Spectral Clustering-Based Partitioning of Large-Scale Power Electronics-Based Power Systems for Small-Signal Stability Analysis

The nodal admittance matrix (NAM)-based approach is well-suited for small-signal stability analysis of large-scale power electronics-based power systems (PEPSs), as it preserves the system structure through its admittance matrix. Previous studies have explored partitioning such systems into subareas and interconnections to reduce computational burden; however, they lacked a formal algorithmic procedure for determining feasible partitions. While several grid partitioning methods, such as those based on graph theory or machine learning, exist in the literature, they cannot be directly applied to NAM-based analysis due to differing objectives and constraints. Here, this paper addresses this gap by presenting a systematic, step-by-step procedure for applying a spectral partitioning algorithm that yields a division of the system into subareas suitable for NAM-based analysis. The computational complexity of the proposed method is also derived to demonstrate its efficiency and justify the practicality of the resulting subarea decomposition. The performance of the partitioning method is evaluated by applying the spectral clustering-derived subareas and interconnections to the NAM-based partitioning approach on a 140-bus system. Computational times for the full-system and partitioned NAM analyses are compared using MATLAB. Additionally, PSCAD simulations of the complete system and partitioned subareas are carried out to verify the effectiveness of the proposed method.

Nupur [Univ. of Tennessee, Knoxville, TN (United S

Partitioning of Large-Scale Power Electronics-Based Power Systems for Small-Signal Stability Analysis

The nodal admittance matrix (NAM)-based approach is suitable for analyzing the small-signal stability of large-scale power electronics-based power systems (PEPSs) as it preserves the system structure by utilizing the admittance matrix. Previously, NAM-based area partition has been proposed, which divides the system into various subareas and interconnections for easier analysis of the low-dimension matrix compared to the entire system-based high-dimension matrix. However, no partition algorithm has been presented for the NAM-based area partition method. This paper focuses on implementing the spectral partitioning algorithm for partitioning large-scale PEPSs into a low-dimension matrix to reduce the computation complexity of the analysis. These spectral components facilitate data transformation into a new space, enabling the application of traditional clustering methods like k-means. To evaluate the performance of the partitioning method, the subareas and interconnections obtained from the spectral clustering algorithm are incorporated into the NAM-based area partition method for a large system with 140 buses. The computational times of the original method, where the NAM-based criterion is directly applied to the entire system, are compared with those of the NAM-based partition method in MATLAB. PSCAD simulations of the whole system and the obtained subareas are conducted to validate the effectiveness of the proposed algorithm.

Nupur, Nupur

Analytical small-signal stability analysis of low-inertia power system frequency response considering secondary frequency regulation

Modern power systems are increasingly vulnerable to frequency instability as inverter-based resources (IBRs) replace synchronous machines and reduce system rotational inertia. Existing small-signal frequency stability assessment methods are either computationally intensive, relying on simulation-driven approaches, or lack analytical stability regions that explicitly account for secondary frequency response (SFR). This paper introduces new analytical frameworks that enable evaluation small-signal frequency stability while explicitly incorporating tunable IBR and SFR parameters. Using Kharitonov’s theorem with an overbounding approach, explicit small-signal stability criteria are derived. In addition, based on Białas’ criterion and Hurwitz matrix, analytical stability regions are established to reveal feasible design spaces for SFR and IBR parameters tuning. Extensive Matlab/Simulink-based simulations validate the accuracy and computational efficiency of the proposed methods, demonstrating that coordinated tuning of SFR and IBR parameters can substantially enhance system resilience. By bridging analytical rigor with practical tunability, this work provides an analytical framework for assessing small-signal frequency stability in low-inertia grids, supporting the real-time, scalable, and resilient operation of sustainable power systems.

14 SOLAR ENERGY

Holistic Small-Signal Stability Analysis for Large-Scale Inverter-Intensive Power Systems with Coupled and Full-Order Dynamics from Control Systems and Power Networks

