Search NASA⌕ Search

SEARCH · Search NASA

Results for “power system transient stability”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 145 records · Page 8

Large-Signal Stability Improvement of Parallel Grid-Forming Inverter-Driven Black Start: Preprint

With the rapid increase of inverter-based resources in modern grids, advanced grid-forming (GFM) inverter capa- bilities, such as system restoration and operation under faults, are urgently needed to realize power electronics-dominant grids at scale. One such capability is inverter-driven black start using GFM inverters. This paper analyzes the ability of two recently proposed advanced GFM controls to help GFM inverters sustain system-wide, off-nominal conditions and remain synchronized until they can overcome the momentary overloading as more GFMs join the process without generator sequence coordination or communications and finally stabilize the grid. Through an extensive set of 1,200 full-order electromagnetic transient simu- lations, we evaluate the black-start process while employing the various GFM inverter controls. The results show that the GFM current limiter and primary control have a significant impact on the stability of the system during dynamic operating conditions and thus impact the success of inverter-driven system restoration.

current limit↗

Control System of Multi-Port Autonomous Reconfigurable Solar Power Plant (MARS) & HIL Platforms for Design

Multi-port autonomous reconfigurable solar power plant (MARS) provides an attractive alternative to connect photovoltaic (PV) and energy storage systems (ESSs) to high-voltage direct current (HVdc) links and high-voltage alternating current (ac) grids. In this paper, a unique hierarchical control system of MARS is proposed and evaluated. To evaluate the control system and associated algorithms in early-stage research of complex architectures like MARS, it is important to develop unique suitable hardware-in-the-loop (HIL) platforms. In this paper, the HIL platforms for MARS to evaluate the performance of the hierarchical control system and the control algorithms implemented are presented. Further, they help with the design process of control systems. The real-time simulation models and algorithms that are utilized for MARS in the HIL platforms are also discussed in the paper. The HIL experiments of the control system of MARS showcase the capability to provide continuity of operation under faults and frequency support to the power grid during loss of generation. They also showcase the stability of the proposed hierarchical control system of MARS.

14 SOLAR ENERGY↗

Third-body stabilization of supercritical CO 2 in CO oxidation: development and application of a ReaxFF force field for the CO/O/CO 2 system

Supercritical CO 2 (scCO 2 ) plays a crucial role as a solvent in separation processes, advanced power cycles, and materials processing. Nonetheless, the atomistic comprehension of how the dense scCO 2 matrix influences the fundamental reaction of carbon monoxide (CO) is still insufficiently explored. Experimental studies and molecular dynamics (MD) simulations frequently fail to detect the highly reactive, transient intermediates, such as atomic oxygen (O), that drive these reactions. Here, to address this issue, we have developed a novel ReaxFF reactive force field for the CO 2 /CO/O system. The force field parameters were calibrated using density functional theory and second-order Møller-Plesset calculations to model CO 2 crystal properties, intermolecular interactions, bond dissociation curves, and reaction energy barriers. The force field reproduces the cohesive energy of the CO 2 crystal, the pressure characteristics of bulk scCO 2 , the equation-of-state behavior over a wide pressure–density range, the pressure dependence of the C–O bond length under compression, and the structural properties of liquid and scCO 2 , as documented by experiments, ab-initio MD, and prominent non-reactive models. The force field was subsequently applied to study the CO + O → CO 2 reaction. In a dilute environment, the reaction is inefficient as the newly formed CO 2 rapidly dissociates due to excess kinetic and potential energy acquired from the exothermic reaction. Conversely, in a dense scCO 2 environment, the surrounding matrix acts as an efficient third body, stabilizing the emerging CO2 product via molecular collisions. Statistical analysis confirms an average excess energy dissipation of 133.9 ± 3.6 kcal/mol over 112.4 ± 17.9 ps. Kinetic energy decomposition reveals that ∼ 92% of the excess kinetic energy is stored in internal (rotational and vibrational) degrees of freedom. This ReaxFF force field establishes a mechanistic foundation for third-body stabilization in dense reactive environments.

