Real Time Phasor Analytics (RTPA) and RTPA-SCR System Strength Online Tool

This presentation showcases the Real-Time Phasor Analytics (RTPA) framework for monitoring inertia and assessing system strength in power grids. RTPA is an open-source tool designed to standardize access to data from Power Management Units (PMUs) and Phasor Data Concentrators (PDCs). It facilitates real-time connectivity to multiple PDCs in accordance with the IEEE C37.118-2 standard and supports asynchronous data stream integration. Additionally, RTPA can simulate a PDC server streaming C37.118-2 data and provides Python bindings for seamless interaction with the framework, eliminating the need for direct Rust programming.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Line Faults Classification Using Machine Learning on Three Phase Voltages Extracted from Large Dataset of PMU Measurements

An end-to-end supervised learning method is developed to classify transmission line faults in a twoyear field-recorded dataset that includes synchronized measurements of three-phase voltages recorded by 38 Phasor Measurement Units (PMU) sparsely located in in the US Western Grid interconnection. Statistical analysis is performed to extract features from this large dataset to train Support Vector Machine (SVM), Random Forest (RF), and eXtreme Gradient Boosting (XGBoost) classifiers initially. The training further leverages a simulated dataset from a synthetic grid with 12 PMUs to increase the number of faults of types infrequently seen in the field-recorded dataset. Training the classification models with the combined dataset resulted in a classification accuracy of 97.7%. This is a significant improvement over 89.7% to 92.5% accuracy obtained by relying on the field-recorded dataset alone.

47 OTHER INSTRUMENTATION↗

Cyber-Power Co-Simulation for End-to-End Synchrophasor Network Analysis and Applications

The resiliency, reliability and security of the next generation cyber-power smart grid depend upon efficiently leveraging advanced communication and computing technologies. Also, developing real-time data-driven applications is critical to enable wide-area monitoring and control of the cyber-power grid given high-resolution data from Phasor Measurement Units (PMUs). North American Synchrophasor Initiative Network (NASPlnet) provides guidance for PMU data exchanges. With the advancement in networking and grid operation, it is necessary to evaluate the performance of different data flow architectures suggested by NASPInet and analyze the impact on applications. Therefore, we need a cyber-power co-simulation framework that supports very large-scale co-simulation capable of running in parallel, high-performance computing platforms and capturing real-life network behavior. This work presents an end-to-end automated and user-driven cyber-power co-simulation using NS3 to model communication networks, GridPACK to model the power grid, and HELICS as a co-simulation engine. Comparative analysis of latency in synchrophasor networks and a performance evaluation of a power system stabilizer application utilizing PMU data in an IEEE 39 bus test system is presented using this cosimulation testbed.

Mustafa, Hussain M.↗

Dynamic Phasor Modeling of Multi-Converter Systems

Generalized form of Dynamic Phasor (DP)-based modeling of multi-converter systems containing high order harmonics has not been proposed in the literature yet due to the complexity and large number of variables that should be included in the model. In this work a generalized form of a system-level model comprising high number of single-phase converters is presented. The proposed method can be applied to any number of single-phase voltage source converters (VSIs). Test cases of this modeling method containing 5 to 100 parallel connected single-phase voltage source inverters are modeled and simulation times are recorded. The results of the proposed method are compared and validated with conventional average models as well as detailed switching models. A systematic approach for comparing the accuracy and timestep between dynamic phasor modeling method and detailed switching model is illustrated. Advantage of DP models over conventional average models for stability assessment are also discussed at the end of the paper.

