Search NASA⌕ Search

SEARCH · Search NASA

Results for “high efficiency dehumidification system”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Laboratory Testing and Performance Characterization of the High Efficiency Dehumidification System (HEDS) Technology

The high efficiency dehumidification system (HEDS) is a unique air handling unit (AHU) design with two water coils. Connected in series, these water coils can sensibly reheat the airstream after it is cooled and dehumidified, thereby mitigating (or sometimes eliminating) the need for conventional sensible reheat with additional energy from hot water, electric resistance or steam coils. Another unique design feature is the size of the HEDS primary cooling coil. While typical AHU cooling coils have a 6-row geometry, the HED's cooling coil has a deeper 10-row geometry enabling discharge air dew point temperatures at or below 55 degrees F despite warmer chilled water supply temperatures approaching (sometimes exceeding) 50 degrees F. The ability to meet acceptable discharge air dew points with warmer chilled water supply temperatures improves both operational efficiency and system resilience against chilled water plant operational or control issues. This report summarizes the 59 steady-state test results that form a comprehensive performance map of the HEDS technology including its reheat capability. The breadth of outdoor air conditions and flow rates over which the HEDS technology was tested and characterized encompasses the unit 1) operating as a dedicated outdoor air system or mixed air system and 2) controlled with constant air volume or variable air volume fan control.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Field Evaluation of the High Efficiency Dehumidification System (HEDS) at the Timken Museum of Art - Measurement and Verification (M&V) Results from Summer, Winter and Spring Evaluation Periods

The High Efficiency Dehumidification System (HEDS) technology from Conservant Systems Inc., installed at the Timken Museum of Art in San Diego, California, was evaluated to determine its performance relative to appropriate baseline operation. Data was collected for measurement and verification for several weeks during three evaluation periods: Summer (Aug-Sep 2023), Winter (Dec 2023-Feb 2024) and Spring (May-Jun 2024). The evaluation included operating the heating, ventilation and air conditioning (HVAC) system in both constant air volume (CAV) and variable air volume (VAV) modes, with and without the HEDS energy recovery and HVAC system optimization technology enabled. The electricity consumption of the chiller and the gas-supplied reheat energy were measured to characterize savings achieved by the HEDS operation. Based on these measurements, the HEDS was responsible for chiller electrical load savings during the summer evaluation period of 39% and 42% for the CAV and VAV operating modes, respectively; 97% and 100% chiller electrical load reductions were observed during the winter evaluation for the CAV and VAV operating modes, respectively; and the corresponding reductions during the spring evaluation were 42% and 52% for CAV and VAV operation, respectively. The measured reheat energy reductions, which are typically provided by natural gas, due to the HEDS during summer were 64% and 97% in CAV and VAV operating modes, respectively, while the corresponding values were 99% and 78% during the winter evaluation, and 59% and 56% during the spring evaluation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Field Evaluation of the High Efficiency Dehumidification System (HEDS) at the Timken Museum of Art - Summary of Measurement and Verification (M&V) Results from Summer 2023

The National Renewable Energy Laboratory (NREL) is performing a measurement and verification (M&V) assessment of the Conservant High Efficiency Dehumidification System (HEDS) at the Timken Museum of Art in San Diego, California. The HEDS was selected for evaluation by the U.S. Department of Energy (DOE) High Impact Technology Catalyst (HIT) evaluation program in 2022. This report documents recently completed analysis of data collected as an initial assessment of the HEDS system performance. Data was collected for the summer M&V during several weeks in August and September 2023 while operating the Timken Museum's HVAC system in several operating modes.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

