following (GFL) inverters interacting with the centralized power plants.

Graph Analysis, Topology evaluation, Infrastructur↗

Examining the Feasibility of Modeling the Inner Current Loop of a Grid-Following Inverter in the Phasor-Based Solver

Historically, when modeling a grid-following (GFL) inverter in the phasor domain, the fast inner current loop is typically ignored. To achieve a more accurate modeling, the authors have attempted to model the inner current loop in the phasor domain, but experienced significant numerical stability issues. This paper conducts a detailed analysis and provides insight into the feasibility of modeling the inner current loop of a GFL inverter in the phasor domain. It points out that: a) because of the neglection of the inverter filter dynamic, the bandwidth of the inner current loop becomes infinite with typical parameters in the phasor domain, resulting in an inaccurate representation of the actual inner current loop, whose bandwidth is typically between 600 Hz to 2 kHz, and b) the relatively large simulation time step in the phasor simulation causes numerical stability issues when simulating such an inner current loop with an infinite bandwidth. Detailed electromagnetic (EMT) and phasor modeling, and frequency response analysis are performed to explain this phenomenon. The findings of this paper explain why it is inappropriate to model the fast current loop of a GFL inverter in the phasor domain.

Mohiuddin, Sheik Mohammad↗

A Generic and Multifunctional Electromagnetic Transient Model for Grid-Following Inverters

This paper presents a generic and multifunctional electromagnetic transient (EMT) dynamic model of grid-following (GFL) inverter-based resources (IBRs) using the PSCAD software platform. The features of the model include flexibility in selecting various types and combinations of DC sources covering photovoltaic modules, battery modules, and ideal DC-source modules as well as flexibility in selecting either switching or averaged models of the inverter. This model also covers exhaustive lists of controller algorithm, including open-loop/closed-loop PQ dispatch control, DC voltage and AC terminal voltage control, and conventional current control designed in the dq-domain, the ..alpha....beta.. -domain, and the positive-/negative-sequence domain. Moreover, this model is equipped with flexibility in selecting various types of current-limiting schemes, including saturation-based and latching-based current limiters, and anti-windup protection. Also, the EMT model is agnostic to the MVA rating and is suitable for interfacing transmission systems by complying with IEEE Std. 2800. The generality in the power circuits and the multifunctional options in the operation and control of the developed EMT model make it suitable for both academia and industry to study various power system aspects, including, but not limited to, the fault behavior of GFL IBRs, the impacts on the protection system, and the transient stability of a system interfaced with large numbers of GFL IBRs.

integrated circuit modeling↗

UPS XML Format and Data

This is the XML data and format for UPS supercomponent including subcomponents: Grid following inverter (GFL), Grid forming inverter (GFM), and dc-dc converter connected to the energy storage and the AI load.

Marthi, Phani Ratna Vanamali [ORNL] (ORCID:0000000↗

How a Large-Scale Deployment of Grid-Forming Inverters May Impact Inter-Area Oscillation Modes: An Investigation in the US Western Interconnection

This report describes work performed to evaluate the impact of high grid-forming (GFM) inverter penetration on the inter-area oscillation mode characteristics of the Western Interconnection. Using simulations, this work analyzes how: a) replacing fossil-fuel-based synchronous generators by GFM inverters will impact properties of the North-South mode, and b) replacing the Colstrip power plant by grid-following (GFL) and GFM inverters will change the characteristics of the Montana mode. Results obtained indicate that high penetration of GFM inverters will significantly alter inter-area oscillation characteristics in interconnections. Low frequency oscillations in the 0.11 Hz range will be predominantly driven by remaining synchronous machines, and hence their relative distribution in the interconnection will impact mode characteristics and observability.

20 FOSSIL-FUELED POWER PLANTS↗