The increasing penetration of inverter-based resources (IBRs) into the existing power systems introduces tremendous benefits for enhanced sustainability but also poses inevitable challenges in terms of insufficient inertia, potential instability, and complex network dynamics, among others. However, the additional coupling introduced by the interactions among gridfollowing (GFL) and grid-forming (GFM) IBRs and the other components (i.e., synchronous generators [SGs], loads, and network, etc.) has not been clearly explored. A holistic, scalable, and quantitative stability analysis framework with the control systems and power networks is still missing. Here, in this paper, to fill in the technical gaps, a holistic small-signal model of the entire system with both rotating generation units and IBRs is established. An extended power flow model with operation dynamics from both generator control schemes and power networks is proposed to provide the varying steady-state operating points for small-signal modeling. The proposed method is compared with MATLAB solvers, and the results show that the proposed approach has a minimum calculation time, which can be less than 12 seconds for a large-scale power system with up to 2,000 buses. Furthermore, a quantitative method is developed to identify the impacts of IBRs on system performance with emphases on the potential stability issues with GFL IBRs, additional benefits of employing GFM IBRs, the feasibility of replacing SGs with GFM IBRs, and the impact of penetration level of different kinds of generation units. Finally, a field island power system is used to verify the proposed approach, and hardware-in-the-loop (HIL) tests are provided to further demonstrate the effectiveness of the proposed analysis.

14 SOLAR ENERGY

Control Parameter Sensitivity Study for Inverter-Based-Resource Dominated Grids: A Small Signal Stability Approach and Framework

The growing adoption of renewable energy is driving the prevalence of inverter-based resources (IBRs) within power grids. Future power grids will integrate both grid-following IBRs (GFM-IBRs) and grid-forming IBRs (GFL-IBRs) alongside synchronous generators. Therefore, it is crucial to perform stability studies that account for all components and especially control interactions related to IBRs. Extensive research has performed to study the IBR-related stability, however, the sensitivity study of IBRs' control parameters on system stability has not been adequately studied yet, especially from a systematic way. Therefore, this paper conducts a small signal stability analysis for a generic grid with multiple types of resources and develops an analytical framework for assessing the sensitivity of control parameters affecting stability margins. To achieve that, the non-autonomous reduced-order non-linear dynamic model is developed for a generic power system with multiple synchronous generator-based resources (SGBRs), GFM-IBRs, and GFL-IBRs. Based on the analytic model, a systematic framework for parametric sensitivity on systems' asymptotic stability is developed. A parameter sensitivity analysis based on eigenvalue methods is proposed. The impact of the droop controllers of GFM-IBRs, PQ-dispatch and the PLL controller of GFL-IBR on the system asymptotic stability is discussed. This sensitivity study is aiming to provide deep insights on control parameters' impact on system stability, and gives direction for parameter tuning in case of instability.

24 POWER TRANSMISSION AND DISTRIBUTION

Advanced grid-forming (GFM) inverter controls, modeling and system impact study for inverter dominated grids

Our main goals in this project are to understand: 1) the stability of the power system with very high penetration of PV or other inverter-based resources (IBR), 2) the interactions among IBRs and traditional generators, and 3) the impact of the GFM inverters on bulk power system. To achieve these goals, we took a holistic research and development approach. First, an impedance-based large system modeling and stability analysis tool was developed to aid the large IBR system small-signal stability analysis. Second, consensus-based control and transient overload ride through were developed to control and coordinate multiple GFM inverters in a large system to maintain transient stability during big grid events. Third, high fidelity electromagnetic transient (EMT) IBR models were developed and integrated into a large reduced WECC model to study the system impact from IBRs. Lastly, extensive validation tests of the GFM control which was developed in this project and implemented in two 1MW commercial solar inverters were performed using different validation platforms, e.g., control hardware-in-the-loop (CHIL) platform, power hardware- in-the-loop (PHIL) platform, and a real PV plant.

14 SOLAR ENERGY

Stability Analysis of Power Systems with High Penetration of State-of-the-Art Inverter Technologies

With the increasing level of inverter-based resources (IBRs) in modern power systems, this paper presents a small-signal stability analysis for power systems comprising synchronous generators (SGs) and IBRs. Four types of inverter controls are considered: two grid-following (GFL) controls, with or without grid support functions; droop-based grid-forming (GFM) controls; and virtual oscillator control-based GFM. We also analyze the impact of STATCOM and synchronous condensers on system stability to assess their role in the energy mix transition. With the small-signal dynamic behavior of the major technologies modeled, this paper provides stringent stability assessments using the IEEE 39-bus benchmark system modified to simulate future power systems. The exhaustive test cases allow for (a) assessing the impacts of different types and controls of generation and supplementary grid assets, as well as system inertia and line impedance on grid stability, and (b) elucidating pathways for the stabilization of IBR-dominated power systems. The analysis also indicates that future power systems can be stabilized with only a fraction of the total generation as voltage sources without SGs or significant system inertia if they are well distributed. This study provides insights into future power system operations with a high level of IBRs that can also be used for planning and operation studies.

