Comprehensive Laboratory Evaluation of Multi-Vendor Grid-Forming (GFM) Inverters
This presentation summarizes the UNIFI 1MW multi-vendor grid-forming inverter testing results.
SEARCH · Search NASA
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
This presentation summarizes the UNIFI 1MW multi-vendor grid-forming inverter testing results.
Power Hardware-in-the-Loop (PHIL) simulation of grid-forming (GFM) inverter systems facilitates the testing of drastic scenarios like on-grid to off-grid transition, islanded microgrid operation without stiff grid etc. To the authors best knowledge, most of studies in literature are focused on PHIL simulation for grid-following inverter systems and only few studies are focused on GFM inverters and those are challenging and problematic especially for high-power applications. In this article, a novel PHIL simulation platform is proposed that enables interfacing of high-power GFM inverter systems. It proposes the concept of a virtual GFM inverter as a part of the proposed PHIL interface for GFM inverter. This addition of virtual GFM inverter in the PHIL interface expands the conventional Ideal Transformer Model (ITM) method and enables it to overcome the issues of instability of existing ITM methods. In the validation stage, a PHIL experiment is conducted on a 3-phase 480 V, 125 kVA GFM inverter system with proposed interfacing method. The results corroborates the fact that the proposed PHIL simulation method performs well and stable for GFM inverter system.
Here, this paper describes a positive-sequence model to represent two widely reported droop-controlled grid-forming inverters for bulk power systems simulation study. Methods of how to develop the equivalent voltage source behind impedance to represent inverters with and without inner control loops, modeling of P-f and Q-V droop controls, active and reactive power limiting modeling, and modeling of fault current limiting controls are described in detail. The model is implemented in commercially available positive-sequence simulation tools and compared with detailed electromagnetic transient models in both a single-grid-forming-inverter infinite-bus system and a modified IEEE 39-bus system. Finally, the model is tested on the full US Western Electricity Coordinating Council (WECC) system. Study results show that the model has a good level of accuracy compared to the detailed EMT models, and at the same time also achieves a high computational efficiency, which is suitable for the bulk power system simulation study.
This paper develops a non-phase-locked loop (PLL) grid-connected inverter that can improve the microgrid’s transients during transition operation. By emulating the operation of a synchronous machine, the inverter generates its own voltage and frequency during startup, synchronizes and connects to the grid, then operates in reactive power mode (grid-feeding) with self-generated voltage and frequency, and switches to voltage-frequency mode to establish system voltage and frequency (grid-forming) when the microgrid disconnects from the main grid, and vice versa. To enable fast synchronization, active synchronization control is adopted both during inverter startup and microgrid reconnection operation. The simulation results show that the developed non-PLL grid-connected inverter works effectively to synchronize the inverter and microgrid to the grid and avoids a phase jump during microgrid transition operation. Thus, the microgrid’s transients are significantly improved with the proposed control technique.
Grid-forming inverters (GFMs) based on active power-frequency droop control and reactive power-voltage droop control have been developed in recent years, which can generate voltage and frequency references for islanded power systems or microgrids to improve system-wide synchronization and power-sharing capability. It is known that the control delays in GFMs may cause system harmonic instability. To eliminate this issue, virtual impedance techniques are normally adopted. This paper gives a comprehensive examination of the impacts of virtual impedance control block Z v in GFMs on system stability. It is revealed that although Z v is effective in eliminating system harmonic stability, it may ruin system synchronization stability as a side effect. To compensate for the negative impacts caused by Z v , an active power-angle control block is added into the conventional droop control. Design criteria are also proposed accordingly to ensure system stability over the entire frequency range. Simulations and experimental testing are conducted to validate the analysis and the proposed design guidelines. It can be concluded that the Z v control-caused grid-synchronization instability issues can be eliminated with an appropriate active power-angle droop design.
This talk will cover the cyber threat landscape and engineering mitigations for grid forming (GFM) inverters. It will discuss the penetration of inverter-based resources (IBRs) in the United States and expected growth. It will then discuss the threat landscape for IBRs based on current and expected penetration. Real-world examples of cyber incidents affecting IBRs will be presented, concluding with an introduction to Cyber-Informed Engineering (CIE) and a guide on applying it to GFM inverters.
