Aggregation of Inverter-Based Resources for Modeling and Simulation

In order to conduct system dynamic studies, it is necessary to have dynamic models of both inverter and plant levels. Detailed and aggregated modeling approaches are two essential options. The detailed modeling method involves capturing the dynamic characteristics of each individual device (e.g., wind turbine or PV array), as well as their interconnections. However, as the scale of the IBR plant increases, the complexity and computation time required for detailed modeling also increase. On the other hand, aggregated modeling offers a more efficient way of representing large-scale IBRs in power system dynamic studies. This approach involves aggregating a large number of wind turbines, PV arrays, inverters, and/or plant controllers into one or a smaller number of equivalent models. In order to analyze the impact of a high-level IBR penetration in power systems, it is important to develop accurate and computationally efficient models for both the detailed and aggregated methods.

14 SOLAR ENERGY↗

Hybrid power plants: An effective way of decreasing loss-of-load expectation

Diversifying variable renewable resources by combining wind, solar photovoltaic, and battery assets in a hybrid power plant can increase renewable energy usage efficiency and improve system flexibility, particularly in distributed energy systems. However, the resilience impact of these systems, particularly outage mitigation, can be difficult to quantify due to uncertainty in resource, energy demand, and outage occurrence. Here, this study outlines a framework to quantify the incremental benefit of hybrid power plant assets for reducing loss-of-load expectation during random outage events. Hybrid power plant performance during outages (considering varying duration and severity) is simulated using a Monte Carlo methodology to reflect uncertainty associated with renewable resource, load demand, and outage timing. Results demonstrate the additional incremental value from increasingly hybrid designs, in which relative capacities of wind, solar photovoltaic, and storage assets contribute to lower loss-of-load expectation than the constituent technologies would alone. The value of added wind or solar capacity increases as the plant composition approaches an equal split. The value of added battery capacity depends on the outage duration and severity, but the first 50 MWh of added storage capacity is the most valuable for reducing the loss-of-load expectation for all plant designs.

14 SOLAR ENERGY↗

Machine learning enables national assessment of wind plant controls with implications for land use

Summary As deployment of wind energy continues to expand, computationally efficient tools for predicting wind plant performance over a wide range of layout designs, technology innovations, and spatial locations are increasingly important for policy and investment decisions. We demonstrate two approaches to training a surrogate model to predict annual energy production (AEP) of parameterized wind plant layouts: one using a Gaussian process (GP) and the other using a fully convolutional neural network (FCNN). We leverage the powerful FCNN architecture by encoding wind plant design parameters and output response surface as an image. The FCNN produces more accurate results than the GP with mean absolute errors equivalent to 1% and 1.9% of plant rated power, respectively, although the GP performs well under limited training data and provides useful uncertainty information. We also evaluate a surrogate model for wake steering, enabling a nationwide assessment of the impact of plant control strategies and plant layout decisions. Across two million locations, we find that wake steering strategies boost AEP with relative gains upwards of 3%. Gains are most pronounced at sites without a dominant wind direction and where layout optimization is less fruitful. Additionally, we perform a nationwide sensitivity analysis showing that wake steering can mitigate wake losses from higher density plant layouts. Our results suggest that regions which have not been previously viable for wind deployment due to moderate wind resources are especially well enhanced by wake steering strategies that could help overcome land constraints and inflexible layout options, potentially identifying new deployment opportunities.

