Search NASA⌕ Search

SEARCH · Search NASA

Results for “Emergency Diesel Generator”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Application and development of technologies for engine-condition-based maintenance of emergency diesel generators

The emergency diesel generator (EDG) of a nuclear power plant has the role of supplying emergency electric power to protect the reactor core system in the event of the loss of offsite power supply. Therefore, EDGs should be subject to periodic surveillance testing to verify their ability to supply specified frequencies and voltages at design power levels within a limited time. To maintain optimal reliability of EDGs, condition monitoring/diagnosis technologies must be developed. Changing from periodic disassemble maintenance to condition-based maintenance (CBM) according to predictions of equipment condition is recommended. In this paper, the development of diagnosis technology for CBM and the application of a diesel engine condition-analysis system are described. (authors)

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Emergency Diesel Generator Reliability and Installation Energy Security

The U.S. Department of Defense’s (DoD’s) fixed installations - or military bases - are a critical element of national security. Military bases support the maintenance and deployment of weapons systems, training and mobilization of combat forces, and provide direct support to combat operations. Fixed installations do not operate without energy and they rely largely on electricity to support critical missions and functions. Installations are dependent on a commercial grid that is vulnerable to disruption due to severe weather, physical attacks, and cyberattacks. This report looks at the impact on the highest priority critical loads.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Online Monitoring Technical Basis and Analysis Framework for Emergency Diesel Generators - Interim Report for FY 2013

The Light Water Reactor Sustainability program at Idaho National Laboratory is actively conducting research to develop and demonstrate online monitoring capabilities for active components in existing nuclear power plants. Idaho National Laboratory and the Electric Power Research Institute are working jointly to implement a pilot project to apply these capabilities to emergency diesel generators and generator step-up transformers. The Electric Power Research Institute Fleet-Wide Prognostic and Health Management Software Suite will be used to implement monitoring in conjunction with utility partners: Braidwood Generating Station (owned by Exelon Corporation) for emergency diesel generators, and Shearon Harris Nuclear Generating Station (owned by Duke Energy Progress) for generator step-up transformers. This report presents monitoring techniques, fault signatures, and diagnostic and prognostic models for emergency diesel generators. Emergency diesel generators provide backup power to the nuclear power plant, allowing operation of essential equipment such as pumps in the emergency core coolant system during catastrophic events, including loss of offsite power. Technical experts from Braidwood are assisting Idaho National Laboratory and Electric Power Research Institute in identifying critical faults and defining fault signatures associated with each fault. The resulting diagnostic models will be implemented in the Fleet-Wide Prognostic and Health Management Software Suite and tested using data from Braidwood. Parallel research on generator step-up transformers was summarized in an interim report during the fourth quarter of fiscal year 2012.

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Impact of Emergency Diesel Generator Reliability on Microgrids and Building-Tied Systems

Microgrids are an emerging alternative as an energy backup system for critical electric loads and have improved performance compared to the traditional architecture where a single emergency diesel generator is tied to an individual building. Both architectures are dependent on the reliability of their individual generators and a quantitative and realistic comparison of the overall system reliability of the two architectures is lacking. Using recently published work on emergency diesel generator finite reliability, a quantitative methodology is presented to compare the reliability of a microgrid architecture based on centralized emergency diesel generators to the traditional approach of generators tied to individual buildings. Three system reliability performance metrics are calculated as a function of outage duration: (1) probability to meet 100% of the critical load; (2) expected fraction of lost load; and (3) probability to meet the highest priority critical loads. It is shown that stand-alone building-tied emergency diesel generators systems, even when two emergency diesel generators are used per building, cannot provide the reliability required to sustain critical loads for a grid outage lasting multiple days. Due to their network configuration and ability to share load, diesel generator-based microgrid configurations are estimated to have = 93% probability of powering all buildings for a 2-week outage there the individual building-tied emergency diesel generator architecture has a =20% probability. Microgrids do present other susceptibilities that are site specific and should be considered including vulnerabilities associated with the on-campus distribution system and cybersecurity.

