General Line Ampacity State Solver

INL’s General Line Ampacity State Solver (GLASS) is a high performance software platform that enables advanced grid system operations and planning efforts to be computed in real time. It enables the combination of advanced sensors and sensor networks, communication and data transfer channels, secure and reliable data management, and real-time processing through a flexible system architecture, with the ability to support and integrate with any utility enterprise system. GLASS is designed to help resolve the problems associated with thermally limited transmission and distribution networks, namely bare overhead power transmission lines. GLASS enables the methodology of Concurrent Cooling (Dynamic Line Rating) by reducing the need of using a cost-prohibited number of weather stations (reduce the number of weather stations per mile of overhead power line) to achieve the resolution necessary for individual electric transmission line span capacity calculations. GLASS achieves this by coupling real-time grid operations data and infrastructure architecture information with real-time field deployed weather station measurements and pre-computed Computational Fluid Dynamics (CFD)-based wind modeling interpolation parameters (look-up tables). GLASS uses mathematical models based on the IEEE 738 standard and builds off of the provided iterative solution using modern software paradigms and programming styles to provide a more robust and modular software system. GLASS also interfaces in real-time with utility companies using known transmission line spans and structures. GLASS provides real-time ampacity calculations based on recent weather station data as well as transmission line specifications. GLASS also allows the user to interact graphically with internal databases, which include information such as transmission line conductor types and thermal rating limits, weather station names and locations, specific transmission line span and structure locations, as well as recent ampacity calculations.

Gentle, Jake↗

GLASS: General Line Ampacity State Solver

The U.S. installed more than 8,000 megawatts of wind generation in 2016. Wind energy is now powering more than 20 million homes. Idaho National Laboratory technology uses real time weather information and computer models to help utilities integrate more wind energy, relieving transmission line congestion, and extending the life time of existing grid infrastructure.

17 WIND ENERGY↗

Transmission Line Ampacity Improvements of AltaLink Wind Plant Overhead Tie-Lines Using Weather-Based Dynamic Line Rating

Abstract—Overhead transmission lines (TLs) are conventionally given seasonal ratings based on conservative environmental assumptions. Such an approach often results in underutilization of the line ampacity as the worst conditions prevail only for a short period over a year/season. We presents dynamic line rating (DLR) as an enabling smart grid technology that adaptively computes ratings of TLs based on local weather conditions to utilize additional headroom of existing lines. In particular, general line ampacity state solver utilizes measured weather data for computing the real-time thermal rating of the TLs. The performance of the presented method is demonstrated from a field study of DLR technology implementation on four TL segments at AltaLink, Canada. The performance is evaluated and quantified by comparing the existing static and proposed dynamic line ratings, and the potential benefits of DLR for enhanced transmission assets utilization. For the given line segments, the proposed DLR results in real-time ratings above the seasonal static ratings for most of the time; up to 95.1% of the time, with a mean increase of 72% over static rating.

17 WIND ENERGY↗

Improvement of Transmission Line Ampacity Utilization by Weather-Based Dynamic Line Rating

Most of the existing overhead transmission lines (TLs) are assigned a static rating by considering the conservative environmental conditions (e.g., high ambient temperature and low wind speed). Such a conservative approach often results in underutilization of line ampacity because the worst conditions prevail only for a short period of time during the year. Dynamic line rating (DLR) utilizes local meteorological conditions and grid loadings to adaptively compute additional line ampacity headroom that may be available due to favorable local environmental conditions. This paper details Idaho National Laboratory-developed weather-based DLR, which utilizes a state-of-the-art general line ampacity state solver for real-time computation of thermal ratings of TLs. Performance of the proposed DLR solution is demonstrated in existing TL segments at AltaLink, Canada, and the potential benefits of the proposed DLR for enhanced transmission ampacity utilization are quantified. Moreover, we investigated a hypothetical case for emulating the impact of an additional wind plant near the test grid. Furthermore, the results for the given system and data configurations demonstrated that real-time ratings were above the seasonal static ratings for at least 76.6% of the time, with a mean increase of 22% over the static rating, thereby demonstrating huge potential for improvement on ampacity utilization.

17 WIND ENERGY↗

Transmission Route Engineering Analysis And Design

INL’s Transmission Route Engineering Analysis and Design [tool] (TREAD) is a tool meant for the design and routing of new transmission lines. TREAD is capable of taking an arbitrarily large amount of surface layers represented as geographical files and then using a modified version of Dijkstra’s Algorithm for finding the best path. TREAD is also capable of interacting with different weather models in order to gather weather data about the locations that are being routed to. This weather data is then used in conjunction with INL’s General Line Ampacity State Solver.