Chowdhury, Emdadul Haque [Pennsylvania State Univ.↗

Nano-Engineered Interfaces in Dual-Layer Electrodes for Protonic Ceramic Cells with Enhanced Stability and Kinetics

Enhancing interfacial stability and charge transfer in protonic ceramic cells (PCCs) remains a critical challenge, as structural degradation and interfacial resistance often compromise durability and efficiency. Here, we report a nanoengineered dual-layer oxygen electrode architecture designed to address these limitations by introducing a fine-grained nanoparticle interfacial contact layer beneath a porous catalytic backbone. The nanoscale powders, through enhanced sintering activity, densify into a robust interfacial layer that promotes strong chemical bonding, uniform adhesion, and continuous ionic/electronic pathways with the BCZYYb electrolyte. This hierarchical architecture mitigates delamination, redistributes mechanical stress, and establishes efficient charge and mass transport channels without relying on corrosive surface treatments. Electrochemical evaluation demonstrates that the dual-layer design markedly reduces interfacial polarization resistance and accelerates electrode kinetics. Compared to the single-layer counterpart, the architecture achieves a peel strength of 44.53 N/cm 2 , a 40% improvement in peak power density (0.96 W cm –2 at 600 °C), and a 130% enhancement in electrolysis current density (4.78 A cm –2 at 1.57 V). Faradaic efficiency remains as high as 88% under high steam concentrations, underscoring minimal charge loss during practical operation. Notably, the electrode retains stability across 450–600 °C and under transient voltage cycling, with impedance spectra confirming suppressed interfacial resistance growth over prolonged use. These results highlight nanoscale interface engineering as a powerful route to enhance both mechanical robustness and electrochemical kinetics in PCCs. The demonstrated scalability and durability of this architecture provide a versatile platform for advancing solid-state electrochemical systems, including reversible fuel cells and high-efficiency hydrogen production technologies.

Faradaic efficiency↗

Machine Learning-Assisted Stability Boundary Determination of Multiport Autonomous Reconfigurable Solar Power Plants

The multiport autonomous reconfigurable solar (MARS) power plant is a promising solution to integrate renewable resources and energy storage systems into the alternating current (ac) power grid and an high-voltage direct current (HVdc) link. In the MARS system, various input power sources are connected to the individual submodules (SMs) through direct current (dc)–dc converters. However, the presence of external power sources can result in unbalanced capacitor voltages of SMs, thereby violating stability constraints under multiple/diverse operating conditions. This article aims to address the gap by accurately determining the stability boundary of the MARS system. As such, a novel machine learning (ML)-assisted energy balancing control (EBC) criterion is proposed. Further, in conjunction with a refined EBC, this approach ensures balanced capacitor voltages across various types of SMs, significantly enhancing the overall system efficiency. The proposed EBC criterion effectively controls EBC activation and deactivation, achieving remarkable accuracy. Both power systems computer aided design (PSCAD)/electromagnetic transients including direct current (EMTDC) simulations and control hardware-in-the-loop (cHIL) tests are conducted to validate the feasibility and efficiency of the proposed method. By combining the EBC and ML-assisted EBC criterion, efficient energy management is achieved for systems featuring multiple input power sources, such as MARS. This approach enables the system to fully exploit its potential across an expanded operational range while upholding high-efficiency standards.

14 SOLAR ENERGY↗

Robust Stabilization of Inverter-Based Resources Using Virtual Resistance-Based Control

This letter proposes a virtual resistance-based nonlinear control to stabilize and robustify the current layer of inverter-based resources, subject to the grid voltage disturbances, and the grid parameter uncertainties. A class of virtual resistances is proposed and analyzed using concepts from dissipative systems theory. Moreover, specific nonlinear virtual resistance-based controllers are derived, with their corresponding performance analytically bounded. Here, the theoretical and simulation results show that the proposed nonlinear virtual resistance-based controllers significantly reduce the L 2 gain of the closed-loop error system to grid voltage variation and parametric uncertainties. Significant improvements of the transient and steady-state current responses are also demonstrated over linear virtual resistance counterparts.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Universal Passive Synchronization Method for Grid-Forming Inverters Without Mode Transition

