Search NASA⌕ Search

SEARCH · Search NASA

Results for “Grids”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Improving Frequency Stability and Minimizing Load Shedding Events by Adopting Grid-Scale Energy Storage with Grid Forming Inverters

The upward adoption trend of renewable generation not only means cleaner energy integrated into modern power grids, but also that most new generation sources are based on front-end inverter bridges, used as interfaces to most wind generation and all the solar PV. It is well known that due to their power electronics-based construction rather than rotational shafts, these sources do not provide inertia inherently, nor substantial amounts of short-circuit currents. However, stable energy such as what can be stored in energy storage systems, although interfaced via inverters, can be controlled to respond to system disturbances in a manner that emulates inertial behavior. This paper focuses on the application of such energy storage systems to augment inertia in the island of Puerto Rico. To do so, a user defined inverter model that contains grid forming capabilities and fast frequency response is modeled and integrated into the real transmission system in power flow and dynamics software. Energy storage is then connected to two selected areas so that it not only provides frequency regulation to avoid widespread load shedding events, but also other tangible benefits. The simulated cases suggest that even relatively small energy storage systems can avert load shedding events if adequately placed in the transmission network.

Grid-forming inverters, IBR, Inertia↗

Experimental Characterization Test of a Grid-Forming Inverter for Microgrid Applications

Standardized experimental testing protocols for grid forming (GFM) inverters to ensure expected operation under both normal and contingency conditions do not exist. Such protocols increase the confidence of system owner/operators that an inverter deployed in a proposed system will engage in typical behaviors to ensure interoperability with other units and ancillary equipment (e.g. protection equipment). This paper presents systematic and comprehensive test protocols to evaluate the performance of GFM inverters under the following operational configurations: islanded operation, heterogeneous islanded operation (parallel with a synchronous generator), grid-connected operation, and transition operation. A commercial GFM inverter is used to verify the test protocols and to understand the inverter's performance and functionalities. In particular, required configuration and tuning of the inverter will be explained in the full paper to enrich the testing protocol.

black start↗

Grid Strength Assessment for High Levels of Inverter-based Resources in the Puerto Rico Power

A system-wide assessment of the Puerto Rico power system grid strength is studied when considering high levels of inverter-based resource penetration. This study is carried out in PSSE and assesses the impact of inverter-based resource (IBR) contributions in response to three-phase ground faults. A hypothetical 100% inverter-based generation scenario is created to assess the extreme impact on short circuit levels and a realistic scenario is considered to assess the impact to short circuit ratios. The overall conclusion is that short circuit capacity and current will drastically decrease in a high IBR scenario, an effect that is quantified in this paper. The short circuit ratio metric is typically used to assess the impact of IBR but generally overestimates grid strength due to not accounting for the impact from multiple IBRs. Other methods such as equivalent circuit based short circuit ratio and weighted short circuit ratio offer a more comprehensive consideration for multiple IBRs and can better account for their mutual interactions. The work presented in this paper is part of the PR100 study.

inverter based resources, PR100, grid strength↗

Demonstration of Grid Services Using Mixed Grid-Forming and Grid-Following Technologies at the Wheatridge Renewable Energy Facility (Final Technical Report)

This Final Technical Report summarizes the analytical, modeling, and engineering work performed to evaluate grid-forming (GFM) inverter capabilities within a large hybrid renewable energy facility. The project focused on assessing the ability of advanced inverter-based resources to provide essential reliability services through coordinated operation of grid-forming (GFM) and grid-following (GFL) technologies. During Budget Period 1, the project developed a comprehensive framework of GFM performance metrics, including angle support, voltage regulation, frequency response, damping behavior, and current-limiting performance. Extensive electromagnetic transient (EMT) studies and hardware-in-the-loop (HIL) testing were conducted to validate GFM behavior under a range of operating conditions, including weak-grid scenarios, voltage disturbances, and multi-resource interactions. The project also established validated modeling approaches, plant-level control integration strategies, commissioning frameworks, and high-speed measurement infrastructure to support future field demonstration. Although the project concluded prior to field demonstration, the results provide a utility-scale foundation for evaluating, modeling, and deploying grid-forming technologies. The methodologies and tools developed contribute to industry understanding of inverter-based resource behavior and support future power system reliability under increasing renewable penetration.