Unlike synchronous generators, the fault response of grid-forming (GFM) inverter-interfaced distributed generators (IIDGs) is notably governed by the selection of control and current limiting strategies rather than inherent physical traits. While recent research has focused on the sequence domain fault model of GFM IIDGs, a research gap exists in elucidating the influence of control and current limiting schemes on this model's characteristics. This article aims to fill this void by examining how different control and current limiting schemes influence the positive and negative sequence impedances in the phasor-domain fault model of GFM IIDGs. This investigation encompasses droop-based, virtual synchronous machine-based, and virtual oscillator-based reference generation controls alongside rotating and stationary reference-frame-based voltage controls. Furthermore, saturation-based, latching-based, circular and virtual impedance-based current limiting schemes are analyzed. To achieve this goal, a thorough numerical simulation study is conducted. Findings indicate that outer reference generation controls exhibit minimal impact. Conversely, the choice of voltage control and various current limiting schemes emerge as the predominant factors shaping the sequence models of GFM IIDGs. These analyses and results are instrumental in devising reliable protection strategies within inverter-based grids, as a comprehensive understanding of electrical elements in the sequence domain is imperative for effective protective measures.
Threshold virtual impedance (TVI)-based current limiting for grid-forming converters (GFMs) has gained great interest due to its ability to maintain voltage source behaviour during faults. However, sequence component extraction (SCE) and negative-sequence control (NSC) are often overlooked in small-signal stability assessments during faults. This paper develops small-signal sequence impedance models for GFMs under four well-known SCE methods based on TVI current limiting control during symmetrical fault conditions. Using the developed impedance models, the impacts of SCE and NSC, and the voltage and current control loop bandwidths, on system stability during faults are investigated. Additionally, since negative-sequence TVI (TVI-) is typically added along with its positive-sequence counterpart, which is often inductive, inductive and resistive TVI- are examined. The findings suggest that a higher voltage or current control loop bandwidth has a negative impact on system stability, while SCE and NSC largely reduce the stable range for voltage and current control loop bandwidth during faults, and that the severity of such impacts is determined by the particular SCE method. Furthermore, it is observed that inductive TVI- significantly degrades system stability, while resistive TVI- can enhance stability when suitable SCE methods are appropriately selected and designed. Matlab/Simulink electromagnetic transient simulations validate these analytical results.
This paper investigates operational techniques to achieve seamless (smooth) microgrid (MG) transitions by dispatching a grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control modes during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worth exploring how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. The results show that the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires that the GFM inverter(s) maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.
This paper investigates operational techniques to achieve seamless (smooth) microgrid (MG) transitions by dispatching a grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control modes during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worth exploring how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. The results show that the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires that the GFM inverter(s) maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.
This paper investigates operational techniques to achieve smooth microgrid (MG) transitions by dispatching the grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control mode during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worthy to explore how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. As expected, the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires the GFM inverter(s) to maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.
Presently, excluding residential backup power applications, grid-forming (GFM) inverters are commercially available for battery energy storage system (BESS) and some PV plus battery systems but not yet for stand-alone PV. This tech update investigates the control design for GFM PV inverter, especially the control required to provide active power reserve and to stabilize the dc link voltage. Subsequently, the use cases of GFM PV plants in utility-level microgrids are discussed considering fully inverter-based microgrids (i.e., with PV and BESS) as well as mixed-source microgrids (i.e., with PV and diesel generator). Scenarios where active power up-reserve from GFM PV plants is beneficial are illustrated. Moreover, requirements and specifications for GFM PV plant, especially for its active power reserve function are developed. In addition, stability of an example utility-level microgrid with two GFM PV plants and a diesel generator is analyzed to shed light on the potential unstable interaction between multiple GFM resources and the countermeasures. This research aims to advance GFM PV technology to offer more flexibility in microgrid design. With GFM PV available, depending on the level of reliability required, cost-benefit analysis, etc., the GFM BESS or diesel generator may be sized smaller while leveraging the full potential of PV generation inside the microgrid.