Xue, Yaosuo↗

Phasor-Based Control for Scalable Integration of Variable Energy Resources

We propose an innovative framework termed phasor-based control (PBC) to facilitate the integration of heterogeneous and intermittent distributed energy resources (DER) on the electric grid. PBC presents a unified approach that is agnostic to optimization criteria and to the particular characteristics of participating resources. It is enabled by synchronized, high-precision voltage phasor measurements that allow stating control objectives in grid-specific, rather than resource-specific, terms. We present qualitative justification and examine the general feasibility of this control approach, including the behavior of candidate control algorithms in simulation. Initial results suggest that PBC has significant potential to support stable and resilient grid operations in the presence of arbitrarily high penetrations of DER.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Wavelet and Deep-Learning-Based Approach for Generation System Problematic Parameters Identification and Calibration

Accurate models of generation systems are critical for maintaining reliable and secure grid operations. In this paper, a novel and systematic approach is proposed to identify and calibrate the generation system problematic parameters using continuous wavelet transform (CWT) and advanced deep-learning technology. The phasor measurement unit (PMU) data are used through “event playback” to check whether the parameter calibration is required, and if yes, a group of suspicious parameters will be identified as the primary problematic parameter candidates (PPCs). These primary PPCs are randomly perturbed to generate the event playback simulation data, which are used by the CWT and convolutional neural networks (CNNs) to further narrow down the primary PPCs into a smaller set of candidates. Then, the identified candidates are perturbed again to generate massive event playback simulation data for training a parameter calibration neural network. Here, we designed a multi-output neural network structure to find the mappings between the perturbed parameters and the simulation data using both CNN and long short-term memory (LSTM) models. Finally, the well-trained and tested CNN-LSTM model is used to estimate the accurate value of the suspicious parameters with actual PMU measurements. The proposed CNN-LSTM network can accurately and reliably estimate the generation-system problematic parameters, and has better performance when compared to other machine-learning methods, such as the multilayer perceptron network and the conditional variational autoencoder method. The accuracy and effectiveness of the proposed approach have been validated through simulation and real-world data.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Secondary-Side Active Rectifier Synchronization and Control in LCC-LC Compensated Inductive Power Transfer Systems

This paper proposes a communication-less synchronization and output power control strategy for LCC-LC compensated inductive power transfer systems with a secondaryside active rectifier. By replacing the passive rectifier with an active bridge, the proposed architecture eliminates the need for a separate secondary-side DC-DC converter and enables direct regulation of battery power. The key challenge in such a system is achieving robust synchronization of the secondary active bridge with the primary inverter without access to primary-side signals. To address this issue, the secondary-side variables are analyzed and the current through the secondary series inductor is identified as a load-independent synchronization variable with a fixed phase relationship to the primary excitation. A fixed-frequency second order generalized (SOGI)-based phase locked loop (PLL) is used to estimate the switching phase and frequency, and a phase-shift-based output power controller is developed using a phasor-transformer model of the active bridges. A modified control formulation is further introduced to remove phase-dependent loop-gain variation and simplify controller design. Simulation results validate the proposed method under both fixed and varying switching-frequency conditions, demonstrating successful frequency tracking from 82 kHz to 88 kHz and accurate output power regulation over a wide operating range. The proposed method offers a compact and effective solution for high-power IPT systems by enabling secondary-side synchronization and control without wireless communication or an additional DC-DC conversion stage.

Fernandes, Arnold Anthony [ORNL] (ORCID:0009000631↗

Dynamic Performance Comparison and Prediction based on Distribution-level Phasor Measurement Units

This paper introduces a new distribution level Phasor Measurement Unit (PMU) which adopts advanced hardware components and structure. The hardware parameters from the new PMU and the existing PMU are used to build a simulation model to predict the PMU performance. Therefore, a real-world testbench is built and four distribution level PMUs are tested under the steady-state and dynamic tests. The quantitative experiment result confirms the prediction model which could guide future PMU design, and also verifies the accuracy of the new PMU on the synchrophasor and frequency measurements in multiple scenarios.

Wu, Yuru↗

Simulated performance of coded PCM/FM modem on Rician fading channel

This paper describes a simulation approach to characterizing the performance of a coded PCM/FM modem operating on the classical Rician fading channel. In particular, we consider the performance of short constraint length convolutional codes in conjunction with Viterbi maximum likelihood decoding. The receiver consists of a narrowband filter followed by an ideal limiter/discriminator. Primary interest is in the bit error probability performance parameterized by both the fading channel and receiver parameters. Particular attention is given to simulating the impulse noise appearing at the discriminator output. This is the 'click' noise caused by encirclements of the origin by the instantaneous signal-plus-noise phasor. Results include the effects of channel memory and narrowband receiver filtering effects on overall bit error probability.