17 WIND ENERGY↗

ExaWind: A multifidelity modeling and simulation environment for wind energy

We introduce the open-source ExaWind modeling and simulation environment for wind energy. The primary physics codes of ExaWind are Nalu-Wind and OpenFAST. Nalu-Wind is a wind-focused computational fluid dynamics (CFD) code that is coupled to the whole-turbine simulation code OpenFAST. The ExaWind environment was created under U.S. Department of Energy funding to achieve the highest-fidelity simulations of wind turbines and wind farms to date, with the goal of enabling disruptive changes to turbine and plant design and operation. Innovation will be gleaned through better understanding of the complex flow dynamics in wind farms, including wake evolution and the impact of wakes on downstream turbines and turbulent flow from complex terrain. High-fidelity predictive simulations employ hybrid turbulence models, geometry/boundary-layer-resolving CFD meshes, atmospheric turbulence, nonlinear structural dynamics, and fluid-structure interaction. While there is an emphasis on very high-fidelity simulations (e.g., blade resolved with full fluid-structure coupling), the ExaWind environment supports lower-fidelity modeling capabilities including actuator-line and -disk methods. Important in the development of ExaWind codes is that the codes scale well on today's largest petascale supercomputers and on the next-generation platforms that will enable exascale computing.

17 WIND ENERGY↗

Quantifying Socioeconomic Impacts of Electricity Generating Technologies

The levelized cost of energy (LCOE) and other cost metrics used in energy planning do not account for out-of-market impacts of the technology choice. While a decision-maker at the utility or asset owner level may compare multiple forms of electricity generating technology using LCOE, a decision-maker over energy policy or community stakeholders may be interested in considering impacts beyond those that LCOE measures. This report quantifies economic impacts such as jobs and wage growth across electricity generation technologies then develops an approach to systematically compare socioeconomic metrics across technology choices. To address additional workforce related impacts, this report also compares the typical workforce education requirements and annual income levels for multiple types of electricity generating facilities. The grid scale electricity generating technologies analyzed in this report produce power using conventional hydroelectric dams, coal, natural gas, nuclear reactors, solar PV, land-based wind turbines, geothermal heat, and woody biomass combustion. Although it doesn’t generate electricity itself, the economic impacts associated with battery storage equipment manufacturing and installation were also analyzed.

03 NATURAL GAS↗

Highlighting the Impact of Yaw Control by Parsing Atmospheric Conditions Based on Total Variation: Preprint

Identification of atmospheric conditions within a multivariate atmospheric dataset is a necessary step in the validation of wind plant control strategies. Most often, operating conditions are characterized in terms of aggregated observations and assume that the atmosphere is 'quasi-steady'. Aggregation of observations without regard to covariance between time series discounts the dynamical nature of the atmosphere and is not sufficiently representative of wind plant operating conditions. Identification and characterization of continuous time periods with atmospheric conditions that have a high value for analysis or simulation sets the stage for more advanced model validation and the development of real-time control and operation strategies. Controlling observational data for statistical stationarity highlights significant enhancements to the power production of waked turbines under wake steering wind plant control. Considering the combined energy ratio of the turbine to which yaw offsets are prescribed as well as the waked turbine show only moderate improvements when filtering for total validation. The same quality control that highlights wake steering also serves to underpin the off-nominal operation of the controlled turbine.

17 WIND ENERGY↗

Cleaning the grid

Wind and solar power plants emit no air pollution while operating, but how effectively do they lower overall emissions from the electric grid? New research traces wind and solar impacts through the grid, even across regional boundaries.

