Search NASA⌕ Search

SEARCH · Search NASA

Results for “small-signal stability”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

Small-Signal Stability of Grid-Forming Inverters Using Current-Limiting and Frequency Stabilization

This paper presents a small-signal stability analysis of grid-forming (GFM) inverters under current-limiting conditions. It examines how adjustments in virtual impedance angles, implemented through advanced current-limiting and frequency stabilization techniques, influence small-signal stability. This paper studies a GFM inverter control integrating a fictitious power technique stabilizing primary control by adding a virtual power term and a hybrid current limiter integrating virtual impedance in the anti-wind-up feedback with current reference saturation limiting. A small-signal model is developed to assess the impact of virtual impedance angles on GFM inverter dynamics during grid disturbances, such as voltage drops. The findings indicate that although increasing the virtual impedance angle (to make it more inductive) enhances large-signal stability and voltage support during faults, it can induce oscillations and lead to instability if the angle exceeds certain thresholds. Based on the small-signal models, this paper provides design considerations for the current-limiter impedances to ensure reliable GFM inverter behavior under grid disturbances while maintaining small-signal stability.

current limiting↗

Small-Signal Stability of Grid-Forming Converters Under Fault Conditions

Threshold virtual impedance (TVI)-based current limiting for grid-forming converters (GFMs) has gained great interest due to its ability to maintain voltage source behaviour during faults. However, sequence component extraction (SCE) and negative-sequence control (NSC) are often overlooked in small-signal stability assessments during faults. This paper develops small-signal sequence impedance models for GFMs under four well-known SCE methods based on TVI current limiting control during symmetrical fault conditions. Using the developed impedance models, the impacts of SCE and NSC, and the voltage and current control loop bandwidths, on system stability during faults are investigated. Additionally, since negative-sequence TVI (TVI-) is typically added along with its positive-sequence counterpart, which is often inductive, inductive and resistive TVI- are examined. The findings suggest that a higher voltage or current control loop bandwidth has a negative impact on system stability, while SCE and NSC largely reduce the stable range for voltage and current control loop bandwidth during faults, and that the severity of such impacts is determined by the particular SCE method. Furthermore, it is observed that inductive TVI- significantly degrades system stability, while resistive TVI- can enhance stability when suitable SCE methods are appropriately selected and designed. Matlab/Simulink electromagnetic transient simulations validate these analytical results.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Spectral Clustering-Based Partitioning of Large-Scale Power Electronics-Based Power Systems for Small-Signal Stability Analysis

The nodal admittance matrix (NAM)-based approach is well-suited for small-signal stability analysis of large-scale power electronics-based power systems (PEPSs), as it preserves the system structure through its admittance matrix. Previous studies have explored partitioning such systems into subareas and interconnections to reduce computational burden; however, they lacked a formal algorithmic procedure for determining feasible partitions. While several grid partitioning methods, such as those based on graph theory or machine learning, exist in the literature, they cannot be directly applied to NAM-based analysis due to differing objectives and constraints. Here, this paper addresses this gap by presenting a systematic, step-by-step procedure for applying a spectral partitioning algorithm that yields a division of the system into subareas suitable for NAM-based analysis. The computational complexity of the proposed method is also derived to demonstrate its efficiency and justify the practicality of the resulting subarea decomposition. The performance of the partitioning method is evaluated by applying the spectral clustering-derived subareas and interconnections to the NAM-based partitioning approach on a 140-bus system. Computational times for the full-system and partitioned NAM analyses are compared using MATLAB. Additionally, PSCAD simulations of the complete system and partitioned subareas are carried out to verify the effectiveness of the proposed method.

