Search NASA⌕ Search

SEARCH · Search NASA

Results for “dispatch GFM inverter”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode

This paper explores the dispatchability of grid-forming (GFM) inverters in grid-connected and islanded mode. An innovative concept of dispatching GFM sources (inverters and synchronous generators) is proposed to output the target power by adjusting their droop intercepts. The fundamental principle is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, and thus dispatching the active and reactive power of a GFM inverter can be achieved through dispatching its frequency and voltage. The concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one GFL inverter, and the load in both grid-connected and islanded mode. This pioneering work results in practical guidance for the development of energy management systems for future electric grids with GFM and GFL inverters. The key findings are summarized as follows: 1) The GFM inverters can be dispatched through frequency and voltage droop intercepts to output the target power; 2) The dispatch rule for grid-connected and islanded mode is slightly different.

dispatch GFM inverter↗

Droop Control-Based Dispatch of an Islanded Microgrid with Multiple Grid-Forming Sources

Before rotating, fossil fuel-based, synchronous generators (SGs) are phased out, in line with renewable generation goals, grid-forming (GFM) inverters are expected to parallel SGs. Primary droop control allows GFM inverters to share power without communication; however, it is necessary to dispatch GFM inverters and/or SGs with the desired output power for better energy management (e.g., one GFM inverter needs to charge the battery due to a low state of charge). Therefore, this paper develops an analytic approach to dispatching GFM inverters and SGs with the desired output power by shifting the droop intercept up/down while maintaining the same frequency operating point for improved transient stability. This concept is demonstrated through a pure hardware setup with two off-the-shelf inverters and one diesel generator under an islanded microgrid, and we provide insight on the real-world implementation of the proposed concept.

droop control↗

Droop Control-Based Dispatch of an Islanded Microgrid With Multiple Grid-Forming Sources

Before rotating, fossil fuel-based, synchronous generators (SGs) are phased out, in line with renewable generation goals, grid-forming (GFM) inverters are expected to parallel SGs. Primary droop control allows GFM inverters to share power without communication; however, it is necessary to dispatch GFM inverters and/or SGs with the desired output power for better energy management (e.g., one GFM inverter needs to charge the battery due to a low state of charge). Therefore, this paper develops an analytic approach to dispatching GFM inverters and SGs with the desired output power by shifting the droop intercept up/down while maintaining the same frequency operating point for improved transient stability. This concept is demonstrated through a pure hardware setup with two off-the-shelf inverters and one diesel generator under an islanded microgrid, and we provide insight on the real-world implementation of the proposed concept.

droop control↗

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode

This paper explores the dispatchability of grid-forming (GFM) inverters in grid-connected and islanded mode. GFM inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generators) and follow the change in the load demand; however, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help grid operators better manage their inverter-based resources (IBRs) to improve operation efficiency and reliability; therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and synchronous generators) to output the target power in both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, and thus dispatching the active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one GFL inverter, and the load in both grid-connected and islanded mode. This pioneering work results in practical guidance for the development of energy management systems for future electric grids with GFM and GFL inverters.

dispatching↗

Droop Control-Based Dispatch of an Islanded Microgrid with Multiple Grid-Forming Sources: Preprint

Before rotating fossil-fuel based synchronous generators (SGs) are phased out in line with renewable goals, grid-forming (GFM) inverters are expected to parallel with SGs. Primary droop control allows them share power without communication, however, it is necessary to dispatch GFM inverters and/or SG with desired output power for better energy management (e.g., one GFM inverter needs to charge the battery due to low state-of-the charge). Therefore, this paper develops analytic approach to dispatch GFM inverters and SG with desired output power by shifting the droop intercept up/down while maintain the same frequency operating point for improved transient stability. This concept is demonstrated through pure hardware setup with two off-the-shelf inverters and one diesel generator under islanded microgrid, and we also provide insight on real-world implementation of the proposed concept.

droop control↗

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode: Preprint

This paper explores the dispatch-ability of grid-forming (GFM) inverters in grid-connected and islanded mode. Grid-forming (GFM) inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generator (SG)) and follow the change of the load demand. However, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help the grid operator better manage their inverter-based resources (IBRs) for improved operation efficiency and reliability. Therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and SG) to output the target power for both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle of doing so is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, thus, dispatching active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one grid-following inverter and loads in both grid-connected and islanded mode. This pioneering work results in a practical guidance for power system energy management system (EMS) development to control a future grid with GFM and GFL inverters.

droop control↗

Performance Evaluation of Multi-Vendor Grid-Forming Inverters for Grid-Connected Operation Through Hardware Experimentation

