Search NASA⌕ Search

SEARCH · Search NASA

Results for “grid following”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 109 records · Page 6

Leveraging PHIL for Inverter Functionality Requirement Evaluation to Ensure a Reliable Grid

This presentation showcases NREL's ongoing research on advanced Multi-point Power Hardware-in-the-Loop (PHIL) systems, enabling comprehensive evaluation of interoperability, stability, and wide-area stability in complex power grids. Key features include high-power PHIL capabilities, seamless PHIL Interfaces for effortless Grid-Following (GFL) and Grid-Forming (GFM) mode switching, and advanced multi-domain PHIL/Controller Hardware-in-the-Loop (CHIL) capabilities for evaluating diverse technology mixes, facilitating rigorous testing and validation of emerging power systems for reliable integration, enhanced resilience, and optimal performance.

lab capabilities↗

Sequence Impedance Modeling of Grid-Forming Inverters

Grid-forming control of inverter-based resources has been identified as a critical technology for operating power systems with high levels of inverter-based resources. This paper presents the sequence impedance modeling of a grid-forming inverter to evaluate its small-signal stability properties. Droop control structure is implemented to control the inverter in grid-forming mode, and the impact of individual controller on the inverter impedance characteristics is discussed. The developed sequence impedance model is compared with that of the grid-following inverter. It is found from the developed sequence impedance models that grid-forming inverters are less prone to harmonic resonance problems during operation with weaker grids. The developed models are validated using PSCAD simulations.

grid- following inverter↗

Sequence Impedance Modeling of Grid-Forming Converters: Preprint

Grid-forming control of inverter-based resources (IBRs) has been identified as a critical technology for operating power systems with high levels of inverter-based resources. This paper presents sequence impedance modeling of grid-forming inverters to evaluate its small-signal stability properties. Droop based grid-forming control with full consideration of the multiloop structure is studied, and the impact of individual controller on the inverter impedance characteristics is discussed. The developed sequence impedance model is compared with that of the grid-following inverter. It is found from the developed sequence impedance models that grid-forming inverters are less prone to harmonic resonance problems during operation with weaker grids. The developed models are validated using PSCAD simulations.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Sequence Impedance Modeling of Grid-Forming Inverters

Grid-forming control of inverter-based resources has been identified as a critical technology for operating power systems with high levels of inverter-based resources. This paper presents the sequence impedance modeling of a grid-forming inverter to evaluate its small-signal stability properties. Droop control structure is implemented to control the inverter in grid-forming mode, and the impact of individual controller on the inverter impedance characteristics is discussed. The developed sequence impedance model is compared with that of the grid-following inverter. It is found from the developed sequence impedance models that grid-forming inverters are less prone to harmonic resonance problems during operation with weaker grids. The developed models are validated using PSCAD simulations.

grid-following inverter↗

Small-Signal Stability Analysis of Low-Inertia Power Grids with Inverter-Based Resources and Synchronous Condensers: Preprint

With the potential environmental impacts of conventional fossil fuels and the technology advances of grid interactive power electronics, inverter-based resources (IBRs) are playing a crucial role in modern power grids. However, due to the lack of physical inertia, IBRs are vulnerable to system disturbances. Further, conventional grid-following (GFL) inverters cannot actively establish the frequency and voltage, which could not be a appropriate solution for 100% inverter-based power grids. Grid-forming (GFM) control, as an emerging inverter control function, has drawn great attention in recent years, while it is still under development and pre-mature for large-scale field deployment. A potential solution for gradually transitioning into a 100% inverter-based power grid is to combine both IBRs and synchronous machines into a mixed generation portfolio. More importantly, synchronous machines can be operated as synchronous condensers (SCs) until they are retired. It is also worth mentioning that the stability analysis is of great importance to ensure the smooth transition from existing power grids to 100% inverter-based system, which is the main focus of this work with detailed modeling and modal analysis.

