Frequency Scans for GFM Performance Verification
This document presents different methods for frequency scan testing of grid-forming resources.
SEARCH · Search NASA
Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.
Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.
This document presents different methods for frequency scan testing of grid-forming resources.
This presentation shows how frequency scan tests of inverter-based resources can be used to define specifications for grid-forming (GFM) control.
Current industry practices for quantifying the system strength contribution from grid-forming (GFM) resources to ensure stability of power systems dominated by inverter-based resources (IBRs) are primarily based on iterative electromagnetic transient (EMT) time-domain simulation studies. While feasible, these approaches are resource-intensive, lack scalability and intuition, and might not evaluate the system strength contribution over the entire frequency range of interest. This paper introduces a novel, frequency-domain approach to quantify system strength support provided by a GFM resource using frequency scans. The proposed method uses transfer functions from the grid voltage magnitude (V) and phase (?), respectively, to the reactive (Q) and active power (P) output of a GFM resource for quantifying its contribution to system strength. These transfer functions provide a direct measure of the ability of a GFM resource to behave as a stiff voltage source behind a reactance over a specified frequency range, enabling robust quantification of its system strength contribution. The key innovation of this work is the development of a frequency domain system strength metric called the dynamic short-circuit ratio (dSCR) that is suitable for IBR-dominated power systems and is directly related with the familiar short circuit ratio (SCR) metric. The new metric, dSCR, enables the assessment of system strength contributions from both synchronous machines and converter-based GFM resources using a unified benchmark, which is not possible with the traditional SCR metric. The paper also demonstrates how impedance scans could identify if an unstable condition observed during weak grid conditions is a result of the lack active or reactive power support or both. By leveraging the proposed frequency-domain dSCR metric for quantifying system strength contribution from GFM IBRs, the paper demonstrates targeted mitigation strategies for weak grid instabilities without resorting to repeated, time-consuming time-domain simulations. The result is a scalable and efficient approach to remediate stability challenges in power systems with high shares of IBRs and accelerating the integration of GFM technologies for system strength support in power systems.
Abstract Galactic dark matter may consist of axionlike particles (ALPs) that can be described as an “ultralight bosonic field” oscillating at the ALP Compton frequency. The ALP field can be searched for using nuclear magnetic resonance (NMR), where resonant precession of spins of a polarized sample can be sensitively detected. The ALP mass to which the experiment is sensitive is scanned by sweeping the bias magnetic field. The scanning either results in detection of ALP dark matter or rules out ALP dark matter with sufficiently strong couplings to nuclear spins over the range of ALP masses corresponding to the covered span of Larmor frequencies. In this work, scanning strategies are analyzed with the goal of optimizing the parameter‐space coverage via a proper choice of experimental parameters (e.g., the effective transverse relaxation time).
This paper presents a testing framework for grid-forming (GFM) resources. First, it analytically derives in the frequency domain the active and reactive power response of an ideal voltage source with a reactor. These transfer functions are then used to quantify the voltage source behavior expected from a GFM inverter within subtransient timescales (5-15 cycles) following a grid disturbance. The paper also shows that the testing of a GFM inverter might require a reactor of an appropriate size between the inverter and the grid simulator used for the inverter testing. Finally, the paper presents a systematic approach for developing specifications for GFM resources using active and reactive power response frequency scans. The testing framework and results presented in this paper are demonstrated using EMT-PSCAD simulations of a 1-MW GFM inverter.
The power grid industry is pushing for electromagnetic transient (EMT)-based studies for generation interconnection and planning process due to high penetrations of inverter-based resource (IBRs). Vendor-specific and site-specific black-box IBR models are preferred in those simulation studies. For small-signal analysis, measurement-based admittance models are necessary. In this paper, we demonstrate the extraction of frequency-domain dq frame IBR models. These linear models are specific to operating conditions. We demonstrate two extraction methods: frequency scan and a step response-based method. The latter relies on converting time-domain responses to Laplace-domain expressions via eigensystem realization analysis (ERA). Both can lead to dq admittance representation and the latter is time saving.
The power grid industry is pushing for electro-magnetic transient (EMT)-based studies for generation interconnection and planning process due to high penetrations of inverter-based resource (IBRs). Vendor-specific and site-specific black-box IBR models are preferred in those simulation studies. For small-signal analysis, measurement-based admittance models are necessary. In this paper, we demonstrate the extraction of frequency-domain dq frame IBR models. These linear models are specific to operating conditions. We demonstrate two extraction methods: frequency scan and a step response-based method. The latter relies on converting time-domain responses to Laplace-domain expressions via eigensystem realization analysis (ERA). Both can lead to dq admittance representation and the latter is time saving.
This dataset contains high-frequency vertical velocity recorded by fixed-point vertical scans done by the UC Davis Halo Streamline scanning lidar. The quality control is performed according to the algorithm of Goring & Nikora (2002).
The U.S. Department of Energy (DOE) Atmospheric Radiation Measurement (ARM) user facility is dedicated to delivering high-quality radar data that significantly advance our understanding of cloud and precipitation processes, improving climate models. With radars operating across diverse frequencies, scanning modes, and global climate conditions, extensive staffing is essential for effective management. Due to current staffing constraints, achieving the expected level of operational excellence requires a more strategic approach. To address this challenge, ARM has developed an operational radar plan for the upcoming Fiscal Year 2025 (FY25) based on budget and staffing considerations.