14 SOLAR ENERGY↗

Least-Cost Pathways for India's Electric Power Sector

The Government of India has a target of deploying 175 GW from renewable energy by 2022 and 40% of electricity capacity from renewable energy by 2030 and has indicated that ambitions for 2030 could be higher. Rapid changes in technology costs and performance could drive further deployment of wind and solar capacity beyond these policy targets. Increased deployment of variable renewable energy (VRE) raises new questions for power system planning regarding the optimal siting of generation capacity, trade-offs between generation and transmission infrastructure, and system flexibility needs. This study aims to evaluate least-cost pathways for India's electric power system over the period 2017-2047. Uniquely, this work considers an expanded planning horizon and range of scenarios not previously analyzed in national planning studies in India. The data collection and model design processes undertaken for this study provides a framework for recurring planning studies. This study finds anticipated changes in electricity demand and component costs can drive a significant shift in India's future electricity supply and how this system will be operated. In the Base scenario, the share of generation from VRE reaches 54% by 2047. Reducing the capital cost of wind has a larger impact on VRE penetration than reducing the capital cost of solar PV or battery storage. In the lowest wind cost scenario (40% capital cost decline by 2047 relative to the Base scenario), the penetration of VRE in the generation mix reaches 722%, exceeding the penetration levels achieved when the cost of battery storage or solar PV are reduced by an even greater 50%. In a future system with high penetrations of RE, capacity additions are driven by the coincidence of demand and RE generation rather than peak demand alone. This study finds the system could have surplus capacity during the peak demand months of July–September because this period corresponds to periods with high wind speeds and more wind generation available to meet peak demand. By contrast, new capacity is needed to meet demand during moderate demand months of October–November when output from wind plants falls more than 75% nationally compared to the previous two months. Finally, the success for gas for electricity production may depend on cost competitiveness rather than fuel availability. Increasing the amount of gas available for electricity production had no significant impact on the capacity or generation mix by 2047, as determined from a scenario that significantly increases fuel availability throughout the planning horizon. In fact, over 80% of new gas fuel available for the power sector remains unused. This suggests the high cost of gas plant operations relative to other technologies may constrain the expansion of gas generation in India more than fuel availability.

14 SOLAR ENERGY↗

Graph network heterogeneity predicts interplant wake losses

Wind plants generate large-scale wakes, which can affect the performance of neighboring installations. Such wakes are challenging to estimate due to the inherent complexity in modeling wake interactions between large quantities of turbines at various distances. Weighted directed graph networks can inform complex models by linking turbine pairs into chains of upstream and downstream neighbors for a given wind direction. A novel interpretation of the graph network adjacency matrix is proposed where each element of the matrix represents the cumulative impact of upstream turbines on an individual. In this study, wake losses were estimated with an engineering wake model across a range of inflow conditions for nine parametric variations of a system containing two neighboring wind plants. The parametric nature of the study isolates turbine spacing within the plant, separation distance between plants, and wind direction as the main drivers of wake losses. Spatial heterogeneity is computed from the weighted average adjacency matrix of each plant arrangement. The proposed method is orders of magnitude faster than wake modeling and does not require detailed turbine information or atmospheric conditions. Furthermore, the weighted average adjacency matrix provides insight on the spatial organization of wake losses at various scales. Plant heterogeneity is correlated with wake losses within and among plants. Framing wind plant wake interaction in terms of graph network spatial heterogeneity provides an efficient approach for predicting wake losses within and among neighboring wind plants with applications to other complex systems where wake interactions are key factor.

17 WIND ENERGY↗

Dynamic Wind Loading on CSP Collectors Caused by Turbulent Wind Fluctuations: Insights from a 2-Year Field Campaign

Concentrating Solar Power (CSP) is a promising solar technology for electricity generation with thermal energy storage and with the additional benefit of industrial heat production. Wind loading on CSP collector structures, such as parabolic troughs or heliostats, is one of the primary drivers of their structural design costs. In particular, dynamic wind loading is a major source of uncertainty in the collector design process, which heavily relies on wind tunnel testing. In the field, the turbulent nature of the incoming wind creates fluctuating loads (support structure loads and resulting mirror deflections) on the collectors, with impacts on fatigue lifetime and optical performance. As is well known, wind tunnel tests cannot entirely reproduce the complex turbulent wind conditions typically observed at full-scale plants. To shed light on this topic, NREL initiated a field campaign at the operational Nevada Solar One (NSO) powerplant that uses parabolic troughs as solar collectors. The aim of the project is a detailed characterization of prevailing wind and turbulence conditions and resulting operational loads on parabolic troughs. We use the published 2-year dataset of high-resolution combined wind and structural loads measurements [1] to characterize the dynamic structural wind response. For quantifying dynamic wind loading, we apply the concept of admittance functions, which are spectral transfer functions that couple the turbulent wind to resulting structural loads (aerodynamic admittance), and to the structural response (mechanical admittance). In practice, aerodynamic admittance describes which turbulent eddy sizes are effective in creating structural loads. The mechanical admittance describes in which frequency ranges these loads are reinforced or dampened by the structure. While these functions are an established concept in civil engineering, their recent application to a single full-scale heliostat [2] proved their broader applicability to CSP collectors. Here, we present a characterization of admittance functions for full-scale parabolic trough collectors and show how wind characteristics (mean wind speed and direction, turbulent kinetic energy, turbulent length scales), the sun-tracking trough angle, and row position alter the admittance functions. Further, we study to which extent the admittance functions are universal for a specific trough geometry and how our findings compare to reported heliostat results. References [1] https://data.openei.org/submissions/5938. [2] Blume, K., Roger, M., and Pitz-Paal, R. 2023b. "Simplified analytical model to describe wind loads and wind-induced tracking deviations of heliostats." Solar Energy, 256, 96-109. https://doi.org/10.1016/j.solener.2023.03.055.