100% renewable↗

Grid Forming and Following Background, Future, and Strategies

The landscape of the U.S. power structure with respect to microgrid configuration strategies that utilize grid forming and grid following converters is becoming relevant. Inverter based control and coordination strategies are every changing due to critical failures and limitations. Understanding current state of grid forming and following converter technology and their normal operational guidelines will lead into the next stage of future research. Grid forming and following converter control strategies and ratio of assets review two case studies to develop an understanding of the current landscape.

29 - ENERGY PLANNING, POLICY AND ECONOMY↗

Evaluation of Optimal Net Load Management in Microgrids Using Hardware-in-the-Loop Simulation: Preprint

This paper presents the performance evaluation of a net load management (NLM) engine that balances load and generation in an isolated community to power a critical facility after a grid interruption event (e.g., lost a large generation unit). The NLM engine is a central dispatch control system that provides high-speed cost-optimal coordination of a set of net loads (combination of generation and deferrable loads) connected to the same electrical network. The NLM algorithm cost-optimally dispatches the grid-following inverters and deferrable loads based on the demanded power and load priorities, and the grid-forming inverters use droop control to form system voltages and share active and reactive power. A controller-hardware-in-the-loop platform is developed to evaluate the control performance of the NLM algorithm. The experimental results indicate that the NLM engine can achieve the targeted system voltage and frequency and balance load and generation to serve the critical facility.

droop control↗

Power Hardware-in-the-Loop Interfaces for Inverter-Based Microgrid Experiments Including Transitions: Preprint

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop (HIL) simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such microgrid interfaces are particularly challenging to model when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents two PHIL interfaces for such microgrids and the preliminary experimental results: One interface is suitable for those who have access to a power amplifier that can operate as a controllable current source, and the other is for those who need a solution that uses a voltage-mode power amplifier.

battery energy storage system↗

Testing GFM and GFL Inverters Operating With Synchronous Condensers

Inverter-based resources (IBRs) are quickly evolving into a source of reliability services to the electric grid. Penetration levels of variable generation are rapidly increasing, ranging from 60% -70% in some systems. To go further, a fundamental shift is required to address challenges associated with grid stability. Synchronous condensers (SCs) are considered an important complementary technology in such transitions. This paper provides one-of-a-kind insights into real experimental results from operating a real MW-scale system consisting of a 2.2-MVA grid-forming (GFM) and grid-following (GFL) battery energy storage system, 2.5-MVA SCs, and a 3-MVA load bank operating as a small, islanded grid. Challenges that are expected in larger systems were mimicked in this small but real system to demonstrate seamless transitions from one mode to another as well as stable operation with different combinations of GFM and GFM resources, including a "loss of last synchronous generator" case. The experimental results presented in this paper are a valuable resource to everyone involved in developing and validating models or developing controls of power systems consisting of inverters and synchronous condensers.

grid-following converter↗

Autonomous Inverter Controls for Resilient and Secure Grid Operation: Vector Control Design for Grid Forming

The project addresses both fundamental and practical challenges of GFM/GFL inverter control for the power grids with high inverter based resources (IBRs) penetration. A data- driven modeling technique is applied to accurately model dynamics of PWM inverters, including electromagnetic-transient (EMT). Systematic and integrative designs of grid- forming (GFM) and grid-following (GFL) primary controls are developed to guarantee system performance under either normal or abnormal operating conditions without violating constraints. This modeling and control framework provides black-start capability in case of an outage without relying on rotating generators, and its secondary control is also shown to enhance resilience against cyber-physical attacks.