The Levelized Cost of Exergy Framework

Exergy is the amount of energy within a substance or within a transfer of energy that can be used to produce work or some other useful output when interacting with some reference environment. Two different energy systems that produce the same output with the same exergetic efficiency must necessarily have the same amount of exergy input, even if the amount of energy input to the two systems is vastly different. For example, a low-grade heat-driven desalination would require far more energy input than a reverse osmosis (RO) plant producing the same amount of water, but if their exergetic efficiencies were the same, they would require the same amount of exergy input. Thus, comparisons between different energy sources on the basis of energy is not always appropriate. Instead, a comparison on a per unit exergy basis provides more insight on the cost-effectiveness of different energy sources and systems. In this presentation, we describe a framework for analyzing the levelized cost of exergy (LCOEx) for both inputs and outputs of various energy systems. Our framework illustrates how the cost per unit exergy of a system's energy source, as well as the exergetic efficiency of the system, greatly affect the cost of the system output. We use the levelized cost of electricity as a benchmark value for LCOEx, due to electricity's ubiquity as an energy source, and because it is relatively inexpensive on a per unit exergy basis. The LCOEx of various heat sources are then compared to the LCOEx of electricity. Medium- and high-grade industrial heat (> 150 degrees C) produced by natural gas tends to have an LCOEx on par with electricity. This is due to the low cost of natural gas, as well as the high exergy content of heat at higher temperatures. Meanwhile, low-grade heat tends to be an expensive exergy source, owing to the low exergy content of the low-grade heat. We first apply our framework to desalination, where RO has come to dominate, due to the low LCOEx of the energy source (electricity) and relatively high exergetic efficiency of RO compared to thermal desalination systems. We then use this framework to highlight an opportunity for dehumidification systems to experience a similar cost improvement as desalination has. If an electrically-driven, high exergetic efficiency dehumidification system were developed (such as the membrane-based dehumidification systems proposed in literature), it would use a low cost exergy source with a high exergetic efficiency and could potentially lower the cost of dehumidification in the way that RO has done for desalination. Finally, we apply our framework to various fuels (natural gas, hydrogen, gasoline, etc.) and energy systems across different sectors (desalination, dehumidification, vehicles, etc.) to understand the variation in the cost of exergy input and exergetic efficiency of different systems and technologies.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Review of liquid desiccant air dehumidification systems coupled with heat pump: System configurations, component design, and performance

Vapor Compression Systems (VCS) are the most common air conditioning technology. VCS cool the air to its dew point temperature (overcooling) to remove water vapor in the air through condensation and then reheats the air back to the comfort temperature for direct use. The VCS process is inefficient due to overcooling and reheating. Liquid Desiccant Dehumidification (LDD) is a potentially energy-efficient air conditioning. LDD removes water vapor in the process air using liquid desiccant’s high-water affinity. It hybrids with sensible cooling to control temperature and humidity separately. The LD in the LDD becomes weak after dehumidification. The LDD needs additional heating to regenerate the weak Liquid Desiccant (LD) to a high concentration for dehumidification. Earlier versions of the LDD systems use highly concentrated liquid desiccant (large water removal capability) to dehumidify the air by only dealing with latent load. It leads to highly elevated temperatures above 60 °C of heat sources (combustion or electric resistance-based heating) for regeneration. The energy needed for the elevated temperature heat resource significantly reduces or demolishes the benefit of LDD systems. In the recent two decades, researchers have investigated a new configured LDD system that couples an LDD with a heat pump at both dehumidification and regeneration sides for better efficiency. The heat pump provides cooling (from the evaporator) for both dehumidification and sensible cooling and simultaneous heating from the condenser for regeneration. The highly integrated system (HP-LDD) with improved efficiency enables the LDD to operate at lower concentrations and temperatures in dehumidification and regeneration. This paper depicts the working principle behind HP-LDD and its heating and cooling requirements. It reviews the comparison between the HP-LDD systems and the conventional LDD systems regarding system configurations, component design, energy efficiency, and dehumidification performance characteristics. The main findings from the review include the preferred use of packed bed over membrane-based dehumidifiers, the use of internally cooled dehumidifiers enabled by the HP cooling capacity, the high dispersion of HP operation conditions, and the dependence of dehumidification performance on various dehumidifiers. Finally, an outlook for future research on HP-LDD strategies is presented based on the reviewed works and their limitations.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Performance Analysis and Limiting Parameters of Cross-flow Membrane-based Liquid-desiccant Air Dehumidifiers