24 POWER TRANSMISSION AND DISTRIBUTION

Small-Signal Stability of Grid-Forming Inverters Using Current-Limiting and Frequency Stabilization

This paper presents a small-signal stability analysis of grid-forming (GFM) inverters under current-limiting conditions. It examines how adjustments in virtual impedance angles, implemented through advanced current-limiting and frequency stabilization techniques, influence small-signal stability. This paper studies a GFM inverter control integrating a fictitious power technique stabilizing primary control by adding a virtual power term and a hybrid current limiter integrating virtual impedance in the anti-wind-up feedback with current reference saturation limiting. A small-signal model is developed to assess the impact of virtual impedance angles on GFM inverter dynamics during grid disturbances, such as voltage drops. The findings indicate that although increasing the virtual impedance angle (to make it more inductive) enhances large-signal stability and voltage support during faults, it can induce oscillations and lead to instability if the angle exceeds certain thresholds. Based on the small-signal models, this paper provides design considerations for the current-limiter impedances to ensure reliable GFM inverter behavior under grid disturbances while maintaining small-signal stability.

current limiting

Application of small-signal modeling and measurement techniques to the stability analysis of an integrated switching-mode power system

Small-signal modeling techniques are used in a system stability analysis of a breadboard version of a complete functional electrical power system. The system consists of a regulated switching dc-to-dc converter, a solar-cell-array simulator, a solar-array EMI filter, battery chargers and linear shunt regulators. Loss mechanisms in the converter power stage, including switching-time effects in the semiconductor elements, are incorporated into the modeling procedure to provide an accurate representation of the system without requiring frequency-domain measurements to determine the damping factor. The small-signal system model is validated by the use of special measurement techniques which are adapted to the poor signal-to-noise ratio encountered in switching-mode systems. The complete electrical power system with the solar-array EMI filter is shown to be stable over the intended range of operation.

Wong, R. C.

Small-Signal Analysis of Current-Limiting Grid-Forming Inverters

Grid-forming (GFM) inverters are equipped with a current limiter to protect the device during grid disturbances. Because the intervention of the current limiter can compromise the transient stability of the GFM inverter, various types of current limiter designs and additional frequency-stabilization control methods have been proposed in recent literature to aid in transient GFM inverter stability; however, the small-signal stability implications of adding these additional control blocks during, in particular, off-nominal conditions are not fully understood. To address this challenge, this paper presents a generic small-signal model of a GFM inverter that incorporates various types of current limiters and frequency stability-enhancing controls. With the proposed model, we analyze the root causes of inverter instability, which reveals two critical design trade-offs. First, due to current-limiter engagement caused by a disturbance, the GFM inverter dynamics are altered, which can lead to voltage oscillations. Second, additional frequency-stabilization controls can improve the small-signal stability of the GFM inverter, but at the cost of reduced power and voltage support to the grid. Comprehensive hardware experiments validate the theoretical concept and analysis. The findings in this work underscore the importance of incorporating both transient-response and small-signal dynamics requirements into the design procedure of GFM current limiters and frequency-stabilization controls.

24 POWER TRANSMISSION AND DISTRIBUTION

Hybrid Symbolic-Numerical Modeling and Parametric Stability Analysis of DC–AC Power Systems

Hybrid DC-AC power systems integrating diverse inverter-based resources (IBRs) and multi-terminal high-voltage direct current (MTDC) networks represent a promising architecture for future power grids, while introducing challenges for modeling, stability analysis, and control design. This paper develops a hybrid symbolic-numerical modeling framework and tool to characterize the parametric small-signal stability of DC-AC coupled power systems. The proposed approach constructs parametric state-space models to enable efficient representation of system dynamics under varying control parameters and network configurations, with target parameters retained as symbolic variables and the remainder treated numerically. The stability analysis framework covers eigenvalue, sensitivity, and stability boundary and region characterization. Enhanced linear matrix inequality (LMI) techniques are proposed to directly certify small-signal stability over regions of parameter space while also reducing the conservativeness and computational burden. The resulting tools and frameworks enable rapid parametric model construction across diverse grid conditions, thereby facilitating stability-informed control and operation in complex DC–AC power systems.

DC–AC power systems

Small-Signal Stability Constrained Optimal Power Flow of Inverter-Dominated Power Systems with Flexible Operation Mode Selection

Given the intermittence and low inertia nature of inverter-based resources (IBRs), modern power systems with high penetration of IBRs challenge the conventional optimal power flow (OPF) analysis and the system may experience unexpected failures if stability constraints are not incorporated. This study proposes a small-signal stability-constrained OPF (SSSC-OPF) with flexible operation mode selection between grid-forming (GFM) and grid-following (GFL) modes for IBRs to address these challenges. The approach aims to maintain system stability with a sufficient stability margin while minimizing operation costs. The effectiveness of the proposed method is validated through extensive case studies on the IEEE 14-bus system. The results demonstrate that the proposed method is able to support system-level power flow analysis, reduce generation costs, and ensure stability under various disturbances.

grid-following

Linearized stability analysis and design of a flyback dc-dc boost regulator.