14 SOLAR ENERGY↗

Automated Manufacturing of Grid Stiffened Panels with Radically Reduced Tooling

Grid stiffened continuous fiber reinforced composite panels are an attractive option for creating lightweight structures due to the tailorability for various applications and the resulting high specific properties. However, the panel stiffeners and stiffener intersections result in high tooling complexity and correspondingly high cost of implementation. These factors have limited the impact of such structures in the composites industry. Previous research has demonstrated the ability to produce high quality, high aspect ratio beams, representative of individual grid stiffeners, using E-glass/PET comingled tow via direct digital manufacturing. Further, prior preliminary efforts have demonstrated the potential to use the same approach to manufacture grid intersections that have continuous fiber in both directions. To expand on the previous efforts in grid stiffeners produced by direct digital manufacture with radically reduced tooling requirements, this effort compares two methods of providing positioning and consolidation, nozzle vs. roller. Both processes are based on a commingled yarn feedstock. The extrusion through a nozzle has been shown to enable grid intersection control through local variations in applied consolidation and serves as the baseline process. However, this approach requires a continuous placement path to create the complete grid stiffened panel as no mechanism for cutting and restarting has been implemented. Alternatively, a newly developed placement head incorporating cut and refeed, mounted to a 6-axis robot, offers the potential of improved path placement efficiency. The two techniques are used to produce similar grid composite stiffeners to evaluate the effectiveness of producing the grid intersections. Rate of deposition of the two end effectors are compared and the quality of the associated grid stiffeners, and intersections, are determined through measurement of geometry, fiber volume fraction and void fraction.

Engineering↗

Use of Grid-Forming Medium-Voltage Power Electronics Hub in a Microgrid Setting

This paper presents the application of a new design of a multiport, modular, medium-voltage power electronics hub (M3PE-HUB) in a microgrid setting. The M3PE-HUB system was modeled in a digital real-time simulator (DRTS) and integrated into the Banshee microgrid test system. This paper presents the preliminary DRTS simulation-based results of the M3PE-HUB system connected in a test microgrid system. Verification and validation of the M3PE-HUB architecture and controls in the test microgrid setting are the primary contributions of this work. The results of the operation during the islanding and resynchronization process indicate the feasibility of the proposed architecture in a microgrid setting. This paper also presents results for a system reconfiguration use case where the M3PE-HUB was used to reconfigure the system under a fault condition.

grid forming↗

A method for assessing economic, environmental, and reliability tradeoffs of interregional transmission connecting ERCOT (the Texas grid) to the eastern and western grids

Reliable development of the power grid is an evolving concern for humanity due to extreme weather that frequently threatens power sector infrastructure. The state of Texas is a uniquely structured testbed for grid planners to study when looking for solutions to development, innovation, and overcoming such challenges. Because of its size and islanded structure, Texas is small enough to model, but big enough to matter. Texas is a global leader in energy production, energy consumption, and maintains an unusually diverse fuel mix. In addition, the state has experienced winter freezes, heat waves, wind storms, droughts and floods that have threatened power sector infrastructure or caused recent blackouts and calls for demand side conservation. One of the most devastating of these events was the North American winter storm, dubbed “Winter Storm Uri” by the Weather Channel, that froze the region in February 2021 and led to an extended power outage event that put the majority of Texan residents in darkness for days. While preparing to avoid such outage events in the future, various tools have been proposed to improve grid reliability, including energy efficiency, demand response, and distributed energy resources. An additional option would be to develop interregional transmission that connects the Texas grid to other national grids. To assess the merits of this idea, we developed a novel, universally-applicable and internationally-relevant framework to study how the Texas grid would evolve alongside access to various interregional ties. This method allows us to stress the synthetic grid structure and analyze how it would respond to the shock of a simulated winter storm event. Our method leverages open-source modeling tools, such as PowerGenome, pyGRETA, and GenX to synthesize unique zonal grid data, construct a consolidated network of model regions, and simulate different developmental pathways of capacity expansion and operational dispatch. We demonstrate our method with an analysis connecting the Electric Reliability Council of Texas (ERCOT), the grid that serves most of Texas, the Western Electricity Coordinating Council (WECC), the grid that serves the western half of the contiguous U.S., and the Eastern Interconnect, the grid that serves the eastern half of the contiguous U.S. Our results indicate that the cost-optimal capacity of interregional transmission connecting the ERCOT grid to other grids lies between 9–13 GW assuming baseline conditions. Building this amount of connecting capacity in one or multiple directions lowers the costs and emissions of development and operation by up to $16 billion and 257 million metric tonnes (MMT) respectively. Additionally, our results show that the interregional connections between ERCOT and other national grids reduce the amount of total load shed required through mild winter storm events. However, our results also show that there is a threshold of very extreme winter storm conditions, spanning multiple service areas, above which the connections exacerbate resource adequacy problems. Therefore, the results indicate that the connections need to be carefully planned alongside the rest of the grid infrastructure to avoid over-reliance on specific resources or technology options.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Wildfire-Power Grid Interactions: Feedback, Impacts, Monitoring, Modeling, and Mitigation Strategies