We report that to dehumidify a humid air stream, existing air conditioning (AC) systems substantially overcool the outdoor humid air below its dew point, thereby significantly reducing energy efficiency. Directly capturing humidity, membrane-based liquid-desiccant dehumidification systems separate sensible and latent cooling (SSLC) loads and thus offer a promising pathway for a high-performance AC solution. Design of an energy-efficient SSLC-AC system, however, rests largely on detailed understating of the dehumidification process. While some studies have identified the dehumidification process mainly depends on membrane characteristics, other studies have argued that the process is limited by desiccant liquid or alternatively air thermo-hydraulic physics for typical humid climate conditions. The present study examines performance and physics of the membrane-based liquid-desiccant dehumidification process over a wide range of climate conditions through a novel 3D, two-phase, multi-species CFD model. Decoupling the thermodynamic and hydraulic effects, the study reveals that the dehumidification rate is a linear function of the water vapor pressure potential ($J=α ΔP$) summarizing the system's thermodynamic state. The slope of the curve (i.e., α) depends on hydraulic transport characteristics of the membrane pores, air stream, and desiccant solution. More importantly, it was found that the air dehumidification process is mainly limited by the air-side transport physics for thin liquid-desiccant films and commonly used porous superhydrophobic membranes. Additionally, results show that, depending on ambient/desiccant conditions and physical dehumidifier characteristics, energy effectiveness and dehumidification rate vary from 13 to 34% and from 0.13 to 1.4 g m -2 s -1 , respectively. Therefore, the present study allows to efficiently design future SSLC-based AC systems exhibiting high performance energy metrics.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Membrane-based Ionic Liquid Absorption System for Ultra-Efficient Dehumidification and Heating

The project team – comprising the University of Florida (UF), GTI Energy, and Modine Manufacturing – sought to develop a highly efficient heat-powered absorption cycle with combined dehumidification and heat pumping. This DOE-supported project advanced the technology from a TRL of 3 to 6, culminating in the development of a 1,000 CFM system. Key innovations implemented in the system addressed the low efficiency, size, cost, and reliability challenges of conventional absorption cycles. Specifically, the system was enabled by: (1) a semi-open cycle that allowed simultaneous dehumidification and heat recovery, (2) non-crystallizing ionic liquids (ILs) that enabled “double-effect” operation at elevated temperatures without the need for costly control equipment, (3) a compact membrane-based absorber that confined the IL and directly cooled it to achieve low dew points, and (4) a novel, highly integrated desorber–condenser assembly that reduced size, weight, and cost. The technology was developed with commercial HVAC applications in mind, particularly for separate sensible and latent cooling (SSLC), an innovation aimed at achieving independent and more efficient humidity control.

42 ENGINEERING↗

Exergy Analysis of a Convective Heat Pump Dryer Integrated with a Membrane Energy Recovery Ventilator

To increase energy efficiency, heat pump dryers and membrane dryers have been proposed to replace conventional fossil fuel dryers. Both conventional and heat pump dryers require substantial energy for condensing and reheating, while “active” membrane systems require vacuum pumps that are insufficiently developed. Lower temperature dehumidification systems make efficient use of membrane energy recovery ventilators (MERVs) that do not need vacuum pumps, but their high heat losses and lack of vapor selectivity have prevented their use in industrial drying. In this work, we propose an insulating membrane energy recovery ventilator for moisture removal from drying exhaust air, thereby reducing sensible heat loss from the dehumidification process and reheating energy. The second law analysis of the proposed system is carried out and compared with a baseline convective heat pump dryer. Irreversibilities in each component under different ambient temperatures (5–35 °C) and relative humidity (5–95%) are identified. At an ambient temperature of 35 °C, the proposed system substantially reduces sensible heat loss (47–60%) in the dehumidification process, resulting in a large reduction in condenser load (45–50%) compared to the baseline system. The evaporator in the proposed system accounts for up to 59% less irreversibility than the baseline system. A maximum of 24.5% reduction in overall exergy input is also observed. The highest exergy efficiency of 10.2% is obtained at an ambient condition of 35 °C and 5% relative humidity, which is more than twice the efficiency of the baseline system under the same operating condition.

Balaraman, Anand (ORCID:0000000218355788)↗

A novel lung-inspired 3D-printed desiccant-coated heat exchanger for high-performance humidity management in buildings

Offering an independent humidity management method for buildings, desiccant-coated heat exchangers (DCHXs) are deemed a promising approach to improve the overall energy efficiency of air conditioning (AC) systems. State-of-the-art DCHXs, however, are bound with conventional HX topologies either providing limited desiccant-air interfacial areas or introducing excessive pressure drop penalties. In this paper a novel 3D-printed DCHX concept inspired by the bronchi arrangement of a human lung is introduced to address the shortcomings inherent in existing DCHX designs. The proposed lung-inspired DCHX utilizes two intertwined bicontinuous flow networks enabling highly efficient heat and mass transfer characteristics for augmented adsorption and regeneration processes at low pressure drop penalties. While the first network evenly distributes an incoming air stream through the entire volume of the lung-inspired DCHX, the second network volumetrically splits a cooling water stream within and through the first network. Effects of various parameters including air flow rate, outdoor air humidity ratio, and regeneration temperature on dehumidification performance and energy efficiency of the proposed lung-inspired DCHX were investigated. Experimental results indicated the proposed lung-inspired 3D-printed DCHX outperforms existing DCHX systems by demonstrating an excellent balance between a high volumetric adsorption rate and a low pressure drop penalty. The volumetric adsorption rate of the proposed lung-inspired DCHX technology is 54.8 g/m 3 -s, a more than two-fold improvement compared with state-of-the-art DCHX systems. Additionally, the lung-inspired DCHX offers high thermal energy efficiency of 56% at a low regeneration temperature of 40 °C. Therefore, the proposed lung-inspired 3D-printed DCHX offers a new solid-desiccant-based air dehumidification pathway for next-generation high-performance AC systems.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Sensitivity Analysis of an Electrospray Dehumidification System