The growth of inverter-based resources (IBRs) in modern power systems can challenge system stability since they do not natively provide inertia, prompting a need to develop new methods to address the potential instabilities. In this paper, a dynamically configurable grid-forming (GFM) and grid-following (GFL) control is proposed, which enables inverters to flexibly transition to support system needs. The operation mode transition between GFM and GFL controls is adopted as an additional degree of control flexibility to adjust the small-signal stability margin. In addition, a holistic and detailed small-signal model for a distribution feeder that captures the dynamics from both synchronous generators (SGs) and IBRs is also derived and used to evaluate the effectiveness of the proposed GFM/GFL controls to augment the system small-signal stability margin. Case studies with varying levels of IBRs were implemented in MATLAB/Simulink to demonstrate the effectiveness of the proposed approach.
With the rapid increase of inverter-based resources in modern grids, advanced grid-forming (GFM) inverter capa- bilities, such as system restoration and operation under faults, are urgently needed to realize power electronics-dominant grids at scale. One such capability is inverter-driven black start using GFM inverters. This paper analyzes the ability of two recently proposed advanced GFM controls to help GFM inverters sustain system-wide, off-nominal conditions and remain synchronized until they can overcome the momentary overloading as more GFMs join the process without generator sequence coordination or communications and finally stabilize the grid. Through an extensive set of 1,200 full-order electromagnetic transient simu- lations, we evaluate the black-start process while employing the various GFM inverter controls. The results show that the GFM current limiter and primary control have a significant impact on the stability of the system during dynamic operating conditions and thus impact the success of inverter-driven system restoration.
Legacy inverters interfacing distributed energy re-sources are traditionally grid-following (GFL) in nature. GFL assets typically follow real power and reactive power set points. Recently, inverters with grid-forming (GFM) capability are gaining attention as GFM assets can increase the resiliency of the distribution system under stressed conditions. These GFM inverters can use photovoltaics, batteries, or fuel cells as their energy source. In this paper, we present information on inverters interfacing fuel cell assets, specifically with GFM capability. By introducing a fuel cell powered GFM coupled with hydrogen production and storage, the GFM can continuously provide GFM activities during periods of low renewable resource availability, and/or during power outages exceeding typical electric battery duration. Finally, we present information on the need for updates on interconnection and interoperability standards that can be leveraged by utilities for including fuel cell inverters in their asset mix.
This document describes a standard library grid-forming (GFM) hybrid control inverter-based resource (IBR) model. The GFM hybrid control approach implements both a typical GFM control and a typical grid-following (GFL) control inside one single inverter simultaneously, so that it can take advantage of both methods without comprising the benefits of a typical GFM. The initial version of model specification was jointly developed by Pacific Northwest National Laboratory (PNNL), Tesla Energy, and EPRI, and it was revised multiple times later to incorporate suggestions from WECC MVS members. Tesla Energy provided main control blocks to support the development of this model specification. This standard library model is developed to help the utility industry better understand the GFM technology. The model could be used to represent equipment for long-term planning studies where vendor-specific models are not available. As equipment matures and improves, standard library models will be updated to capture the new functionalities of GFMs. It is not intended that these models will always remain representative of all future GFM technologies.
Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such interfaces are particularly challenging when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This presentation shows the use of PHIL interfaces for such microgrids and the preliminary experimental results.
Existing state-of-the-art of single-phase grid-forming (GFM) inverter are primarily focused on electromagnetic transient simulation, and there are very few works performing hardware test, and there is no clear understanding how the single-phase GFM inverter should behave from a hardware perspective. Therefore, this paper addresses the gap by performing hardware experiment to evaluate the performance of a single-phase GFM hardware inverter. We enrich the existing GFM testing protocols by investigating transient performance of GFM inverters under different grid dynamic events, and quantifiable performance metrics are made to have a common understanding of expected performance of single-phase GFM inverters. A commercial single-phase GFM inverter is used to verify the test protocols and understand the inverter's performance and functionalities.