Lehmer, JacobP.↗

Using Computational Fluid Dynamics to Assess Dynamic Line Rating in Southern Idaho

The overall goal of the study is to combine computational fluid dynamics (CFD) simulations with weather data that is collected over a 1-year long period across southern Idaho to calculate the dynamic line ratings (DLR) of several transmission lines. These ratings can be compared to the static rating assumptions to show the potential for additional current carrying capacity along transmission lines through account for additional effects of convective cooling from the wind. The region of interest is quite large, sized at 144 km by 98 km; in order to cover this large region, the CFD simulations are split into four separate regions of over 80 million computational cells each. The weather data that was collected suggest initial assumptions used to make the static ratings were vastly over predicted with regards to summer temperatures and solar irradiance. The weather data is ran through the General Line Ampacity State Solver (GLASS) tool that was developed by Idaho National Laboratory (INL) to parse large quantities of weather data across thousands of transmission midpoint spans in the region. For shorter lines, the dynamic line ratings often show large improvement over static ratings. The case study here shows over 95% of the time DLR values are above static values on the short transmission lines. However, for long lines, a conundrum occurs, where due to the large number of weather stations associated with the line, there is often a single weather station which may read local wind speeds of zero. This often defaults the line rating to be limited by natural convective cooling and does not show as much improvement over static as might be expected from the weather data if DLR calculations are used with a minimum ampacity across all midpoints. Other methods with transient state calculations should be utilized for long lines.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Using Computational Fluid Dynamics of Wind Simulations Coupled With Weather Data to Calculate Dynamic Line Ratings

Dynamic line rating is a technology that allows for the rating of electrical conductors to be calculated based on local weather conditions rather than using ”worst-case” assumptions of weather conditions. The static ratings are typically based on weather conditions that are conservative in nature, and thus dynamic line rating may provide room to increase the current capacity. The local weather conditions may estimate conditions more accurately near the transmission lines accounting for terrain such as nearby hills. One way to estimate the local weather conditions is through the use of computational fluid dynamics. The results of a wind field simulation can be coupled with sparsely located weather stations to provide an accurate assessment of the wind speeds along the path of the conductor. Here, the wind field simulations are calculated using a steady state Reynolds-averaged Navier-Stokes model. These results along with local solar radiance measurements can be used to provide estimates of the steady state ampacity with the standard IEEE equations. An advanced test case for this process involves performing these simulations in a complex terrain, Hells Canyon, the deepest river gorge in North America. The results show that by using weather-based sensors without considering localized wind conditions, the available ampacity may be over-predicted significantly.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Forecasting Dynamic Line Rating with Spatial Variation Considerations

Dynamic line rating (DLR) is a technology that allows the ampacity of an electrical conductor to be calculated using real-time or forecasted weather conditions. Historically, the ampacity of a conductor has been determined using a static line rating method which assumes conservative weather assumptions. Therefore, not only can DLR give a more accurate measurement of the true ampacity of a conductor, but it can also increase its ampacity during weather conditions with greater thermal mitigations. The two primary cooling factors in the ampacity calculations are wind speed and direction. In complex terrain, wind speed and direction can have large variations over short distances. Therefore, accurately identifying the limiting span of a transmission line requires high spatial resolution of the wind along its path. One solution is to install dense weather stations along their path, though this can become costly over long distances. Therefore, researchers have investigated the use of Computation Fluid Dynamic (CFD) simulations to accurately compute the wind field along the path of a transmission line and use these results to identify the limiting section of the conductor. This work presents a case study that evaluates the coupling of CFD simulations and forecasted weather simulations using the High-Resolution Rapid Refresh (HRRR) model points over a 2-year span within a region in south eastern Idaho. The primary goal of the work is the evaluation of the number of HRRR model points used, i.e., weather stations, along the path of the line and the accuracy of the resulting DLR ampacity. This was done using 4, 10, 17, 26, and 35 HRRR model points along two transmission line paths. The results indicate that as the number of model points are increased, the DLR ampacity of the lines decrease, yet converge as more points are added and demonstrate little change with additional HRRR points. It is expected that these results can help transmission line operators identify the number of weather stations that must be installed when coupled with CFD simulations and DLR ampacity to ensure accurate ratings and safe operations.

17 WIND ENERGY↗

Forecasting Dynamic Line Rating with Spatial Variation Considerations

Dynamic line rating (DLR) is a technology that allows the ampacity of an electrical conductor to be calculated using real-time or forecasted weather conditions. Historically, the ampacity of a conductor has been determined using a static line rating method which assumes conservative weather assumptions. Therefore, not only can DLR give a more accurate measurement of the true ampacity of a conductor, but it can also increase its ampacity during weather conditions with greater thermal mitigations. The two primary cooling factors in the ampacity calculations are wind speed and direction. In complex terrain, wind speed and direction can have large variations over short distances. Therefore, accurately identifying the limiting span of a transmission line requires high spatial resolution of the wind along its path. One solution is to install dense weather stations along their path, though this can become costly over long distances. Therefore, researchers have investigated the use of Computation Fluid Dynamic (CFD) simulations to accurately compute the wind field along the path of a transmission line and use these results to identify the limiting section of the conductor. This work presents a case study that evaluates the coupling of CFD simulations and forecasted weather simulations using the High-Resolution Rapid Refresh (HRRR) model points over a 2-year span within a region in south eastern Idaho. The primary goal of the work is the evaluation of the number of HRRR model points used, i.e., weather stations, along the path of the line and the accuracy of the resulting ampacity. This was done using 4, 10, 17, 26, and 35 HRRR model points along two transmission line paths. The results indicate that as the number of model points are increased, the DLR ampacity of the lines decrease, yet converge as more points are added and demonstrate little change with additional HRRR points. It is expected that these results can help transmission line operators identify the number of weather stations that must be installed when coupled with CFD simulations and DLR ampacity to ensure accurate ratings and safe operations.

17 WIND ENERGY↗