Wildfires are increasingly interacting with electric power systems through a two-way hazard chain: fires damage grid assets and trigger cascading outages, while grid faults can ignite new fires under hot, dry, and windy conditions. This review synthesizes the state of knowledge across five domains: (i) physical impacts of flames, heat, and smoke on lines, towers, insulators, and substations; (ii) power-infrastructure-initiated ignitions via conductor clash, high-impedance faults, and corona discharge; (iii) widespread blackouts and disproportionate societal impacts; (iv) multi-scale monitoring spanning laboratory tests, in-situ and grid-integrated sensors, and Earth observation; (v) coupled modeling that links fire behavior with grid operations; and (vi) technological and strategic mitigation pathways spanning prevention, response, and recovery. We integrate these domains into a novel 'feedback-aware' socio-technical framework. Through a longitudinal analysis (2005-2025) of global incidents, we identify that while vegetation contact remains the most frequent ignition source, aging infrastructure failure has emerged as a critical driver of catastrophic 'mega-fires'. We further identify persistent gaps, including limited interoperability of high-frequency grid and environmental data, scarce real-time data assimilation, and under-developed equity metrics for outage management. We conclude by outlining a research agenda to (1) deploy interoperable sensing architectures, (2) advance feedback-coupled fire-grid simulations, and (3) evaluate mitigation portfolios through techno-economic and fairness lenses. Recognizing wildfire-grid interactions as coupled socio-technical systems is essential for protecting infrastructure and communities and for ensuring reliable, sustainable electricity in a changing world.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Enhanced Large-Signal Stability Method for Grid-Forming Inverters During Current Limiting: Preprint

Grid-forming (GFM) inverters are a promising technology for the widespread integration of renewable energy sources in future power systems. As a key element of GFM inverter control, the primary controller governs the internal reference voltage and angle. During contingencies in the grid---such as faults, voltage drops, or frequency and phase jumps---an inverter can be forced into a current-limiting mode of operation modulating inverter dynamics, and, as a result, it is prone to losing synchronism with the grid. In this paper, we propose a novel GFM primary control method with an additional synchronization term that naturally activates during contingencies to improve the dynamic response. The method allows the inverter to remain synchronized with the grid, which improves the inverter's dynamic behavior both during and after current-limiting grid conditions and enhances grid support, including voltage support using full current capacity. The method is demonstrated for voltage, frequency, and phase jumps both in a single-machine-to-infinite-bus and a network-wide electromagnetic transient simulation of the IEEE 14-bus system with 5 GFM inverters. The simulations provide insights into the proposed synchronization method and confirm the high potential of the method, which robustly secures synchronism under severe contingencies.

current limiting↗

Correlation Between Weather Alerts and Grid Component Failures for Grid Alert

Weather events cause most grid failures. Often, we even get notifications on our phones to take cover or be prepared for an imminent event. If electric grid utilities had a similar warning that also included probable scenarios and the equipment involved, they could prepare and minimize the effects. Recent research at Idaho National Laboratory into electric grid risk analysis methods resulted in a tool that allows for the development of the most likely scenarios given failure probabilities of grid components. INL has a project with the U.S. Department of Energy’s Cybersecurity, Energy Security, and Emergency Response (CESER) program to develop a Grid Alert application that receives messages from the existing emergency alert system, filters and determines components possibly affected by the emergency event, calculates probable scenarios uses MASTERRI and then notifies the utility if there is significant risk. Historical failure data of elements that comprise the U.S. electric grid have been compiled by utilities and organizations such as the international regulatory body North American Electric Reliability Corporation (NERC). Nominal failure rates are obtained from this data. To make this tool possible, estimated failure rates are needed for different component types given the alert type, severity, and location. Historic weather-related grid element failures are correlated with historic weather events from Integrated Public Alert & Warning System (IPAWS). These correlated events and failures are used along with Bayesian updates from the historical norms to provide a modified failure rate for grid elements in the alert areas and calculate probable scenarios. This discusses the Grid Alert project plan but focuses on the data gathered and process used in determining failure rates for possible grid failure scenarios.