This paper presents the functional performance evaluation tests of multiple (three) commercial grid-forming (GFM) inverters when they operate in parallel with the grid through hardware experiments. The goal of these tests is to explore and benchmark the GFM inverters' functionalities and dynamic response when they are operated in parallel with power grids. Both steady-state (changing the inverter's frequency and voltage droop) and transient (adding step changes to grid's frequency/voltage) tests are performed for each GFM inverter with the same testing circuit and testing protocol. The key findings are summarized as follows: 1) The GFM inverters can be dispatched through frequency and voltage droop intercepts to output the target power; and 1) the GFM inverters automatically respond to system frequency and voltage events to output the needed power; 3) all the GFM inviters shows stability issues when absorbing reactive power from the grid.

frequency droop↗

Performance Evaluation of Multi-Vendor Grid-Forming Inverters for Grid-Connected Operation Through Hardware Experimentation: Preprint

Existing real-world projects of GFM inverters that operate in parallel to power grids typically are sized between dozens and a few hundreds Megawatt (MW) scale according to a recent NERC GFM inverter white paper. These large systems are often difficult to evaluate prior to deployments because of their large size. The performance of smaller GFM inverters (dozens to a few hundreds MW) that operate parallel with power grids (distribution systems) is even less understood. There is an opportunity to better understand these systems through hardware testing under controlled laboratory conditions. Therefore, this paper presents the functional performance evaluation tests of multiple (three) commercial GFM inverters when they operate in parallel with the grid through hardware experiments. The goal of these tests is to explore the GFM inverters' functionalities and dynamic response when in parallel with power grids to eventually develop universal specifications for GFM inverters. Both steady state (changing the inverter's frequency and voltage droop) and transient (adding step change in grid's frequency/voltage) tests are performed for each GFM inverter with the same testing circuit and testing protocol. The experimental results indicate the bench-marked performance that: 1) the GFM inverters can be dispatched through frequency and voltage droop intercepts to output the target power when paralleled to the grid; 2) the GFM inverters automatically respond to system frequency and voltage events to output the needed power, however, the GFM inverters all show stability issues when absorbing reactive power from the grid.

grid-forming inverters↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters

This paper investigates operational techniques to achieve seamless (smooth) microgrid (MG) transitions by dispatching a grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control modes during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worth exploring how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. The results show that the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires that the GFM inverter(s) maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-forming control↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters

This paper investigates operational techniques to achieve seamless (smooth) microgrid (MG) transitions by dispatching a grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control modes during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worth exploring how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. The results show that the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires that the GFM inverter(s) maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-forming↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters: Preprint

This paper investigates operational techniques to achieve smooth microgrid (MG) transitions by dispatching the grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control mode during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worthy to explore how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. As expected, the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires the GFM inverter(s) to maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-following control↗

Autonomous Microgrid Restoration Using Grid-Forming Inverters and Smart Circuit Breakers

The proliferation of distributed inverter-based resources (IBRs) raises the questions if these IBRs can be used to blackstart microgrids and distribution feeders after major outages. In this paper, we propose and evaluate an autonomous microgrid restoration concept using grid-forming (GFM) IBRs and smart circuit creakers (SCBs). The concept is first explored in simulation platform and then a hardware testbed containing actual GFM inverters is developed to demonstrate these functionalities. A combination of dispatchable virtual oscillator control (dVOC) and droop-based control schemes have been designed for GFM inverter controls in the software simulations and hardware testbed. Subsequently, operation of SCBs using two distinct principles have been demonstrated that can restore or connect portions of the network.

black start↗

Autonomous Microgrid Restoration Using Grid-Forming Inverters and Smart Circuit Breakers: Preprint

The proliferation of distributed inverter-based resources (IBRs) raises the questions if these IBRs can be used to blackstart microgrids and distribution feeders after major outages. In this paper, we propose and evaluate an autonomous microgrid restoration concept using grid-forming (GFM) IBRs and smart circuit creakers (SCBs). The concept is first explored in simulation platform and then a hardware testbed containing actual GFM inverters is developed to demonstrate these functionalities. A combination of dispatchable virtual oscillator control (dVOC) and droop-based control schemes have been designed for GFM inverter controls in the software simulations and hardware testbed. Subsequently, operation of SCBs using two distinct principles have been demonstrated that can restore or connect portions of the network.