Nupur [Univ. of Tennessee, Knoxville, TN (United S↗

Analytical small-signal stability analysis of low-inertia power system frequency response considering secondary frequency regulation

Modern power systems are increasingly vulnerable to frequency instability as inverter-based resources (IBRs) replace synchronous machines and reduce system rotational inertia. Existing small-signal frequency stability assessment methods are either computationally intensive, relying on simulation-driven approaches, or lack analytical stability regions that explicitly account for secondary frequency response (SFR). This paper introduces new analytical frameworks that enable evaluation small-signal frequency stability while explicitly incorporating tunable IBR and SFR parameters. Using Kharitonov’s theorem with an overbounding approach, explicit small-signal stability criteria are derived. In addition, based on Białas’ criterion and Hurwitz matrix, analytical stability regions are established to reveal feasible design spaces for SFR and IBR parameters tuning. Extensive Matlab/Simulink-based simulations validate the accuracy and computational efficiency of the proposed methods, demonstrating that coordinated tuning of SFR and IBR parameters can substantially enhance system resilience. By bridging analytical rigor with practical tunability, this work provides an analytical framework for assessing small-signal frequency stability in low-inertia grids, supporting the real-time, scalable, and resilient operation of sustainable power systems.

14 SOLAR ENERGY↗

Small-Signal Stability Constrained Optimal Power Flow of Inverter-Dominated Power Systems with Flexible Operation Mode Selection

Given the intermittence and low inertia nature of inverter-based resources (IBRs), modern power systems with high penetration of IBRs challenge the conventional optimal power flow (OPF) analysis and the system may experience unexpected failures if stability constraints are not incorporated. This study proposes a small-signal stability-constrained OPF (SSSC-OPF) with flexible operation mode selection between grid-forming (GFM) and grid-following (GFL) modes for IBRs to address these challenges. The approach aims to maintain system stability with a sufficient stability margin while minimizing operation costs. The effectiveness of the proposed method is validated through extensive case studies on the IEEE 14-bus system. The results demonstrate that the proposed method is able to support system-level power flow analysis, reduce generation costs, and ensure stability under various disturbances.

grid-following↗

Hybrid Symbolic-Numerical Modeling and Parametric Stability Analysis of DC–AC Power Systems

Hybrid DC-AC power systems integrating diverse inverter-based resources (IBRs) and multi-terminal high-voltage direct current (MTDC) networks represent a promising architecture for future power grids, while introducing challenges for modeling, stability analysis, and control design. This paper develops a hybrid symbolic-numerical modeling framework and tool to characterize the parametric small-signal stability of DC-AC coupled power systems. The proposed approach constructs parametric state-space models to enable efficient representation of system dynamics under varying control parameters and network configurations, with target parameters retained as symbolic variables and the remainder treated numerically. The stability analysis framework covers eigenvalue, sensitivity, and stability boundary and region characterization. Enhanced linear matrix inequality (LMI) techniques are proposed to directly certify small-signal stability over regions of parameter space while also reducing the conservativeness and computational burden. The resulting tools and frameworks enable rapid parametric model construction across diverse grid conditions, thereby facilitating stability-informed control and operation in complex DC–AC power systems.

DC–AC power systems↗

Stability Analysis of Power Systems with High Penetration of State-of-the-Art Inverter Technologies

With the increasing level of inverter-based resources (IBRs) in modern power systems, this paper presents a small-signal stability analysis for power systems comprising synchronous generators (SGs) and IBRs. Four types of inverter controls are considered: two grid-following (GFL) controls, with or without grid support functions; droop-based grid-forming (GFM) controls; and virtual oscillator control-based GFM. We also analyze the impact of STATCOM and synchronous condensers on system stability to assess their role in the energy mix transition. With the small-signal dynamic behavior of the major technologies modeled, this paper provides stringent stability assessments using the IEEE 39-bus benchmark system modified to simulate future power systems. The exhaustive test cases allow for (a) assessing the impacts of different types and controls of generation and supplementary grid assets, as well as system inertia and line impedance on grid stability, and (b) elucidating pathways for the stabilization of IBR-dominated power systems. The analysis also indicates that future power systems can be stabilized with only a fraction of the total generation as voltage sources without SGs or significant system inertia if they are well distributed. This study provides insights into future power system operations with a high level of IBRs that can also be used for planning and operation studies.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A State-Space Model for Stability Boundary Analysis of Grid-Following Voltage Source Converters Considering Grid Conditions