Electrically enhanced condensation achieved by an electrospray system can enhance dehumidification in HVAC applications if successfully scaled up. The first step towards scale-up is identifying critical design and operating parameters that significantly impact dehumidification for the electrospray system. Sensitivity analysis is one approach for identifying critical parameters. This paper presents a methodology that can efficiently perform quantitative sensitivity analysis on a computationally expensive high fidelity simulation model, which is a computational fluid dynamics (CFD) model of the electrospray system. The methodology employs surrogate modeling and Sobol sensitivity analysis. We estimate the main and total effect Sobol sensitivity indices of four operating parameters of the electrospray system. The results reveal that the most important parameter is the size of the sprayed droplets, followed by the volumetric flow rate of the bulk air and injected water in the system. The water injection velocity of the spray was found to have little to no impact on dehumidification.

Young, David↗

The levelized cost of exergy: a technoeconomic framework for energy system comparison

While the levelized costs of electricity and heat have been quantified before, these two metrics cannot be directly compared, due to the different exergy content of heat and work. To address this, we develop a levelized cost of exergy (LCOEx) framework that enables direct comparisons between energy sources and processes. We find that moderate- and high-grade heat have an LCOEx that is comparable to electricity (5–10 ¢ per kWh ex ), while low-grade heat sources have much higher LCOEx values (>50 ¢ per kWh ex ). The LCOEx of a system's output is affected by (i) the LCOEx of the system input, (ii) the CAPEX of the system, and (iii) the exergetic efficiency of the system. We use our framework to identify which processes are already achieved with relatively high cost effectiveness (production of fuels, hydrogen, and ammonia) and which have room for improvement (dehumidification, food production).

08 HYDROGEN↗

Demonstrating non-isothermal vacuum membrane air dehumidification for efficient next-generation air conditioning

Vacuum membrane air dehumidification has gained significant interest in recent years as a highly efficient means of air dehumidification. Prior theoretical modeling work by the authors introduced the Active Membrane Energy Exchanger (AMX) concept, which combines active heat exchange and vacuum membrane dehumidification into one non-isothermal system, and found that it could outperform other air conditioning technologies under many conditions. However, no experimental literature exists on combining active heat exchangers and vacuum membrane dehumidification. Here, the goal of the present study is to evaluate the dehumidification (mass transfer) performance of the AMX concept relative to isothermal membrane dehumidification through three main methodologies: (1) membrane material-level characterization, (2) experimental prototype development and testing, and (3) computational fluid dynamics (CFD) simulations. The dense membranes used in this work showed up to a 40% increase in water vapor permeance at cooler temperatures, and the prototype system showed up to a 6% increase in humidity removal when the air was simultaneously cooled. Furthermore, the membrane module-integrated heat exchange tubes provided additional mixing and turbulence, leading to a 4–8% increase in humidity removal. The upper limit coefficient of performance was equal to approximately 2.2, necessitating advanced system designs to improve efficiency. This study is the first to highlight that combining the cooling and vacuum dehumidification processes can improve dehumidification performance.