Modestino, J. W.↗

Dynamic Parameter Estimation with Physics-based Neural Ordinary Differential Equations

Accurate estimation of dynamic parameters of gen-erators is crucial to building a reliable model for dynamical studies and reliable operation of the power system. This paper develops a physics-based neural ordinary differential equations (ODE) approach to learn the parameters of generator dynamic model using phasor measurement units (PMU) data. We design a physics-based neural network to represent the swing equations of the power system dynamics. A loss function is defined as the difference between dynamic simulation results from the physics-based neural networks and pseudo PMU measurements. The parameters of generator dynamic model are iteratively updated using the neural ODEs and the adjoint method. By exploiting the mini-batch scheme in neural ODE training, the parameter estimation performance is significantly improved. Numerical study results on a 3-machine 9-bus system show that the proposed algorithm outperforms state-of-the-art baseline method in both computation time and dynamic parameter estimation accuracy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Local Phasor-Based Control of DER Inverters for Voltage Regulation on Distribution Feeders

We introduce a new control paradigm termed Phasor-Based Control (PBC) to coordinate Distributed Energy Resources (DER) for improved voltage regulation and other objectives. PBC is a multi-layer control framework where the state of the distribution grid is represented by voltage phasors, and Phasor Measurement Units (PMUs) measure the state at critical points in the distribution grid. In the PBC paradigm, a supervisory controller (S-PBC) sets phasor targets which local controllers track. In this paper, we propose a Proportional Integral (PI) implementation for the local control layer (LPBC), to regulate real and reactive power output of distributed inverters to track a voltage phasor target computed by the supervisory layer. We tune the PI controller gains offline with a genetic algorithm that yields better performance than the Ziegler-Nichols method. We benchmark the proposed L-PBC controller against droop volt-var control (DVVC) and observe improved voltage regulation in simulation on the IEEE 13 node unbalanced test feeder (IEEE 13NF). Furthermore, by means of numerical simulation we observe the response of the L-PBC controllers to small and large grid disturbances. Simulations on larger feeders, IEEE 123-node and 647-node, demonstrate challenges with tuning controllers in setups with different amounts of power-voltage coupling.

42 ENGINEERING↗

Sensor enabled data-driven predictive analytics for modeling and control with high penetration of DERs in distribution systems