admittance functions↗

Grid and Wind Transient Ride Through Assessment of Type-5 Synchronous Wind Turbine

The integration of the inverter-based renewable energy resources is increasing and replacing conventional synchronous generators in the evolving bulk power system (BPS), impacting the system inertia along the way. Also, the limited over-current capability of power electronic converters continues to deteriorate the grid strength of the evolving power systems. Type-5 wind turbines have the potential to mitigate these problems because this configuration interfaces with the grid through a synchronous generator; hence, its operation and consequent grid impacts might mimic the conventional synchronous generator. The drivetrain of this type of turbines, however, is different from the more common Type-3 and Type-4 turbines. A hydraulic torque converter and gearbox with torque limiting feature are integral parts of a Type-5 wind turbine drivetrain, to isolate the wind speed variations at the wind turbine rotor from the grid connected generator side. This supports the synchronous operation of the generator. However, high fidelity models of Type-5 wind turbine drivetrain including these core components are not openly and widely available for grid integration and transient stability studies. Moreover, Type-5 turbines are not commonly deployed and hence its power generation and frequency stability characteristics are not widely publicized. This hinders appropriate assessment of Type-5 wind power plant's contribution to bulk grid resilience. This work provides transient stability assessment of a standalone Type-5 wind turbine. Normal operation and grid transient studies are performed to see the step load change and wind speed disturbance impacts on the Type-5 drivetrain and generation dispatch. Preliminary results show that Type-5 wind turbines can support load changes of between 0.6 p.u to 1.15 p.u. Beyond this point, the synchronization of the generator starts to deviate from its set point.

17 - WIND ENERGY↗

Use of Systems Engineering in Repurposing Coal-Fired Power Plants with Malta Pumped Thermal Energy Storage System

he electric sector across North America is facing a transition. Both economics and policy decisions have pointed towards a broad retirement of fossil assets across markets. Owners are facing the problem of how to evolve the base of the electric sector from fossil asset to greener alternative. Coal-fired power plants built the modern electricity grid. Their rotating machinery are the beating heart of the grid, providing essential resiliency and reliability services. Power plant retirements are disruptive to plant workforces and cause outsized impacts on surrounding communities. The transition from thermal power plants that use rotating machinery to generate electricity (e.g., coal- and gas-fired plants) to variable, inverter-based generation (e.g., solar and wind) is affecting the reliability of the electric grid. Grid operators and national regulators have issued warnings about known and anticipated risk. In 2021, Malta Inc. was awarded a Department of Energy (DOE) grant to study how to integrate a Malta 100MW Pumped Heat Energy Storage (PHES) system with a retiring coal-fired power plant to meet emissions requirements, retain plant workforces, preserve communities, and maintain grid reliability. This presentation provides a summary of this study, focusing on how systems engineering approach was used to arrive at a proposed design concept that met multiple objectives and requirements. There will be three main parts for this presentation. The first part of the presentation will focus on how different systems engineering was applied for this work. In particular, the following areas: stakeholder engagement, site selection process, developing requirements and use cases for the integrated system, defining the system and its boundary, coming up with different system architecture/option, performing a techno-economic analysis to compare the different options and down selection of the preferred option, will be discusses. For these areas, discussion on the decisions on how much breadth and depth to go into each area will be provided. These discussions provide good insights into how to apply systems engineering. The second part of the presentation will provide a deeper dive into the two recommended integration options that repurpose coal-fired power plants with Malta PHES system. The comparison of the two options and general guidance of how to choose an option will be provided. This is particularly useful for utilities who are facing coal-plant retirements. The two options will be compared based on its performance (such as power output, efficiency), complexity, and cost. The social impact on local communities of the two options will also be discussed. The final part of the presentation will discuss the impact that this work has had, including Malta Inc. being invited to the White House to discuss progress and outcomes of this work with the Interagency Working Group on Coal and Power Plant Communities and Economic Revitalization. In summary, this presentation aims to provide a showcase of how sy