backup power↗

Enhanced Component Performance Study: Emergency Diesel Generators 1998–2018

This report presents an enhanced performance evaluation of emergency diesel generators (EDGs) at U.S. commercial nuclear power plants. This report evaluates component performance over time using (1) Institute of Nuclear Power Operations (INPO) Consolidated Events Database (ICES) data from 1998 through 2018 and (2) maintenance unavailability (UA) performance data from Mitigating Systems Performance Index (MSPI) Basis Document data from 2002 through 2018. The objective is to show estimates of current failure probabilities and rates related to EDGs, trend these data on an annual basis, determine if the current data are consistent with the probability distributions currently recommended for use in NRC probabilistic risk assessments, show how the reliability data differ for different EDG manufacturers and for EDGs with different ratings; and summarize the subcomponents, causes, detection methods, and recovery associated with each EDG failure mode. Engineering analyses were performed with respect to time period and failure mode without regard to the actual number of EDGs at each plant. The factors analyzed are: sub-component, failure cause, detection method, recovery, manufacturer, and EDG rating. A statistically significant increasing trend was identified in the frequency of FTLR demands for emergency power system (EPS) and high pressure core spray (HPCS) EDGs and a statistically significant decreasing trend was identified in the frequency of run > 1H hours for EPS and HPCS EDGs.

99 GENERAL AND MISCELLANEOUS↗

Enhanced Component Performance Study. Emergency Diesel Generators 1998–2013

This report presents an enhanced performance evaluation of emergency diesel generators (EDGs) at U.S. commercial nuclear power plants. This report evaluates component performance over time using Institute of Nuclear Power Operations (INPO) Consolidated Events Database (ICES) data from 1998 through 2013 and maintenance unavailability (UA) performance data using Mitigating Systems Performance Index (MSPI) Basis Document data from 2002 through 2013. The objective is to present an analysis of factors that could influence the system and component trends in addition to annual performance trends of failure rates and probabilities. The factors analyzed for the EDG component are the differences in failures between all demands and actual unplanned engineered safety feature (ESF) demands, differences among manufacturers, and differences among EDG ratings. Statistical analyses of these differences are performed and results showing whether pooling is acceptable across these factors. In addition, engineering analyses were performed with respect to time period and failure mode. The factors analyzed are: sub-component, failure cause, detection method, recovery, manufacturer, and EDG rating.

20 FOSSIL-FUELED POWER PLANTS↗

Enhanced Component Performance Study: Emergency Diesel Generators 1998-2020

This report presents an enhanced performance evaluation of emergency power system (EPS) and high-pressure core spray (HPCS) emergency diesel generators (EDGs) at U.S. commercial nuclear power plants. This report evaluates component performance over time using (1) Institute of Nuclear Power Operations (INPO) Industry Reporting and Information System (IRIS) data from 1998 through 2020 and (2) maintenance unavailability performance data from Mitigating Systems Performance Index (MSPI) Basis Document data from 2002 through 2020. The objective is to show estimates of current failure probabilities and rates related to EDGs, trend these data on an annual basis, determine if the current data are consistent with the probability distributions currently recommended for use in NRC probabilistic risk assessments, show how the reliability data differ for different EDG manufacturers and for EDGs with different ratings; and summarize the subcomponents, causes, detection methods, and recovery associated with each EDG failure mode. The EDG failure modes considered are fail to start (FTS), fail to load and run (FTLR), and fail to run after one hour of operation (FTR>1H). Engineering analyses were performed with respect to time period and failure mode without regard to the actual number of EDGs at each plant. The factors analyzed are: subcomponent, failure cause, detection method, recovery, manufacturer, and EDG rating. The following increasing trends were identified for EDGs for the most recent 10-year period: • HPCS EDG FTS failure probability • EPS and HPCS EDG frequency of start demands (demands per reactor year) • EPS and HPCS EDG frequency of FTLR demands. The following decreasing trends were identified for EDGs for the most recent 10-year period: • EPS EDG FTS failure probability • EPS EDG FTLR failure probability • EPS EDG unavailability • EPS and HPCS EDG frequency of FTLR events (failures per reactor year).