The electric power grid is undergoing a tremendous transformation due to the increasing penetration of renewable energy resources beginning with wind and more recently with the distributed energy resources (DERs) such as solar and battery storage. DERs have dramatically changed the role of the distribution systems in the overall power grid, and they are expected to contribute a significant portion of power generation in the future. If current trends for DERs continue, system operation and control will need to change dramatically for improved grid reliability and resiliency. As renewable resources increase in penetration, new and challenging operational, planning, and design problems are expected to emerge. Some of the key challenges that arise in the planning and operation of the future grid are: 1) Quantifying the impact of high DER penetration in distribution systems on bulk grid behavior over multiple time scales. 2) Identifying whether a particular DER configuration/settings have a large impact on the overall grid behavior. These challenges can be addressed in an offline manner using detailed T&D grid models and they can also be addressed in an online manner using sensor measurements. In particular, the advancement and planned growth in sensor technology in power grid over various voltage levels provide us with a unique opportunity to tackle these challenges from a data analytic perspective without needing detailed T&D grid models. A few questions that naturally arise when addressing the challenges from DERs using sensor data are: 1) How can we use limited sensor measurements to monitor & control voltage stability and small signal stability of the bulk system? 2) How can we ensure that the developed data analytic methods are robust to data availability and quality issues? 3) How can we compute the developed analytics in a scalable manner using streaming measurements? In this project, we addressed the aforementioned challenges arising from DERs and answered the questions raised above on how to effectively use the sensor measurements to enhance the reliability and performance of the electric grid. Thus, the overarching goal of this project is to develop effective reduced/representative system models from data that make the computational complexity sufficiently manageable so as to be useful to simulate, analyze, and even control complex non-linear power systems dynamics with large penetrations of DERs. In order to achieve the objective, the project team established a four-fold technical approach 1) Formulated a combined transmission-distribution co-simulation framework for data generation and validation, 2) Derived reduced/representative models of power systems based on data-driven methods for efficient computation and appropriate representation of system behavior, 3) Developed data driven characterization of power system behavior based on transfer operator theory, machine learning and optimization for model estimation, 4) Incorporated a scalable data management and processing architecture using distributed Kafka streaming applications that coordinate input data streams to the developed data analytics. The key accomplishments of the project are: 1) Development of a scalable multi-timescale T&D co-simulation framework (both for steady state and for dynamic co-simulation) using commercial solvers (PSSE and GridLAB-D). The steady-state T&D co-simulation interface is shared with our industry partner (PJM). 2) A structured reduced order dynamic model of distribution systems that can represent partial motor stalling along with a systematic procedure to derive the model parameters. 3) A PMU based online method to monitor, localize and mitigate fault-induced delayed voltage recovery using DER reactive support and load control in distribution systems. 4) Development of linear operator based robust methodologies for dynamic state estimation, uncertainty quantification, system identification and trajectory prediction for power system dynamics. 5) An adaptive damping control for utilizing wind energy resources to provide oscillation damping and system stability. 6) Implementation of Kafka-based framework for efficient processing of streaming data using Linux-based local virtual environment.

DER integration↗

Islanding Detection in Rural Distribution Systems

This paper summarizes the literature on detection of islanding resulting from distributed generating capabilities in a power distribution system, with emphasis on the rural distribution systems. It is important to understand the legacy technology and equipment in the rural distribution electrical environment due to the growth of power electronics and the potential for adding the new generations of intelligent sensors. The survey identified four areas needing further research: 1. Robustness in the presence of distribution grid disturbances; 2. the future role of artificial intelligence in the islanding application; 3. more realistic standard tests for the emerging electrical environment; 4. smarter sensors. In addition, this paper presents a synchro-phasor-based islanding detection approach based on a wireless sensor network developed by the University of Texas at Austin. Initial test results in a control hardware-in-the-loop (CHIL) simulation environment suggest the effectiveness of the developed method.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Non-Stationary Power System Forced Oscillation Analysis using Synchrosqueezing Transform

Non-stationary forced oscillations (FOs) have been observed in power system operations. However, most detection methods assume that the frequency of FOs is stationary. In this paper, we present a methodology for the analysis of nonstationary FOs. Firstly, Fourier synchrosqueezing transform (FSST) is used to provide a concentrated time-frequency representation of the signals that allows identification and retrieval of non-stationary signal components. To continue, the Dissipating Energy Flow (DEF) method is applied to the extracted components to locate the source of forced oscillations. The methodology is tested using simulated as well as real PMU data. In conclusion, the results show that the proposed FSST-based signal decomposition provides a systematic framework for the application of DEF Method to non-stationary FOs.

42 ENGINEERING↗

Evaluating Methods for Measuring Grid Frequency in Low-Inertia Power Systems: Preprint

Accurate measurement of grid frequency is a critical component of reliable grid control. Traditionally, methods such as phase locked loops (PLLs) and discrete Fourier transforms (DFTs) have been used in inverters and phasor measurement units (PMUs) to measure frequency. However, as the percentage of inverter-based resources (IBRs) such as solar and wind has increased, these conventional frequency measurement methods are proving unable to guarantee reliable control in some cases. One challenge is measuring frequency during transient events, where there is a disruption in the steady state sinusoidal voltage. During these events, the underlying frequency of the grid may barely change, but measurement methods report a large spike in frequency due to the disrupted waveform. New methods must balance between suppressing spikes in frequency during faults, and providing fast, accurate, measurements in all other grid operation conditions, especially during events with high rate-of-change-of frequency (ROCOF), which are more prevalent in high-IBR power systems. This paper first surveys frequency measurement methods that have been proposed to reduce measurement errors during transient events. Then, both conventional and more novel frequency measurement methods are tested against an IEEE standard and industry recommendations, and their performance is evaluated for events simulated in PSCAD. Results quantify the trade-offs in performance during different grid conditions and lead to suggestions for the most appropriate frequency and ROCOF measurement methods for low inertia grids.