24 - POWER TRANSMISSION AND DISTRIBUTION↗

Existing Methods for Grid Strength Assessment and Role of Hydropower in Future Grids

The power system is undergoing rapid evolution with increasing penetration of inverter-based resources (IBRs), large loads, microgrids, and power electronic devices. Ensuring reliable and stable operation of the modern power grid is a multi-faceted challenge that requires detailed understanding of this complex system. Dynamic stability is a major concern in maintaining the security of power grids as the generation mixes and large loads transitions to include high shares of power electronic devices. The operation of IBRs in regions with low system strength and higher grid impedances has been found to be the main reason behind many of the power system instabilities that manifest themselves in various types of oscillations and interactions that, if not properly addressed and damped, can jeopardize the reliable operation of the power system. Weak grid conditions compound such stability problems, particularly when many IBRs operate in proximity to and connect to weak power grids. Therefore, it is important to assess grid strength for planning, integration and operation of IBRs for a given power system. In this report, we aim to understand and classify existing methodologies for grid strength assessment, along with their limitations and future needs. Further, we aim to utilize the huge untapped potential in utilizing hydro energy resources in addressing some of the pertinent challenges of grid strength and reliable operation of modern power systems. Hydropower, historically valued for its flexibility and dispatchability, now faces new constraints due to reduced share of synchronous machines in the generation mix and seasonal variability of available water resources. Yet, these same plants present untapped potential beyond energy generation - notably, as providers of critical grid services. This report explores how hydropower plants, particularly through operation as synchronous condensers, can play a pivotal role in strengthening the grid amid evolving system dynamics.

13 HYDRO ENERGY↗

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode: Preprint

This paper explores the dispatch-ability of grid-forming (GFM) inverters in grid-connected and islanded mode. Grid-forming (GFM) inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generator (SG)) and follow the change of the load demand. However, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help the grid operator better manage their inverter-based resources (IBRs) for improved operation efficiency and reliability. Therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and SG) to output the target power for both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle of doing so is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, thus, dispatching active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one grid-following inverter and loads in both grid-connected and islanded mode. This pioneering work results in a practical guidance for power system energy management system (EMS) development to control a future grid with GFM and GFL inverters.

droop control↗

Resilience of the Electric Grid Through Trustable IoT-Coordinated Assets

The electricity grid has evolved from a physical system to a cyberphysical system with digital devices that perform measurement, control, communication, computation, and actuation. The increased penetration of distributed energy resources (DERs) including renewable generation, flexible loads, and storage provides extraordinary opportunities for improvements in efficiency and sustainability. However, they can introduce new vulnerabilities in the form of cyberattacks, which can cause significant challenges in ensuring grid resilience. We propose a framework in this paper for achieving grid resilience through suitably coordinated assets including a network of Internet of Things devices. A local electricity market is proposed to identify trustable assets and carry out this coordination. Situational Awareness (SA) of locally available DERs with the ability to inject power or reduce consumption is enabled by the market, together with a monitoring procedure for their trustability and commitment. With this SA, we show that a variety of cyberattacks can be mitigated using local trustable resources without stressing the bulk grid. Multiple demonstrations are carried out using a high-fidelity cosimulation platform, real-time hardware-in-the-loop validation, and a utility-friendly simulator.

distributed energy resources↗

Cost-Benefit Analysis of Grid-Supportive Loads for Fast Frequency Response

Flexibility in inverter-based loads could be used to support the converter-dominated power grid by offering a rapid, autonomous, and adjustable power reserve during system transients to help maintain system stability. Based on technical potential, ancillary service (AS) value, and implementation costs, this study illustrates the cost-benefit analysis of grid-supportive loads (GSLs) for the supply of fast frequency response (FFR). The net benefit for each GSL is demonstrated using a case study and relevant data sources. The findings suggest that implementation costs for enabling GSL features are low compared to the value that grid operators get from the acquisition of responsive reserve services. The authors believe that, given the rising popularity of renewable energy sources, GSLs can be a useful tool for grid stability in low-inertia systems.