Power systems are transforming with increasing levels of inverter-based resources (IBRs). This transformation requires critical roles of grid-forming (GFM) inverters replacing synchronous generators for bulk power system stabilization and ancillary services, also allowing flexible power system operation, such as microgrid that is operated by multiple GFM IBRs to achieve system resilience against contingencies. To realize the resilient power systems allowing flexible in-and-out operation of GFM IBRs potentially programmed with different primary controls, a synchronization method universally applicable, i.e., independent of control types, would be beneficial to ease the integration process, but it has not been actively studied. To fill the gap, this paper proposes a universal synchronization method that achieves a passive synchronization to enable a smooth transition in a grid with off-nominal system parameters, i.e., voltage and frequency. The logic proposed requires no modification on the primary control, thus applicable to any type of GFMs with a voltage reference input. To validate the concept, a simulation of an IEEE 13-bus benchmark system modified with 3 GFM inverters is presented. It simulates an inverter-driven black start scenario in which GFM inverters autonomously turn on and connect to the grid under heavy loading, using the synchronization logic. The case study demonstrates that GFM inverters can tune their voltage reference to smoothly synchronize without severe transients, and contribute to a seamless black start of the grid under unbalanced load conditions. Two GFM methods - Droop and dispatchable virtual oscillator control - are used for the demo to validate feasibility and interoperability of the passive synchronization.

black start↗

Seamless Transition of Critical Infrastructures using Droop Controlled Grid-forming Inverters

Seamless recovery of power to critical infrastructures, after grid failure, is a crucial need arising in scenarios that are increasingly becoming more frequent. Here, this article proposes a seamless transition strategy using a single and unified mode-dependent droop controlled grid-forming inverters. The control strategy achieves the following objectives: 1) regulates the output active and reactive power by the droop-controlled inverters to a desired value while operating in on-grid mode; 2) seamless transition and recovery of power injections into the load after grid failure by inverters that operates in grid-forming mode all the time; 3) requires only a single bit of information on the grid/network status for the mode transition. A framework for assessing the stability of the system and to guide the choice of parameters for controllers is developed using control-oriented modeling. A controller hardware-in-the-loop-based real-time simulation study on a test system based on the realistic electrical network of a commercial-scale medical center is conducted for initial prototyping of the control strategy. A hardware experiment is conducted with two 3 - $\phi$, 480 -V, 125 -kVA grid-forming inverters, a 3 - $\phi$, 480 -V, 270 -kVA grid simulator, a physical grid switch, and a physical load bank. The experimental data establishes the effectiveness of the always grid-forming operation and control of inverters in meeting power delivery objectives when on-grid and off-grid under various kinds of loads and scenarios while minimizing transients during transitions. Furthermore, performance comparison with existing strategies showcases the advantage of the proposed strategy.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Control of a Three-Phase Grid-Connected Voltage-Sourced Converter Using Long Short-Term Memory Networks

With the rise of inverter-based resources (IBRs) within the power system, the control of grid-connected converters (GCCs) has become pertinent due to the fact they interface IBRs to the grid. The conventional method of control for a GCC such as the voltage-sourced converter (VSC) is through a decoupled control loop in the synchronous reference frame. However, this model-based control method is sensitive to parameter changes causing deterioration in controller performance. Data-driven approaches such as machine learning can be utilized to design controllers that are capable of operating GCCs in various system conditions. This work explores a deep learning-based control method for a three-phase grid-connected VSC, specifically utilizing a long short-term memory (LSTM) network for robust control. Simulations of a conventional controlled VSC are conducted using Simulink to collect data for training the LSTM-based controller. The LSTM model is built and trained using the Keras and TensorFlow libraries in Python and tested in Simulink. The performance of the LSTM-based controller is evaluated under different case studies and compared to the conventional method of control. Simulation results demonstrate the effectiveness of this approach by outperforming the conventional controller and maintaining stability under different system parameter changes.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Large-Scale Hardware Experiment Demonstration of Operating High Inverter-Based Resource Power Systems With Grid-Forming Inverters