Analytic expressions for the small-signal power-stage describing functions of a switched dc-dc boost regulator are derived from an approximate continuous circuit model which is developed by a time-averaging technique. Closed-loop stability is attained through the design of frequency compensation of the loop gain. Open- and closed-loop regulator output impedances are derived from the linearized models for the given configuration. The analysis and design are compared with and confirmed by breadboard measurements.

Wester, G. W.

Generalized computer-aided discrete time domain modeling and analysis of dc-dc converters

A generalized discrete time domain modeling and analysis technique is presented for all types of switching regulators using any type of duty-cycle controller, and operating in both continuous and discontinuous inductor current. State space techniques are employed to derive an equivalent nonlinear discrete time model that describes the converter exactly. The system is linearized about its equilibrium state to obtain a linear discrete time model for small signal performance evaluations, such as stability, audiosusceptibility and transient response. The analysis makes extensive use of the digital computer as an analytical tool. It is universal, exact and easy to use.

Lee, F. C.

Gateway Power Quality Lessons Learned

Power Quality is a physical description of the electrical characteristics that allow the system to function properly without significant loss of performance or life. This physical description includes steady state voltage limits, transient voltage limits in normal/abnormal conditions, ripple voltage, stability, fault conditions, and more. All which are vital for improving reliability, ensuring stable operation, defining proper fault recovery, and ensuring a ‘plug and play’ approach to design and integration. Typically, a specification for Power Quality is created based on expected system performance or an existing standard, such as the International Space Power System Interoperability Standards (ISPSIS). One example of such a specification is the Gateway Power Quality Specification. It defines the requirements and characteristics of the 120 Volt direct current electrical power system for the Gateway Electrical Power System (EPS) and the Gateway Electrical Power Consuming Equipment (EPCE). This specification also maintains a separate requirement verification section that defines test methods for requirement verification. The test methods include analysis, test, inspection, and demonstration. These test methodologies and requirements are used to ensure that the loads operate when connected to the specified power quality and performance as defined by this specification. The challenge with developing a specification is that desired system characteristics are not always fully matured before the specification is needed and many performance requirements may be application specific. This drives the need to utilize lessons learned through extensive analysis and testing as well as historical knowledge to finalize requirements. Some example requirements where this is important are Small and Large Signal Stability, Ripple Voltage, Inrush/Surge Currents, and Fault Containment. Lessons learned are also important in the testing, analysis, and verification to ensure consistent and accurate results to verify performance. This presentation will cover the lessons learned for power quality relative to ripple, inrush/surge, fault containment, testing/verification, and more.

Power Quality

A fast time domain digital simulation technique for power converters - Application to a buck converter with feedforward compensation

Small signal analysis was performed earlier to demonstrate the marked improvement of dynamic properties and stability margins of a switching regulator employing a novel feedforward input filter compensation scheme. A large signal nonlinear recurrent time domain model is presented for the converter to analyse the transient response due to a step input change with and without the presence of the proposed feedforward loop. The results are verified with experimental data.

Kelkar, S. S.

A State-Space Model for Stability Boundary Analysis of Grid-Following Voltage Source Converters Considering Grid Conditions

With the growing significance of renewable energy resources and energy storage systems, the number of grid-connected inverters has been rising at an increasingly rapid pace. Generally, these inverters are directly integrated with the distribution network by synchronizing with the grid voltage at the point of common coupling. However, the low grid strength and varying R/X ratios, as the common characteristics of most distribution networks or weak grids, can lead to dynamic interactions that comprise stability and limit the power transfer capacity of grid-connected inverters. To ensure stable operation of the inverters, researchers must determine the stability boundary, described as the maximum power transfer capacity of grid-connected inverters under the premise of maintaining system small-signal stability. For this purpose, we propose to formulate a state-space model of the system in the synchronously rotating dq-frame of reference and perform eigenvalue analysis to determine the stability boundary. With a detailed model of the control structure and parameters of the grid-connected inverters, the stability boundary is identified as a surface with respect to different grid strengths and R/X ratios. Case study results of proposed eigenvalue analysis are compared with those of admittance model-based stability analysis as well as time-domain simulation using a switching model in Matlab/Simulink, validating the effectiveness and accuracy of the proposed eigenvalue analysis for stability boundary identification.

grid-connected inverters