99 GENERAL AND MISCELLANEOUS↗

Enhanced Component Performance Study: Emergency Diesel Generators 1998–2014

This report presents an enhanced performance evaluation of emergency diesel generators (EDGs) at U.S. commercial nuclear power plants. This report evaluates component performance over time using (1) Institute of Nuclear Power Operations (INPO) Consolidated Events Database (ICES) data from 1998 through 2014 and (2) maintenance unavailability (UA) performance data from Mitigating Systems Performance Index (MSPI) Basis Document data from 2002 through 2014. The objective is to show estimates of current failure probabilities and rates related to EDGs, trend these data on an annual basis, determine if the current data are consistent with the probability distributions currently recommended for use in NRC probabilistic risk assessments, show how the reliability data differ for different EDG manufacturers and for EDGs with different ratings; and summarize the subcomponents, causes, detection methods, and recovery associated with each EDG failure mode. Engineering analyses were performed with respect to time period and failure mode without regard to the actual number of EDGs at each plant. The factors analyzed are: sub-component, failure cause, detection method, recovery, manufacturer, and EDG rating. Six trends with varying degrees of statistical significance were identified in the data.

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

Enhanced Component Performance Study: Emergency Diesel Generators 1998–2022

This report presents an enhanced performance evaluation of the emergency power system (EPS) and high-pressure core spray (HPCS) emergency diesel generators (EDGs) at U.S. commercial nuclear power plants. This report evaluates component performance over time using (1) Institute of Nuclear Power Operations (INPO) Industry Reporting and Information System (IRIS) data from 1998 through 2022 and (2) maintenance unavailability performance data from Mitigating Systems Performance Index (MSPI) Basis Document data from 2002 through 2022. The objective is to show estimates of current failure probabilities and rates related to EDGs, trend these data on an annual basis, determine if the current data are consistent with the probability distributions currently recommended for use in Nuclear Regulatory Commission (NRC) probabilistic risk assessments, show how the reliability data differ for different EDG manufacturers and for EDGs with different ratings; and summarize the subcomponents, causes, detection methods, and recovery associated with each EDG failure mode. The EDG failure modes considered are fail to start (FTS), fail to load and run (FTLR), and fail to run after one hour of operation (FTR>1H). Engineering analyses were performed with respect to time-period and failure mode without regard to the actual number of EDGs at each plant. The factors analyzed include subcomponent, failure cause, detection method, recovery, manufacturer, and EDG rating. The following increasing trends were identified for EDGs for the most recent 10-year period: (1) HPCS EDG FTS failure probability, (2) EPS and HPCS EDG frequency of start demands (demands per reactor year), and (3) EPS and HPCS EDG frequency of FTLR demands. The following decreasing trends were identified for EDGs for the most recent 10-year period: (1) EPS EDG FTS failure probability, (2) EPS EDG FTLR failure probability, (3) EPS EDG unavailability, and (4) EPS and HPCS EDG frequency of FTLR events (failures per reactor year).

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Enhanced Component Performance Study: Emergency Diesel Generators 1998-2024

This report presents an enhanced performance evaluation of the emergency power system (EPS) and high-pressure core spray (HPCS) emergency diesel generators (EDGs) at U.S. commercial nuclear power plants. This report evaluates component performance over time using (1) Institute of Nuclear Power Operations (INPO) Industry Reporting and Information System (IRIS) data from 1998 through 2024 and (2) maintenance unavailability performance data from Mitigating Systems Performance Index (MSPI) Basis Document data from 2002 through 2024. The objective is to show estimates of current failure probabilities and rates related to EDGs, trend these data on an annual basis, determine if the current data are consistent with the probability distributions currently recommended for use in Nuclear Regulatory Commission (NRC) probabilistic risk assessments, show how the reliability data differ for different EDG manufacturers and for EDGs with different ratings; and summarize the subcomponents, causes, detection methods, and recovery associated with each EDG failure mode. The EDG failure modes considered are fail to start (FTS), fail to load and run (FTLR), and fail to run after one hour of operation (FTR>1H). Engineering analyses were performed with respect to time-period and failure mode without regard to the actual number of EDGs at each plant. The factors analyzed include subcomponent, failure cause, detection method, recovery, manufacturer, and EDG rating. The following increasing trends were identified for EDGs for the most recent 10-year period: • EPS and HPCS EDG frequency of start demands (demands per reactor year) • EPS and HPCS EDG frequency of FTLR demands • EPS and HPCS EDG frequency of run>1H hours. The following decreasing trends were identified for EDGs for the most recent 10-year period: • EPS EDG FTR>1H failure rate • EPS EDG unreliability • EPS and HPCS EDG frequency of FTR>1H events (failures per reactor year).