This paper presents experimental hardware results from a microgrid system as the penetration level of grid-forming (GFM) inverters increases. The experiment aims to showcase the advantages of GFM inverters in enhancing system stability and to investigate the operational challenges in systems relying entirely on inverter-based resources (IBRs). Five test scenarios are devised to progressively increase GFM inverter penetration levels: 0% (S1), 19% (S2), 37% (S3), 68% (S4), and 100% (S5). To ensure consistency, identical loading conditions and dynamic events are applied across all scenarios. The conducted tests include load step changes, output variation of grid-following (GFL) inverters during islanded mode, transition operations (such as synchronization to the grid and islanding), and rateof- change-of-frequency (ROCOF) and voltage jump tests during grid-connected mode. Key findings from the tests are summarized as follows: (1) Scenario S1 proved most challenging for load steps, and GFL variations because of insufficient GFM capacity, leaving the diesel generator unable to handle transient ridethrough; (2) Scenario S5 was the most difficult for transition operations, because the lack of a diesel generator to maintain stiff bus voltage resulted in unexpected reactive power flows during synchronization, causing the point of common coupling (PCC) breaker to trip; (3) Scenarios S4 and S5 were particularly challenging for ROCOF tests because of minimal system inertia, leading to large transients that triggered breaker trips; and (4) Scenario S4 exhibited the strongest voltage recovery capability because of the presence of the diesel generator and a higher number of GFM inverters, both of which possess the highest capacity for reactive power injection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

From Event Data to Wind Power Plant DQ Admittance and Stability Risk Assessment

This paper presents a dynamic event data-based stability risk assessment method for power grids with high penetrations of inverter-based resources (IBRs). This method relies on obtaining the IBRs' DQ admittance through dynamic event data and computing the system's eigenvalues based on the admittance models. Two critical technologies are employed in this research, including time-domain and frequency-domain data fitting and dq-frame voltage and current signal derivation. The first technology is key to obtaining the s-domain expressions from the transient response data, and the s-domain DQ admittance model from the frequency-domain measurements. The second technology is key to obtaining the dq-frame voltage and current signals from either the three-phase instantaneous measurements or the phasor measurement unit (PMU) data. The method is illustrated using data generated from a Type-4 wind power plant modeled in PSCAD. This paper demonstrates the technical feasibility of the proposed approach.

17 WIND ENERGY↗

Dynamic Validation of CNN-Based Surrogate Models for Inverter-Based Resources in Open-Source Solvers

Traditionally, distribution system planning has focused on steady-state analyses, with limited consideration of dynamic behavior. However, as large or medium-scale inverter-based resources (IBRs), particularly grid-following (GFL) inverters in commercial or industry buildings, become more prevalent, understanding their dynamic impact is essential for grid planning and operation. This article presents an innovative deep-learning (DL)-approach using convolutional neural networks technique to model the GFL inverters. Developed from real grid-tied commercial IBR transient data, these dynamic DL models overcome proprietary constraints by requiring minimal knowledge of internal converter physics while maintaining high accuracy and flexibility. To demonstrate their applicability, the models were incorporated into GridLAB-D, an open-source, three-phase distribution analysis tool. This integration enables dynamic simulations of large-scale distribution networks with high IBR penetration stability analysis. Rigorous testing and validation, aligned with industry standards, confirmed the reliability and efficiency of this approach, paving the way for enhanced planning and operational assessments of modern power systems.

Deep-learning↗

Modified Andronov-Hopf Oscillator-Based Grid-Forming Converter with Emulated Virtual Cable for Enhanced Power Sharing Performance

Nonlinear oscillator-based grid-forming converters offer superior dynamic and steady-state performance, making them an attractive solution for interconnecting renewable resources. This paper proposes a novel modified Andronov-Hopf oscillator to enhance the operating spectrum and facilitate the integration of renewable energy sources. An inner loop controller based on the Lyapunov energy function is implemented to achieve robust stability and performance, while a virtual cable emulation strategy enables seamless parallel operation. Comprehensive modeling and simulation studies validate the effectiveness of the proposed system, demonstrating its capabilities in addressing diverse operating scenarios, including grid faults, renewable energy fluctuations, and parallel operation. The proposed solution exhibits fast transient response, robust stability, and flexible operation, making it a valuable contribution to the field of renewable energy integration. The results of this study can be used to inform the design and implementation of next-generation grid-forming converters, enabling a more sustainable and reliable energy future. Additionally, the proposed system's ability to operate in both grid-connected and islanded modes makes it an ideal candidate for remote and off-grid renewable energy applications. The proposed solution's scalability and modularity also make it suitable for large-scale renewable energy integration. The proposed system is verified through MATLAB/Simulink and PLECS simulations, demonstrating its effectiveness in ensuring robust and efficient operation.