30 DIRECT ENERGY CONVERSION↗

Wickability-optimized textured liquid-desiccant air dehumidifiers for independent moisture management in energy-efficient buildings

Liquid-desiccant-based air conditioning systems are envisioned to enable independent humidity management, thereby improving the energy efficiency of future buildings. Existing liquid-desiccant-based air conditioning concepts, however, suffer from a poor liquid flow distribution deteriorating moisture removal rate. They are consequently flooded with the liquid-desiccant solution, which significantly degrades the energy efficiency of the dehumidification process. Here, in this work, the capillary forces and wickability effect of textured air dehumidifier surfaces are altered to minimize the liquid-desiccant flow rate of the fully wetted state, thereby transforming the physics of interfacial desiccant flow distribution. Consequently, the wickability-optimized air dehumidifier surface maximizes both moisture removal rate and dehumidification energy efficiency. It was interestingly found that the length scale of a textured air dehumidifier surface concept is optimized at an intermediate pattern density. Dry solid-air menisci appear at length scales exceeding the optimum pattern distance while the effective liquid–air interfacial area is reduced at smaller length scales, both of which degrade the moisture removal rate. At the optimum pattern density, the effective liquid–air interfacial area increases with the solution flow rate, thereby increasing the dehumidification rate. At a water vapor pressure potential of 3 kPa and a solution flow rate of 2.8 g/s, experimental results indicated a moisture removal rate of 0.16 g/m2-s for a textured surface concept with a capillary length scale of 3 mm, a 28% improvement compared with that of smooth-plate dehumidifier surfaces. A high moisture removal rate of the textured surface at a low desiccant flow rate led to a high thermal efficiency of 0.75 at a water vapor pressure potential of 5.6 kPa and a LiBr flow rate of 2.8 g/s. The insights gained from the present study accelerate the development of advanced textured surface concepts for next-generation liquid-desiccant-based air dehumidification systems offering independent humidity management for future energy-efficient buildings.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Advances in Desiccant Wheels for Dehumidification, VOC Mitigation, and CO 2 Removal for Energy-Efficient IAQ Management

Humidity control is pivotal to maintain occupant thermal comfort and suppress mold growth in indoor environments. Furthermore, poor indoor air quality (IAQ) due to the presence of volatile organic compounds (VOCs) and high concentrations (>1,000 ppm) of CO 2 can cause health issues and negatively affect cognitive performance. Therefore, providing high-quality indoor air has gained significant attention over the past decade. Conventional cooling coil and filter-based HVAC systems have limited capability to meet the augmented demand for occupant thermal comfort and high indoor air quality. Moreover, modern buildings are increasingly airtight to save energy, and increasing ventilation to mitigate VOC and CO 2 concentration is discouraged. Separate sensible and latent cooling technology using a rotary desiccant wheel presents a promising solution in this respect. Because of the development of desiccant materials with high water vapor, VOC, and CO 2 uptake, desiccant wheels can be used as an integrated technology option for IAQ management. Here, to promote desiccant wheel use for energy-efficient management of IAQ in buildings, this article reviews recent advancements in using desiccant wheels for dehumidification, VOC mitigation, and CO 2 capture from outdoor air. Finally, the article presents the authors’ perspective by summarizing the key research gaps in the field and discussing the future direction of research to address these gaps from two different aspects, namely, suitable adsorbent material development and desiccant wheel design.

CO2 capture↗

Corrosion of Metal Alloys in Potassium Acetate Solutions for Liquid Desiccant Dehumidification and Air Conditioning

For commercial buildings, liquid desiccant air conditioners (LDACs) could provide up to 80% energy savings compared to high-efficiency vapor compression AC, but commonly utilized liquid desiccants are highly corrosive. This precludes the use of metallic components, necessitating specialized plastics and thereby driving up cost, weight, and limiting operational temperature and pressure ranges. Less corrosive alternatives are sought. Here, potassium acetate solutions are investigated as less-corrosive alternatives to the chloride salt solutions that are typically used in LDAC systems. Corrosion evaluations for a Cu alloy (C12200) and two Al alloys (Al3003 and Al1100) in both potassium acetate and chloride salt solutions are presented. We show that yearly corrosion rates are lower in potassium acetate solutions by up to three orders of magnitude. Active corrosion behavior is largely absent in potassium acetate solutions but is present in chloride salt solutions. Furthermore, solid corrosion products are observed in chloride salt solutions. Thus, we conclude that potassium acetate is a promising candidate as a less corrosive alternative liquid desiccant for LDAC systems with metallic components.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

On the validity and limitations of 1D model for heat and mass transfer performance evaluation in a multilayer binder-free desiccant dehumidifier: isothermal dehumidification with internal cooling