22 GENERAL STUDIES OF NUCLEAR REACTORS↗

Verification of voltage/frequency requirement for emergency diesel generator in nuclear power plant using dynamic modeling

One major cause of the plant shutdown is the loss of electrical power. The study is to comprehend the coping action against station blackout including emergency diesel generator, sequential loading of safety system and to ensure that the emergency diesel generator should meet requirements, especially voltage and frequency criteria using modeling tool. This paper also considered the change of the sequencing time and load capacity only for finding electrical design margin. However, the revision of load list must be verified with safety analysis. From this study, it is discovered that new load calculation is a key factor in EDG localization and in-house capability increase.

46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND ↗

Systems engineering approach towards performance monitoring of emergency diesel generator

Systems engineering is an interdisciplinary approach and means to enable the realization of successful systems. In this study, systems engineering approach towards the performance monitoring of Emergency Diesel Generator (EDG) is presented. Performance monitoring is part and parcel of predictive maintenance where the systems and components conditions can be detected before they result into failures. In an effort to identify the proposal for addressing performance monitoring, the EDG boundary has been defined. Based on the Probabilistic Safety Analysis (PSA) results and industry operating experiences, the most critical component is identified. This paper proposed a systems engineering concept development framework towards EDG performance monitoring. The expected output of this study is that the EDG reliability can be improved by the performance monitoring alternatives through the systems engineering concept development effort.

42 ENGINEERING↗

Emergency Diesel Generator Backup Power Systems for Military Bases

Backup power systems on military installations must provide reliable power during a grid outage. The risks of blackouts and loss of electric power are not new. Outages of just a few hours are well known, but longer duration outages are becoming more frequent. The U.S. Army, Navy, and Air Force now require backup power from one to two weeks. For multiday outages, the reliability of emergency diesel generators will have a significant impact on the installation’s backup power system’s ability to provide power for critical missions.

backup power↗

Reliability of emergency and standby diesel generators: Impact on energy resiliency solutions

Emergency diesel generators are the most common form of backup power for critical loads when the grid fails and are most often deployed as stand-alone generators (<2000 kW) tied to individual buildings for hospitals, emergency services, military bases, ports, airports, industries, and commercial facilities. Understanding the finite reliability of emergency diesel generators during continuous operation is critical for energy planners, managers, and end-users. A new analysis of two large non-public emergency diesel generator operational data sets shows that commonly used reliability metrics are inadequate to predict the performance during a grid outage. Additional metrics addressing the likelihood of an emergency diesel generator to be available at the time an outage starts, successfully start and carry load, and constantly run for the duration of the outage are needed to predict the continuous run-time reliability of emergency diesel generators during a grid outage. This is the first analysis of the reliability of modern generators that follow standard maintenance protocols commonly used for backup power and these new metrics are shown to be dependent on the level of emergency diesel generator maintenance with values that can vary by more than an order of magnitude. Even using the new metrics for well-maintained emergency diesel generators, the analysis shows that the single emergency diesel generators configurations are only 80% likely to provide power for the duration of a two-week grid outage.

ENERGY PLANNING, POLICY, AND ECONOMY,POWER TRANSMI↗

Development of Asset Fault Signatures for Prognostic and Health Management in the Nuclear Industry

Proactive online monitoring in the nuclear industry is being explored using the Electric Power Research Institute’s Fleet-Wide Prognostic and Health Management (FW-PHM) Suite software. The FW-PHM Suite is a set of web-based diagnostic and prognostic tools and databases that serves as an integrated health monitoring architecture. The FW-PHM Suite has four main modules: Diagnostic Advisor, Asset Fault Signature (AFS) Database, Remaining Useful Life Advisor, and Remaining Useful Life Database. This paper focuses on development of asset fault signatures to assess the health status of generator step-up generators and emergency diesel generators in nuclear power plants. Asset fault signatures describe the distinctive features based on technical examinations that can be used to detect a specific fault type. At the most basic level, fault signatures are comprised of an asset type, a fault type, and a set of one or more fault features (symptoms) that are indicative of the specified fault. The AFS Database is populated with asset fault signatures via a content development exercise that is based on the results of intensive technical research and on the knowledge and experience of technical experts. The developed fault signatures capture this knowledge and implement it in a standardized approach, thereby streamlining the diagnostic and prognostic process. This will support the automation of proactive online monitoring techniques in nuclear power plants to diagnose incipient faults, perform proactive maintenance, and estimate the remaining useful life of assets.