cost-benefit analysis↗

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode

This paper explores the dispatchability of grid-forming (GFM) inverters in grid-connected and islanded mode. GFM inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generators) and follow the change in the load demand; however, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help grid operators better manage their inverter-based resources (IBRs) to improve operation efficiency and reliability; therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and synchronous generators) to output the target power in both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, and thus dispatching the active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one GFL inverter, and the load in both grid-connected and islanded mode. This pioneering work results in practical guidance for the development of energy management systems for future electric grids with GFM and GFL inverters.

dispatching↗

Universal Passive Synchronization Method for Grid-Forming Inverters Without Mode Transition

Power systems are transforming with increasing levels of inverter-based resources (IBRs). This transformation requires critical roles of grid-forming (GFM) inverters replacing synchronous generators for bulk power system stabilization and ancillary services, also allowing flexible power system operation, such as microgrid that is operated by multiple GFM IBRs to achieve system resilience against contingencies. To realize the resilient power systems allowing flexible in-and-out operation of GFM IBRs potentially programmed with different primary controls, a synchronization method universally applicable, i.e., independent of control types, would be beneficial to ease the integration process, but it has not been actively studied. To fill the gap, this paper proposes a universal synchronization method that achieves a passive synchronization to enable a smooth transition in a grid with off-nominal system parameters, i.e., voltage and frequency. The logic proposed requires no modification on the primary control, thus applicable to any type of GFMs with a voltage reference input. To validate the concept, a simulation of an IEEE 13-bus benchmark system modified with 3 GFM inverters is presented. It simulates an inverter-driven black start scenario in which GFM inverters autonomously turn on and connect to the grid under heavy loading, using the synchronization logic. The case study demonstrates that GFM inverters can tune their voltage reference to smoothly synchronize without severe transients, and contribute to a seamless black start of the grid under unbalanced load conditions. Two GFM methods - Droop and dispatchable virtual oscillator control - are used for the demo to validate feasibility and interoperability of the passive synchronization.

black start↗

A State-Space Model for Stability Boundary Analysis of Grid-Following Voltage Source Converters Considering Grid Conditions

With the growing significance of renewable energy resources and energy storage systems, the number of grid-connected inverters has been rising at an increasingly rapid pace. Generally, these inverters are directly integrated with the distribution network by synchronizing with the grid voltage at the point of common coupling. However, the low grid strength and varying R/X ratios, as the common characteristics of most distribution networks or weak grids, can lead to dynamic interactions that comprise stability and limit the power transfer capacity of grid-connected inverters. To ensure stable operation of the inverters, researchers must determine the stability boundary, described as the maximum power transfer capacity of grid-connected inverters under the premise of maintaining system small-signal stability. For this purpose, we propose to formulate a state-space model of the system in the synchronously rotating dq-frame of reference and perform eigenvalue analysis to determine the stability boundary. With a detailed model of the control structure and parameters of the grid-connected inverters, the stability boundary is identified as a surface with respect to different grid strengths and R/X ratios. Case study results of proposed eigenvalue analysis are compared with those of admittance model-based stability analysis as well as time-domain simulation using a switching model in Matlab/Simulink, validating the effectiveness and accuracy of the proposed eigenvalue analysis for stability boundary identification.

grid-connected inverters↗

Frequency Stability Enhancement in a Fully Solar Power Grid: A Case Study on the Saudi Model

Recently, renewable energy sources (RES) such as solar photovoltaic (PV) have been recognized for their significant potential. Several studies have explored the issue of frequency stability with high RES penetration. A significant observation related to this issue is the decline in the weighted short circuit ratio (WSCR), which has the potential to adversely affect system stability. This research uniquely focuses on the gradual transition of the Saudi Electricity Company (SEC) system to a fully integrated solar PV grid, offering insight and methodology that can be adapted for other power systems. While a variety of mitigation methods are available, synchronous condensers (SC) were used in this study to stabilize grid frequency, and their implementation has been shown to improve the overall performance of the system. In response to the observed decline in WSCR, a comprehensive short circuit analysis was applied across all regions in the Saudi power grid model to evaluate the reduction in short circuit power and highlight areas requiring enhancement. Finally, scenarios illustrating frequency response with a gradual increase in SCR were analyzed, with the objective of establishing a stable, fully solar PV power system that is resilient to sudden power grid disturbances.

14 SOLAR ENERGY↗