Efficient humidity control is essential for maintaining indoor thermal comfort, yet conventional vapor-compression-based dehumidifiers are energy-intensive. Employing separate sensible and latent cooling through desiccant-coated heat exchangers (DCHEs) combined with evaporative coolers offers energy savings of up to 80 % compared to conventional systems. However, the dehumidification performance of DCHEs remains limited due to the use of polymer binders for coating desiccant materials onto heat exchange surfaces. In our previous study, we developed a multilayer fixed-bed binder-free desiccant dehumidifier (MFBDD) that demonstrated high dehumidification capacity and low pressure drop compared to rotary desiccant wheels. Nevertheless, its potential for further enhancement through internal cooling and the use of step-shaped adsorption isotherms has not been explored. In this study, a physics-based one-dimensional (1D) transient model is developed and validated to capture the coupled heat and mass transfer processes in the MFBDD and extended to simulate internal cooling using a high-capacity composite metal–organic framework, MIL-101/GO-6 (water uptake ≈1.6 g/g within 35–47 % RH). The model enables detailed analysis of local air and bed temperature dynamics and quantifies how internal cooling affects the dehumidification performance under a wide range of operating conditions. Results show that integrating internal cooling and using MIL-101/GO-6 enhance mass adsorbed, moisture removal capacity, and dehumidification effectiveness by 50 %–99 % compared with the M.S. Gel baseline. The study further reveals that achieving near-isothermal operation requires simultaneous enhancement of the convective heat transfer coefficient and heat exchange surface area. In conclusion, this work provides the first detailed physical insight into the interplay between internal cooling and step-shaped isotherms in a binder-free desiccant device and establishes a validated modeling framework for scaling up and system-level performance evaluation of next-generation energy-efficient dehumidification systems.

Heat and mass transfer↗

Energy-efficient sorption-based gas clothes dryer systems

Standard electric resistance and fuel-driven dehydration technologies exhibit a maximum coefficient of performance of well below 1 mainly due to enthalpy losses associated with the air leaving the dehydration system. To improve energy efficiency, condensing dryer systems condense the moisture captured from a product in a closed-loop air circulation cycle. Existing condensing dehydration systems including heat pump dryers, however, need to significantly cool the air to achieve dehumidification. The added cooling and subsequent heating to return the air to a desired drying temperature consume substantial energy and thus reduce drying performance. Here, an innovative sorption-based gas dehydration system is proposed to overcome barriers deteriorating energy efficiency in existing gas, electric, or heat pump dryer systems. Decoupling latent and sensible loads, the system employs a liquid-desiccant solution to directly capture air humidity, thereby allowing circulation of the air in a closed loop to achieve high drying energy efficiency. In other words, the system captures waste latent heat from the moisture produced during the dehydration process and reuses it to improve energy efficiency. This study focuses on a comprehensive quasi-steady-state thermodynamic modeling of the proposed sorption-based dehydration concept employed for a gas clothes dryer application to predict transient response and overall drying performance (i.e., time and energy metrics). The analysis indicates the proposed sorption-based gas clothes dryer system can deliver a specific moisture extraction rate of 1.71 kg of water per kWh (i.e., a combined energy factor of 3.167 kg (6.98 lbm) of dry cloth per kWh) with a drying time of 44 min. This is a 112% energy improvement compared with state-of-the-art gas clothes dryers exhibiting a combined energy factor of 1.50 kg (3.3 lbm) of dry cloth per kWh. The technology pursued here can potentially be employed as a platform for many fuel-driven equipment to take advantage of available waste thermal energy in the environment instead of simply burning a fuel.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Material properties of aqueous potassium acetate solutions for use in liquid desiccant air conditioning

We present thermophysical properties of aqueous potassium acetate solutions relevant to their application as a liquid desiccant in air-conditioning systems. Liquid desiccant air conditioners could provide up to 80% energy savings compared to high-efficiency vapor compression air conditioners. However, the commonly used liquid desiccants, particularly chloride salt solutions, are highly corrosive. This precludes the use of metallic components, necessitating specialized plastics and thereby driving up cost, weight, and limiting operational temperature and pressure ranges. Potassium acetate has been identified as a less corrosive alternative, potentially enabling broader material compatibility in LDAC components. In this study we systematically measured and modelled key thermophysical properties of KAc solutions density, vapor pressure, viscosity, specific heat capacity, phase behavior, and diffusion coefficient across a range of concentrations (10 - 70wt%) and temperatures. For instance, KAc exhibits a vapor pressure of 3.1 kPa at 50wt% and 40degrees C, demonstrating dehumidification capability comparable to chloride salts. By providing an extended dataset and associated models, this work advances the understanding needed to design energy-efficient, corrosion mitigating LDAC system.

36 MATERIALS SCIENCE↗