frequency↗

Novel Data Driven Noise Emulation Framework using Deep Neural Network for Generating Synthetic PMU Measurements

Sensors play a critical role in supporting day-to-day grid operations and they are essential to operator’s decision-making process. Furthermore, sensors and sensor behaviors need to be emulated with grid simulations to perform modeling studies and to design cutting edge power systems applications. Ensuring the accurate behavior of these applications requires accurate emulation of sensors and pertinent signals. However, most grid simulators and modeling tools assume either zero error scenarios or simplistic noise models that may not always correlate to real-world sensors. To address the above issue, this work presents an initial study on the noise characteristics of phasor measurement units (PMUs), along with models for recreating their unique noise signatures. The proposed methods (both analytical and machine-learning-based) provide a substantial increase in a sensor’s model fidelity, a feature that can be leveraged by an end-user application to yield more accurate system representations. The proposed methods were then applied to micro PMU data from the EPFL microgrid campus to extract sensor noise profiles. This data was used to train a deep learning model, which was tested to emulate the noise characteristics present in actual signals. Based on the observed results and the employed data-driven methodology, the proposed methods may be adapted to replicate the behavior of other grid sensors and power new applications capable of detecting sensor degradation and eventual device failures in near real-time.

PMU, noise emulation, synthetic measurements, deep↗

High Frequency Adaptive Instability Suppression Controls in a Liquid-Fueled Combustor

This effort extends into high frequency (>500 Hz), an earlier developed adaptive control algorithm for the suppression of thermo-acoustic instabilities in a liquidfueled combustor. The earlier work covered the development of a controls algorithm for the suppression of a low frequency (~280 Hz) combustion instability based on simulations, with no hardware testing involved. The work described here includes changes to the simulation and controller design necessary to control the high frequency instability, augmentations to the control algorithm to improve its performance, and finally hardware testing and results with an experimental combustor rig developed for the high frequency case. The Adaptive Sliding Phasor Averaged Control (ASPAC) algorithm modulates the fuel flow in the combustor with a control phase that continuously slides back and forth within the phase region that reduces the amplitude of the instability. The results demonstrate the power of the method - that it can identify and suppress the instability even when the instability amplitude is buried in the noise of the combustor pressure. The successful testing of the ASPAC approach helped complete an important NASA milestone to demonstrate advanced technologies for low-emission combustors.

Kopasakis, George↗

Dynamic Equivalence of Large-Scale Power Systems Based on Boundary Measurements

Parallel computing helped speed up many tasks that can be done independently. The advance in gaming industry did not produce a technology that helps the power industry to reduce the computation time for dynamic simulation in individual cases. To perform faster than real-time simulation for the purpose of predicting power system dynamic trajectory, power industry continues to struggle to reduce the system size and simulation time of large-scale power systems while keeping its dynamic behavior under various disturbances. There is also an acute need for real-time dynamic model reduction as more renewables enter the generation mix with dramatic changes in the generation outputs. All existing model reduction solutions are based on having access to a detailed dynamic model of the system. The system changes by the minutes, dynamic models are only updated annually. To solve this problem, wide-area measurements obtained by the phasor measurement unit (PMU) at the boundaries between the reduced system and the study system is used to represent the external area. An artificial neuro-fuzzy inference system (ANFIS) is established to perform the mapping of the measurement to the external equivalent model. Here the external area is regarded as a black-box. Model reduction studies are conducted on the Northeast Power Coordinating Council (NPCC) under various types of contingencies, by using a co-simulation approach between PSS/E and MATLAB. The results look very promising and will be discussed in this paper.