Andronov-Hopf Oscillator (AHO)↗

The Cause of Insufficient Damping in Phase-Locked-Loop and Its Influence

Phase-locked loop (PLL) is a critical component that synchronizes grid-following (GFL) inverter-based resources (IBR) to the grid. Insufficient damping in PLL has been identified as a cause associated with real-world weak grid stability issues. This paper reveals that the second-order low-pass filter deployed in a sophisticated PLL structure can have negative influence on damping performance and lead to system instability when the grid is weak and power generation is low. Improving the PLL damping is illustrated as one of the mitigation approaches. The dynamic study is carried out in electromagnetic transient (EMT) simulation environment. In addition to EMT demonstration, a simplified analytical model of PLL is developed to represent a PLL with the sophisticated structure. The resulting overall analytical model of the entire system is then used for eigenvalue- based analysis to illustrate the influence of PLL on dynamic modes.

Wang, Zhengyu↗

Impacts of Control, Penetration, and Distribution of Embedded Storage Network in Bulk Power System

The current shift in generation mix from fossil fuel plants towards variable and intermittent renewable energy sources is poised to create a future grid with reduced physical inertia and mismatch between generation and demand. Embedded storage, which is a concept of a coordinated network of storage units sited at the interface between the transmission and distribution system, is proposed as a mechanism to provide a buffer between generation and demand. This paper proposes an automated framework to model and integrate embedded storage in large-scale power systems with industry-grade grid-following (GFL) and grid-forming (GFM) control technologies. More importantly, the developed framework is used to explore the impacts of embedded storage control, penetration, location, and capacity in providing fast frequency response to the grid under contingency events such as generator trips and faults. The framework and study are conducted using the transient-stability simulation tool PSS/E and a realistic model of the Puerto Rico grid as a chosen test system. The simulation results show that GFL and GFM embedded storage, distributed throughout the system, with sufficient penetration and capacity, can effectively improve primary frequency response of the system under the studied contingency events.

Battery Energy Storage, embedded storage, grid-for↗

Data-Driven Security Assessment of Power Grids Based on Machine Learning Approach: Preprint

Data-driven security assessment provides key indicators on power system stability using simulations on scheduling models, as opposed to dynamic simulations that are more time-consuming. This paper investigates data-driven security assessment of power grids based on machine learning. Multivariate random forest regression is used as the machine learning algorithm due to its high robustness to the input data. Three stability issues are analyzed using the proposed machine learning tool, including transient stability, frequency stability and small signal stability. The estimation values from machine learning tool are compared with those from dynamic simulations. Results show that the proposed machine learning tool can effectively predict the stability margins for the three stability metrics.

14 SOLAR ENERGY↗

Limiter-aware adaptive excitation control for hydropower generators with legacy voltage regulation systems

Hydropower units often rely on legacy excitation systems with fixed automatic voltage regulator (AVR) settings, but parameter drift, changing operating conditions, and evolving grid-service demands can degrade terminal-voltage regulation over time. This problem should be addressed because poor voltage regulation affects reactive-power support, system stability, and reliable plant operation, and replacing installed AVR and limiter logic is costly and disruptive in practice. To address this issue, this paper proposes a retrofit-friendly enhancement for hydropower generator excitation systems that combines adaptive tuning of the AVR middle lead–lag branch with a small proportional-integral correction for removing steady bias and slow drift. The adaptive laws are normalized, projection-bounded, and equipped with leakage, while adaptation is enabled only in the middle branch. Thus, the intent of the underexcitation and overexcitation limiters, as well as legacy current and rate limits, remains unchanged. Stability is analyzed under incremental performance assumptions, yielding boundedness and asymptotic tracking in the absence of saturation. The method is evaluated using real operational data from a utility-scale hydropower unit at Rocky Reach Dam, Unit C-8. Compared with the fixed AVR baseline, the proposed method reduces terminal-voltage mean squared error by about 70%, removes long periods of steady-state bias, and improves transient tracking while coexisting with limiter actions. These results show that substantial voltage-control improvement can be achieved on existing hydropower units with minimal integration effort and without replacing the installed AVR structure.

ESST5B model↗