25 ENERGY STORAGE↗

Estimation Methodology to Evaluate Hypothetical Downwind Impacts from Fusion Plants

The continuing move toward establishing fusion systems for power generation and the associated research to that end is prompting examination of the potential health and safety impacts of such plants to the environment and human health. As many fusion facilities will have tritium inventories on site as part of the fusion fuel, evaluating the potential for downwind impacts from fusion facilities or power plants resulting from accident or routine emissions is a general requirement for assessing location and impacts to workers and the public. As part of siting considerations and permitting, the fusion facilities would be evaluated for potential for downwind concentration and dose impacts. For accident assessment scenarios, the downwind impacts are usually modeled as an instantaneous (or near-instantaneous) release of material transported following the wind. A range of meteorological conditions are usually assessed to determine a bounding case which results in a dose exceeding a specified threshold (e.g., 95 th or 99 th percentile; DOE 2015). This report provides initial estimates of the downwind dose impacts from a potential tritium release at a fusion power plant-relevant facility and identifies potential distances required to limit impacts to nearby population. This effort is meant to provide a bounding analysis and theoretical understanding of impacts of tritium releases for facilities subject to various environmental and atmospheric conditions. Using a Gaussian dispersion model to simulate a brief plume, downwind concentration and dose is projected for tritium oxide. Releases are assumed to consist entirely of tritium oxide due to the increased dose impacts from the oxide form relative to the elemental form of tritium. We also briefly identify how climatological conditions could potentially be used to support risk profile determination.

54 ENVIRONMENTAL SCIENCES↗

Streamlining Energy Sprawl: Assessment of Geothermal Impacts on Public Lands

Renewable energy power generation, including geothermal, solar photovoltaics (PV), and wind, can have significant land use impacts depending on the technology and the size of the facility. At the same time, innovations across these renewable technologies are working to improve plant efficiency per acre of disturbance. Through a survey of satellite imagery and other sources, this analysis reevaluates the impact of geothermal power generation and examines the variations in land use for different geothermal technologies (binary, flash, and dry steam). Geothermal operations on Bureau of Land Management (BLM) sites serve as the focus for this analysis - i.e., only active sites with federal mineral ownership for which the BLM receives royalties from power production. The results show significant variation in direct land disturbance across the operations sites and across these three geothermal technologies. Although there is variation across plants within the same geothermal technology category, dry steam plants (The Geysers) were shown to have the lowest impact, in acres per megawatt capacity and acres per gigawatt-hour generation, followed by flash steam and binary plants. Overall, direct land impacts relative to capacity and generation have declined 16-27% for facilities constructed since 2000 as compared to those constructed prior, even though most new facilities are binary plants (which traditionally had higher land disturbance). Additionally, capacity factors based on actual net production data were found to average only 50% across all operations sites, suggesting that previous estimates based on nameplate capacity only may lead to an undercounting of generation-based land disturbance metrics. Should the geothermal industry capture additional market share, improving land disturbance metrics through accurate net production and capacity data and further minimizing impacts will be increasingly important as competition over land use intensifies.