With the growing significance of renewable energy resources and energy storage systems, the number of grid-connected inverters has been rising at an increasingly rapid pace. Generally, these inverters are directly integrated with the distribution network by synchronizing with the grid voltage at the point of common coupling. However, the low grid strength and varying R/X ratios, as the common characteristics of most distribution networks or weak grids, can lead to dynamic interactions that comprise stability and limit the power transfer capacity of grid-connected inverters. To ensure stable operation of the inverters, researchers must determine the stability boundary, described as the maximum power transfer capacity of grid-connected inverters under the premise of maintaining system small-signal stability. For this purpose, we propose to formulate a state-space model of the system in the synchronously rotating dq-frame of reference and perform eigenvalue analysis to determine the stability boundary. With a detailed model of the control structure and parameters of the grid-connected inverters, the stability boundary is identified as a surface with respect to different grid strengths and R/X ratios. Case study results of proposed eigenvalue analysis are compared with those of admittance model-based stability analysis as well as time-domain simulation using a switching model in Matlab/Simulink, validating the effectiveness and accuracy of the proposed eigenvalue analysis for stability boundary identification.

grid-connected inverters↗

Small-Signal Analysis of Current-Limiting Grid-Forming Inverters

Grid-forming (GFM) inverters are equipped with a current limiter to protect the device during grid disturbances. Because the intervention of the current limiter can compromise the transient stability of the GFM inverter, various types of current limiter designs and additional frequency-stabilization control methods have been proposed in recent literature to aid in transient GFM inverter stability; however, the small-signal stability implications of adding these additional control blocks during, in particular, off-nominal conditions are not fully understood. To address this challenge, this paper presents a generic small-signal model of a GFM inverter that incorporates various types of current limiters and frequency stability-enhancing controls. With the proposed model, we analyze the root causes of inverter instability, which reveals two critical design trade-offs. First, due to current-limiter engagement caused by a disturbance, the GFM inverter dynamics are altered, which can lead to voltage oscillations. Second, additional frequency-stabilization controls can improve the small-signal stability of the GFM inverter, but at the cost of reduced power and voltage support to the grid. Comprehensive hardware experiments validate the theoretical concept and analysis. The findings in this work underscore the importance of incorporating both transient-response and small-signal dynamics requirements into the design procedure of GFM current limiters and frequency-stabilization controls.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Application of small-signal modeling and measurement techniques to the stability analysis of an integrated switching-mode power system

Small-signal modeling techniques are used in a system stability analysis of a breadboard version of a complete functional electrical power system. The system consists of a regulated switching dc-to-dc converter, a solar-cell-array simulator, a solar-array EMI filter, battery chargers and linear shunt regulators. Loss mechanisms in the converter power stage, including switching-time effects in the semiconductor elements, are incorporated into the modeling procedure to provide an accurate representation of the system without requiring frequency-domain measurements to determine the damping factor. The small-signal system model is validated by the use of special measurement techniques which are adapted to the poor signal-to-noise ratio encountered in switching-mode systems. The complete electrical power system with the solar-array EMI filter is shown to be stable over the intended range of operation.

Wong, R. C.↗

Diodes stabilize LED output

Small-signal diodes are placed in series with light-emitting diodes (LED's) to stabilize LED output against temperature fluctuations. Simple inexpensive method compensates for thermal fluctuations over a broad temperature range. Requiring few components, technique is particularly useful where circuit-board space is limited.