grid reconfiguration↗

UNIFI 1-MW Multi-Vendor Grid-Forming Inverter Test Updates

This presentation gives an update on UNIFI 1MW multi-vendor GFM inverter testing. The 1MW demo enters the last stage of the test, which is the integration test. And the main objectives of the integration tests include: 1) explore the interoperability of dispatching a future grid with energy mix (GFM inverters, GFL inverters and synchronous machine). The presentation highlights one example test, ROCOF, and summarizes all the key learning.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Decentralized Distribution System Restoration with Grid-Forming/Following Inverter-Based Resources

The high penetration of distributed energy resources (DERs) in active distribution systems has posed challenges to the centralized distribution system restoration (DSR) strategies in current practice. On the other hand, the advancement in smart inverter technologies enables the bottom-up restoration capability. This paper is motivated to develop a 3-layered hierarchical framework for decentralized DSR, based on the grid-forming (GFM) and grid-following (GFL) grid-edge inverters. The first layer presents the tertiary control, which determines the load pickup schedule and generation dispatch of DERs, using the alternating direction method of the multipliers algorithm. The second layer consists of two control functions: GFM control, which regulates voltage and frequency, establishing a stable grid for GFL inverters to follow; and GFL control, which regulates the real and reactive power. In the third layer, the primary control is proposed to regulate the inverter voltage and current, which is developed based on the virtual oscillator control (VOC). Furthermore, the developed framework is tested in the modified IEEE 13-node test feeder. Two scenarios of grid-connected and islanded operating modes are designed, and simulation results demonstrate the effectiveness of decentralized DSR strategies for controlling grid-edge inverters to enhance the distribution system resilience.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Controller Hardware-in-the-Loop Evaluation of a Microgrid Controller for a Microgrid System with Multiple Grid-Forming Inverters

This paper presents the laboratory evaluation of a commercial Microgrid Management System (MGMS) implemented in the real-world Bronzeville Microgrid which features a futuristic scenario with high renewable energy integration and the use of multiple Grid-Forming (GFM) inverters. The primary objective of the performance evaluation for the MGMS is to assess the MGMS's capability to dispatch GFM units, including a GFM PV unit and two GFM battery units, to maintain the system stability and ensure economic operation, thus guaranteeing the microgrid's resilience during prolonged outages and dynamic events. The laboratory controller hardware-in-the-loop provides realistic testing environment through detailed electromagnetic transient modeling of the microgrid system, hardware MGMS, and standard communication protocols (DNP3). The CHIL evaluation shows how the MGMS effectively manages the GFM inverters, highlighting its performance in maintaining stability, reliability, and survivability in a microgrid environment with a high penetration of renewable energy sources.

controller hardware-in-the-loop↗

Controller Hardware-in-the-Loop Evaluation of a Microgrid Controller for a Microgrid System with Multiple Grid-Forming Inverters: Preprint

This paper presents the laboratory evaluation of a commercial Microgrid Management System (MGMS) implemented in the real-world Bronzeville Microgrid which features a futuristic scenario with high renewable energy integration and the use of multiple Grid-Forming (GFM) inverters. The primary objective of the performance evaluation for the MGMS is to assess the MGMS's capability to dispatch GFM units, including a GFM PV unit and two GFM battery units, to maintain the system stability and ensure economic operation, thus guaranteeing the microgrid's resilience during prolonged outages and dynamic events. The laboratory controller hardware-in-the-loop provides realistic testing environment through detailed electromagnetic transient modeling of the microgrid system, hardware MGMS, and standard communication protocols (DNP3). The CHIL evaluation shows how the MGMS effectively manages the GFM inverters, highlighting its performance in maintaining stability, reliability, and survivability in a microgrid environment with a high penetration of renewable energy sources.

controller hardware-in-the-loop↗

Controller-Hardware-in-the-Loop Evaluation of a Microgrid Controller for a Microgrid System With Multiple Grid-Forming Inverters

This paper presents the laboratory evaluation of a commercial Microgrid Management System (MGMS) implemented in the real-world Bronzeville Microgrid which features a futuristic scenario with high renewable energy integration and the use of multiple Grid-Forming (GFM) inverters. The primary objective of the performance evaluation for the MGMS is to assess the MGMS's capability to dispatch GFM units, including a GFM PV unit and two GFM battery units, to maintain the system stability and ensure economic operation, thus guaranteeing the microgrid's resilience during prolonged outages and dynamic events. The laboratory controller hardware-in-the-loop provides realistic testing environment through detailed electromagnetic transient modeling of the microgrid system, hardware MGMS, and standard communication protocols (DNP3). This CHIL evaluation shows how the MGMS effectively manages the GFM inverters, highlighting its performance in maintaining stability, reliability, and survivability in a microgrid environment with a high penetration of renewable energy sources.

controller hardware-in-the-loop↗