14 SOLAR ENERGY↗

Small-Signal Stability Constrained Optimal Power Flow of Inverter-Dominated Power Systems with Flexible Operation Mode Selection

Given the intermittence and low inertia nature of inverter-based resources (IBRs), modern power systems with high penetration of IBRs challenge the conventional optimal power flow (OPF) analysis and the system may experience unexpected failures if stability constraints are not incorporated. This study proposes a small-signal stability-constrained OPF (SSSC-OPF) with flexible operation mode selection between grid-forming (GFM) and grid-following (GFL) modes for IBRs to address these challenges. The approach aims to maintain system stability with a sufficient stability margin while minimizing operation costs. The effectiveness of the proposed method is validated through extensive case studies on the IEEE 14-bus system. The results demonstrate that the proposed method is able to support system-level power flow analysis, reduce generation costs, and ensure stability under various disturbances.

grid-following↗

Quantitative Small-Signal Stability Analysis of Grid-Forming Inverters in Large-Scale Power Systems

In this paper, the challenges induced by the integration of inverter-based resources (IBRs) into existing power systems are discussed. Although the grid-forming (GFM) control has been used to enhance system performance in multiple sections of electric power systems (e.g., transmission and distribution systems, microgrids, among others), the coupling mechanism between GFM inverter and various types of other components in modern power systems should be clearly explored. Existing analyses mainly focus on qualitative investigations that verify the effectiveness of deploying GFM inverters for stability enhancement. A holistic system-level quantitative analysis is still missing to verify the detailed benefits of GFM inverters and their interactions with other generation units (e.g., synchronous generators [SGs], conventional grid-following [GFL] inverters, synchronous condensers, among others). To fill in the technical gaps, a holistic small-signal model of the entire system with both rotating generation units and IBRs is established along with the customized power flow analysis for varying steady-state operating points. Further, a quantitative method is proposed to identify the impacts of GFM inverters on system performance with an emphasis on a quantifiable stability margin and a complete modal analysis at the system level. Finally, a realistic test system is used to verify the proposed approach.

grid-following↗

Impedance Scan of Inverter-Based Resources and Diesel Generator for Stability Analysis: Preprint

Impedance-based methods are widely used for power system stability analysis with inverter-based resources (IBRs), e.g., assessing dynamic interactions between the power grid and an IBR, control interactions between multiple IBRs, and the sub-synchronous oscillation and damping phenomenon. Since it is difficult to get a numerical model 100% matching with the hardware IBR, using the hardware inverter directly to obtain its output impedance has become a prominent approach nowadays. Therefore, this article presents the impedance scan using hardware IBRs, and also a hardware diesel generator as it still stays with the grid before the grid completely goes to renewable. The devices under test (DuTs) for the impedance scan includes two 3-..phi.., 480 V, 60 Hz commercial grid-forming IBRs (one of 250 kVA and another of 125 kVA rating) in series with ..delta..-Y transformers, one 3-..phi.., 480 V, 60 Hz commercial grid-following IBR (of 125 kVA rating), and a 3-..phi.., 480 V, 60 Hz commercial diesel generator (of 187.5 kVA rating). Using voltage signals perturbed with sub-, inter-, and higher harmonic components, and measuring the current response, the positive-sequence impedances are computed via an offline- based post-analysis. Moreover, best-fit transfer functions are estimated that closely resemble the measured data points of the positive-sequence impedances. Based on the observations from various outcomes of the hardware experiments, this article also provides some fundamental insights on the equivalent positive- sequence impedance of a combination of multiple hardware components by comparing the estimated and the empirically computed impedances. A comparative insight on the damping capability of the DuTs using the positive-sequence impedances of the hardware is also discussed.

grid following inverter↗

Dynamic Validation of CNN-Based Surrogate Models for Inverter-Based Resources in Open-Source Solvers

Traditionally, distribution system planning has focused on steady-state analyses, with limited consideration of dynamic behavior. However, as large or medium-scale inverter-based resources (IBRs), particularly grid-following (GFL) inverters in commercial or industry buildings, become more prevalent, understanding their dynamic impact is essential for grid planning and operation. This article presents an innovative deep-learning (DL)-approach using convolutional neural networks technique to model the GFL inverters. Developed from real grid-tied commercial IBR transient data, these dynamic DL models overcome proprietary constraints by requiring minimal knowledge of internal converter physics while maintaining high accuracy and flexibility. To demonstrate their applicability, the models were incorporated into GridLAB-D, an open-source, three-phase distribution analysis tool. This integration enables dynamic simulations of large-scale distribution networks with high IBR penetration stability analysis. Rigorous testing and validation, aligned with industry standards, confirmed the reliability and efficiency of this approach, paving the way for enhanced planning and operational assessments of modern power systems.