46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND ↗

Resilience and economics of microgrids with PV, battery storage, and networked diesel generators

Current designs and assessments of microgrids have ignored component reliability, leading to significant errors in predicting a microgrid’s performance while islanded. Existing life cycle cost studies on hybrid microgrids—which combine photovoltaics (PV), battery storage and networked emergency diesel generators—also have not identified all the potential economic opportunities. Reducing the number of emergency diesel generators through reliance on PV and battery, retail bill savings, and demand response and wholesale market revenue streams are all important. This paper provides a new statistical methodology that calculates the impact of distributed energy reliability and variability on a microgrid’s performance and a novel use of the optimization platform REopt to explore multiple cost savings and revenue streams. We examine the impacts for microgrids in California, Maryland, and New Mexico and show that a hybrid microgrid is a more resilient and cost-effective solution than a diesel-only system. Under realistic conditions, a hybrid microgrid can provide higher system reliability when islanded and have a lower life cycle cost under multiple market conditions than a traditional diesel generator-based system. The improved performance of the hybrid system is resilient to conditions experienced over the last 20 years in solar irradiance and sees little degradation in performance immediately after a hurricane. The cost savings to provide this more resilient backup power system as compared to a diesel-only microgrid are significant. The net present cost for a hybrid microgrid is 19% lower in New Mexico and 35% lower in Maryland than a diesel-only microgrid. In California, the net present cost of the hybrid microgrid is negative because, unlike a diesel-only microgrid, a hybrid microgrid has lower life cycle costs than the power costs without a microgrid.

25 ENERGY STORAGE↗

Light Water Reactor Sustainability Program

The online monitoring (OLM) of active components project under the Light Water Reactor Sustainability program at Idaho National Laboratory (INL) implemented fault signatures for generator step-up transformers (GSUs) and emergency diesel generators (EDGs). INL, in collaboration with Electric Power Research Institute (EPRI), demonstrated the OLM capabilities for GSUs and EDGs using the EPRI Fleet-Wide Prognostic and Health Management (FW PHM) Suite software.

46 INSTRUMENTATION RELATED TO NUCLEAR SCIENCE AND ↗

Online Monitoring of Plant Assets in the Nuclear Industry

Today’s online monitoring technologies provide opportunities to perform predictive and proactive health management of assets within many different industries, in particular the defense and aerospace industries. The nuclear industry can leverage these technologies to enhance safety, productivity, and reliability of the aging fleet of existing nuclear power plants. The U.S. Department of Energy’s Light Water Reactor Sustainability Program is collaborating with the Electric Power Research Institute’s (EPRI’s) Long-Term Operations program to implement online monitoring in existing nuclear power plants. Proactive online monitoring in the nuclear industry is being explored using EPRI’s Fleet-Wide Prognostic and Health Management (FW-PHM) Suite software, a set of web-based diagnostic and prognostic tools and databases that serves as an integrated health monitoring architecture. This paper focuses on development of asset fault signatures used to assess the health status of generator step-up transformers and emergency diesel generators in nuclear power plants. Asset fault signatures describe the distinctive features based on technical examinations that can be used to detect a specific fault type. Fault signatures are developed based on the results of detailed technical research and on the knowledge and experience of technical experts. The Diagnostic Advisor of the FW-PHM Suite software matches developed fault signatures with operational data to provide early identification of critical faults and troubleshooting advice that could be used to distinguish between faults with similar symptoms. This research is important as it will support the automation of predictive online monitoring techniques in nuclear power plants to diagnose incipient faults, perform proactive maintenance, and estimate the remaining useful life of assets.

20 FOSSIL-FUELED POWER PLANTS↗