GEOTHERMAL ENERGY↗

Mountain waves can impact wind power generation

Abstract. Mountains can modify the weather downstream of the terrain. In particular, when stably stratified air ascends a mountain barrier, buoyancy perturbations develop. These perturbations can trigger mountain waves downstream of the mountains that can reach deep into the atmospheric boundary layer where wind turbines operate. Several such cases of mountain waves occurred during the Second Wind Forecast Improvement Project (WFIP2) in the Columbia River basin in the lee of the Cascade Range bounding the states of Washington and Oregon in the Pacific Northwest of the United States. Signals from the mountain waves appear in boundary layer sodar and lidar observations as well as in nacelle wind speeds and power observations from wind plants. Weather Research and Forecasting (WRF) model simulations also produce mountain waves and are compared to satellite, lidar, and sodar observations. Simulated mountain wave wavelengths and wave propagation speeds (group velocities) are analyzed using the fast Fourier transform. We found that not all mountain waves exhibit the same speed and conclude that the speed of propagation, magnitudes of wind speeds, or wavelengths are important parameters for forecasters to recognize the risk for mountain waves and associated large drops or surges in power. When analyzing wind farm power output and nacelle wind speeds, we found that even small oscillations in wind speed caused by mountain waves can induce oscillations between full-rated power of a wind farm and half of the power output, depending on the position of the mountain wave's crests and troughs. For the wind plant analyzed in this paper, mountain-wave-induced fluctuations translate to approximately 11 % of the total wind farm output being influenced by mountain waves. Oscillations in measured wind speeds agree well with WRF simulations in timing and magnitude. We conclude that mountain waves can impact wind turbine and wind farm power output and, therefore, should be considered in complex terrain when designing, building, and forecasting for wind farms.

17 WIND ENERGY↗

Fish Friendly Water Rules' Impact On the Power Grid with High VRE Levels

Columbia River basin multipurpose reservoirs are operated for hydropower production and many other purposes considering the aquatic habitat of the river basin. Specifically, the river basin fish population is a vital element for the tribal community of the river basin. When conventional thermal power plants are retired, hydropower flexibility balances the wind and solar variability of the power grid and provides grid services to maximize the high renewable power absorption. On the other hand, over-reliance on hydropower could harm the river basin fish habitat. For example, water release pulses during peak electricity demand hours and shorter-term water release variation could harm the fish population. Power grid planners, environmentalists, Columbia Basin tribes, hydro regulators, and water resource planners work together to understand the impacts of Columbia River basin operation in a fish-friendly way in the current power grid and power grid with higher renewable power share. We examine different levels of renewable share in the Western Interconnection to understand the multiple weather years and future climate projection and operating scenario impact on the power grid and water system. We measure power grid impacts for various water resources planning scenarios in terms of total system operating cost, system reliability indicators, changes in wind and solar generation and curtailments, local marginal prices, and revenue for hydropower producers. The study results inform reservoir operating rules decisions from hydropower power producers, system operators, other water users, tribes, environmentalists, and other stakeholders.

environmental↗

Dynamic Interaction of Grid-Forming and Grid-Following Inverters with Synchronous Generators in Hybrid Power Plants

As the integration of renewable energy resources such as wind and solar generation continues to grow, the use of hybrid power plants with both synchronous machines and power electronic inverters operating in parallel becomes more common. This paper studies the impact on small-signal stability for these pairs of devices, first as an isolated two-device system and then as part of a 9-bus test system. Each operational scenario was studied with both a grid-following inverter and a grid-forming inverter. In each scenario, the state variables associated with the synchronous generator's excitation system were found to be responsible for the inception of instability. These results underscore the importance of accurate modeling of excitation systems when modeling power systems with hybrid power plants.

hybrid power plant↗