Deep-learning↗

Small-Signal Stability Support from Dynamically Configurable Grid-Forming/Following Inverters for Distribution Systems

The growth of inverter-based resources (IBRs) in modern power systems can challenge system stability since they do not natively provide inertia, prompting a need to develop new methods to address the potential instabilities. In this paper, a dynamically configurable grid-forming (GFM) and grid-following (GFL) control is proposed, which enables inverters to flexibly transition to support system needs. The operation mode transition between GFM and GFL controls is adopted as an additional degree of control flexibility to adjust the small-signal stability margin. In addition, a holistic and detailed small-signal model for a distribution feeder that captures the dynamics from both synchronous generators (SGs) and IBRs is also derived and used to evaluate the effectiveness of the proposed GFM/GFL controls to augment the system small-signal stability margin. Case studies with varying levels of IBRs were implemented in MATLAB/Simulink to demonstrate the effectiveness of the proposed approach.

grid-following control↗

Transient Stability Study of a Real-World Microgrid with 100% Renewables

This paper performs a transient stability study of a real-world microgrid that can operate with 100% renewables to better understand the stability and reliability of the microgrid under various dynamic scenarios. In particular, the operation of multiple grid-forming (GFM) and grid-following (GFL) inverters in such a power system is not well understood under dynamic operation conditions, such as islanding and black start; therefore, in this paper, an electromagnetic transient model of the microgrid is developed to investigate the stability of the system under various dynamic operating conditions and to identify potential reliability risks. The PSCAD/EMTDC simulation with the high-fidelity model provides helpful insights into the optimal operation modes of GFM and GFL inverters as well as the stability and reliability of the microgrid. It can also inform field deployment in terms of inverter control parameters and coordination as well as the expected performance of black start and unplanned islanding.

black start↗

Transient Stability Study of a Real-World Microgrid with 100% Renewables

This paper performs a transient stability study of a real-world microgrid that can operate with 100% renewables to better understand the stability and reliability of the microgrid under various dynamic scenarios. In particular, the operation of multiple grid-forming (GFM) and grid-following (GFL) inverters in such a power system is not well understood under dynamic operation conditions, such as islanding and black start; therefore, in this paper, an electromagnetic transient model of the microgrid is developed to investigate the stability of the system under various dynamic operating conditions and to identify potential reliability risks. The PSCAD/EMTDC simulation with the high-fidelity model provides helpful insights into the optimal operation modes of GFM and GFL inverters as well as the stability and reliability of the microgrid. It can also inform field deployment in terms of inverter control parameters and coordination as well as the expected performance of black start and unplanned islanding.

black start↗

On the Low Risk of Subsynchronous Resonance (SSR) in Type III Wind Turbines Operating in Grid-Forming Control

We have shown in a previous work that the risk of sub-synchronous resonance (SSR) between a wind power plant with Type III wind turbines and series-compensated transmission lines is low when the wind turbines in the plant are operated in grid-forming mode, instead of the standard grid-following mode. The fundamental mechanism behind the improved damping characteristics is explained in this paper by modeling the positive and negative sequence impedances of Type III wind turbines for GFM operation mode. It is discovered that the GFM control naturally acts against the negative resistance of Type III wind turbines that results from an interaction between the proportional gain of the rotor-side converter current controller and negative slip. The developed sequence impedance models and improved damping behavior are verified using PSCAD simulations of a 2.5-MW Type III GFM wind turbine. The modeling predictions are also supported by experimentally measuring the sequence impedance response of a 2.5-MW Type III wind turbine during operation in GFL and GFM modes.

grid-following turbine↗