The U.S. Department of Energy (DOE) Atmospheric Radiation Measurement (ARM) user facility is dedicated to delivering high-quality radar data that significantly advance our understanding of cloud and precipitation processes, improving climate models. With radars operating across diverse frequencies, scanning modes, and global climate conditions, extensive staffing is essential for effective management. Due to current staffing constraints, achieving the expected level of operational excellence requires a more strategic approach. To address this challenge, ARM has developed an operational radar plan for the upcoming Fiscal Year 2025 (FY25) based on budget and staffing considerations. This report summarizes the Fiscal Year 2024 (FY24) ARM radar-related activities and outlines the strategic plan for FY25. It presents a comprehensive radar plan that includes detailed activities, priorities, and a projected timeline aligned with the ARM radar roadmap. Key tasks, detailed in Table 1, cover various radar operational stages and coordinated efforts among ARM teams.
This paper presents results and new insights gained from a hardware test campaign on a 2 MVA PV inverter for validating its vendor-supplied EMT model. The test campaign was conducted using a 7 MVA grid simulator and a 2 MW PV emulator. It considered both time-domain transient tests and frequency-domain impedance scan tests. The paper highlights the inadequacy of transient tests in capturing all critical resonance modes of the inverter, and the effectiveness of the frequency scan testing in addressing this problem. The paper shows the frequency scan testing as an effective tool for EMT model validation of IBR units which can highlight inaccuracies in the EMT models that are easy to overlook when model validation is performed using only the time-domain transient tests such as voltage ride-through and phase jump tests.
This dataset contains wind profiles retrieved from 6-beam Velocity Azimuth Display (VAD) scans done by a Streamline XR Doppler Lidar operated by Lawrence Livermore National Laboratory and deployed at the Tree Tops site (1.5 km South-West of MLBS site). The wind components (expressed as zonal, meridional and vertical) are retrieved through the algorithm of Paschke et al. (2015). The quality control of the radial wind speed is performed following the algorithm of Foken et al. (2004).
This dataset contains wind profiles retrieved from 6-beam Velocity Azimuth Display (VAD) scans done by a Streamline XR Doppler Lidar operated by the University of Virginia and deployed at the MLBS site. The wind components (expressed as zonal, meridional and vertical) are retrieved through the algorithm of Paschke et al. (2015). The quality control of the radial wind speed is performed following the algorithm of Foken et al. (2004).
Continuous Wave Laser Beam (LB) melting offers control over the localised heating and cooling of melt pools for welding, brazing, additive manufacturing and solidification. Research into laserliquid metal interactions has primarily focused on the heat and mass transport under large thermal gradients imposed by the localised melting conditions. Recent commercial availability of blue (450 nm) wavelength lasers has enabled the printing of material with poor IR (1064) nm attenuation like Cu. However, little research has been conducted into varying input laser frequency and scan rate at fixed absorption to understand the effects of laser light on surface oxide formation and the underlying liquid metal thermodynamic response. Here, this article conducts laser melting of 304L under Blue (450 nm) and Infrared (IR, 1064 nm) laser frequencies and examines their impact on laser oxide thickness, chemistry and coloration. We find that laser frequencies induce changes in the oxide layer thickness and chemistry that cannot be explained using conventional thermal absorption shifts and fluid dynamics. We suggest that light coupling may have thermodynamic implications for the chemical potential of the liquid metal, which may drive the observed phase behaviour. Identifying mechanisms for the tuning of the chemical potential via laser frequency control could enable the ability to control solidification microstructure and atomic ordering in laser welding and additive manufacturing processes.
The Horn Location Sensor (HLS) system—named for the magnetic focusing horns it monitors, along with other critical beamline elements – is a high-precision alignment system developed for the Long-Baseline Neutrino Facility (LBNF) to support the Deep Underground Neutrino Experiment (DUNE). With minimal maintenance, the HLS can operate reliably in environments with high radiation, and it ensures that key components such as the protective baffle, focusing horns, and beam position monitors are aligned correctly – each essential for maintaining one of the world’s most intense muon-neutrino beams. A high-precision hydrostatic level sensor, a linear variable differential transformer, and INVAR rods are all used in the system to monitor vertical motion and tilt with sub-millimeter accuracy. A novel Sweep Tracker interferometer enhances calibration fidelity by correcting for non-linearities in laser wavelength and scan rate in real time. A critical part of DUNE’s precision alignment and flux prediction requirements, the HLS system initially supports beam power of up to 1.2 MW and can be upgraded to 2.4 MW.
This dataset contains wind profiles retrieved from 6-beam Velocity Azimuth Display (VAD) scans done by the UC Davis scanning Lidar. The wind components (expressed as zonal, meridional and vertical) are retrieved through the algorithm of Paschke et al. (2015). The quality control of the radial wind speed is performed following the algorithm of Goring & Nikora (2002).
A search for cosmological axions has been performed by scanning a frequency region of 38 MHz centered at about 10.2 GHz, corresponding to an axion mass 𝑚 𝑎 ≃ 42 μ eV. The QUAX experimental apparatus, a haloscope comprised of a 1-liter volume tunable cavity immersed in an 8 T magnetic field and a quantum-limited detection chain, set limits on the axion-photon coupling at the 10 −14 GeV −1 level. As no signal candidate has been observed, viable hadronic axion models are ruled out in a currently preferred postinflationary region 𝑚 𝑎 > 40 μ eV.
The "data collection" basically involves setting up the thermal wave frequency, laser scan distance, and other parameters related to the experimental setup. The modification of this code is minor and the details of this code can be found in the earlier patent ("thermal conductivity microscope"). The "data analysis" instead, replaces the simplified analytical model by a more complete analytical model, and used a "thermoquadruple" method to solve the analytical model. The efficiency is orders of magnitude improved and the accuracy is also better. Meanwhile, the previous model can only handle a two-layer sample structure. The new, complete model can handle materials with multiple layers (any given number), which is necessary to handle post ion irradiated materials.