Deters, R. A.↗

Virtual Self-Excited Induction Generator-Based Grid-Forming Inverter Control for Robust Voltage Regulation Under Nonideal Loading

This paper presents a generator-inspired control methodology for grid-forming (GFM) inverters that deliberately emulates a self-excited induction generator so that the inverter can hold its voltage and frequency under difficult loading and severe terminal disturbances across wide voltage and frequency ranges. The design integrates a Lyapunov energy function-based inner loop to provide high bandwidth and strong disturbance rejection, and it complements this with a passivity-based argument that furnishes a coherent large-signal stability guarantee beyond small-signal limits. Analytical insights are developed via the Krylov-Bogoliubov-Mitropolsky averaging method, which reveals an intrinsic resistive droop characteristic; these closed-form relations both explain the observed dynamics and yield simple, decentralized tuning rules. The methodology is validated on a controller-hardware-in-the-loop platform and exercised in real time across balanced, unbalanced, and nonlinear loads, as well as during parallel operation. Across these scenarios, the inverter maintains balanced three-phase voltages, limits harmonic content, settles quickly with well-damped transients, and remains resilient when multiple units operate in parallel. The contributions are a self-excited-machine-inspired GFM controller with enhanced dynamic performance and robustness, a single stability rationale grounded in passivity, closed-form expressions that guide tuning, and comprehensive hardware-in-the-loop validations demonstrating effectiveness and superiority under challenging operating conditions.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Linearized stability analysis and design of a flyback dc-dc boost regulator.

Analytic expressions for the small-signal power-stage describing functions of a switched dc-dc boost regulator are derived from an approximate continuous circuit model which is developed by a time-averaging technique. Closed-loop stability is attained through the design of frequency compensation of the loop gain. Open- and closed-loop regulator output impedances are derived from the linearized models for the given configuration. The analysis and design are compared with and confirmed by breadboard measurements.

Wester, G. W.↗

Investigations of stability and dynamic performances of switching regulators employing current-injected control

The stability and dynamic performances of a buck/boost regulator employing a current-injected control are examined. Small-signal models for the power state, the multi-loop error processor and the duty-cycle pulse-modulator are developed. The error-processor model which incorporates the current-injected loop, the dc loop and the compensation network permits evaluation of the effects of each individual control loop and their combined efforts toward shaping the performance characteristics of the closed-loop system. Comparisons are made between this modeling approach and earlier approaches. Some important yet subtle dissimilarities are discussed. This model predicts the constant-frequency 50 percent duty-cycle instability which is inherent to the current-injected control.

Lee, F. C.↗

Rotated-Droop Control for Enhanced Stability and Power Decoupling in Microgrids With Complex Line Impedances

Classical droop control in microgrids predominantly assumes inductive line impedance, which simplifies implementation but causes power coupling and steady-state errors in systems with resistive and inductive lines. This paper proposes a rotated-droop control strategy for grid-forming inverters that reformulates the power equations by incorporating the magnitude and angle of the line impedance within a rotated reference frame. This method enhances the decoupling of active and reactive power dynamics without increasing complexity or requiring communication links. A small-signal state-space model was created to capture the dynamic behavior of the system under varying impedance parameters, preserving the original droop gains by rotating the power control structure. This allows eigenvalue-based stability analysis and enhances damping and transient performance. Simulation and experimental results validated the improved power-sharing performance, faster response, and robustness of the proposed method under different impedance conditions. This approach maintains the decentralized structure of the conventional droop control while enabling greater adaptability and scalability, making it suitable for modern inverter-based microgrids with dynamic topologies.

Campo-Ossa, Daniel Dario [Univ. of Puerto Rico, Ag↗

Quantitative energy extraction measurements in a photoionization-stabilized self-sustained XeF laser

Detailed time-correlated gain, fluorescence, and laser energy measurements were used to obtain quantitative data on energy extraction efficiencies for a photoionization-stabilized self-sustained XeF laser. A current pulse of 25 ns full width at half-maximum produced an 80-cu-cm XeF plasma in NF3:Xe:He gas mixtures with a maximum output energy of 80 mJ. The results show that the maximum small-signal gain and the maximum specific output energy is proportional to the NF3 content of the gas mixture. This suggests that there is an optimum fractional utilization of the NF3 molecules in the discharge. Under high-gain conditions, 30-40% of the energy stored in XeF(asterisk) can be extracted in a gain-switched pulse. The output energy represents less than 1% of the input energy.

Lee, C. M.↗