Assessment of the 3430 Building Filtered Exhaust Stack Sampling Probe Location: Stack Verification Following Fan and Air Blender Additions

The velocity uniformity and flow angle results from the 3430 stack verification tests, performed in April 2023, demonstrated that the CFD model results may be used to support the qualification of the stack sampling location. The measured velocity uniformity verification test result was 2.1 %COV. This value is well within the uniformity criterion, which is that the velocity uniformity be =20 %COV. Additionally, this value is well within the criterion that the actual stack measurement must be within 5% of the surrogate stack (i.e., CFD modeled stack); in this case the CFD modeled average result of 2.85 %COV for the nominal operating range of 22,800 cfm to 62,400 cfm. Additionally, the measured average flow angle at the 3430 stack monitor location was 5.6 degrees. The result is =20 degrees, so the criterion is met.

3430 Building↗

Assessment of the 3420 Building Filtered Exhaust Stack Sampling Probe Location: Stack Verification Following Fan and Air Blender Additions

The Pacific Northwest National Laboratory (PNNL) 3420 Building, which is part of the Physical Sciences Facility (PSF), houses radiological capabilities that results in the requirement that emissions monitoring must be conducted for potential radionuclides in the exhaust air discharge of this building. The air monitoring system is required to conform to Title 40 of the Code of Federal Regulations part 61 (40 CFR 61) Subpart H, which in turns requires a sampling probe in the exhaust stream to conform to the criteria of American National Standards Institute / Health Physics Society (ANSI/HPS) N13.1-2011, Sampling and Monitoring Releases of Airborne Radioactive Substances from the Stack and Ducts of Nuclear Facilities. To support the air emissions permit for the 3420 Building on the PNNL campus, stack testing that used computational fluid dynamics (CFD) modeling as a surrogate stack and verification tests of velocity uniformity and flow angle on the retrofitted facility stack was performed. The ANSI/HPS N13.1-2011 criteria for the air monitoring probe location are that velocity uniformity, gaseous tracer uniformity, and particulate tracer uniformity must be less than or equal to 20%COV. Furthermore, no point in the sampling location may have a gaseous tracer concentration that varies from the mean concentration by more than 30%. Additionally, the flow angle at the sampling location must not be more than 20°. The CFD modeling of the stack, as reported by Recknagle et al. (2018) demonstrated that the stack meets the criteria at the probe location. The velocity uniformity and flow angle results from the 3420 stack verification tests, performed in October 2020, demonstrated that the CFD model results may be used to support the qualification of the stack sampling location. The measured velocity uniformity verification test result was 1.4%COV. This value is well within the uniformity criterion, which is that the velocity uniformity be =20%COV. Additionally, this value is well within the criterion that the actual stack measurement must be within 5% of the surrogate stack result of 2.1%COV when all four fans were operating. Additionally, the measured average flow angle at the 3420 stack monitor location was 15.5 degrees. Although this is higher than expected based on the CFD model, the result is =20 degrees, so the criterion is met. Based on these stack verification test results, the reconfigured 3420 Building filtered exhaust stack meets the qualification criteria given in the ANSI/HPS N13.1-2011 standard. Further changes to the system configuration or operating conditions that are outside the bounds described in this and the CFD report (Recknagle et al., 2018) may require additional tests and additional analysis to determine compliance with the standard.

3420 Building↗

Modeling and Qualification of a Modified Emission Unit for Radioactive Air Emissions Stack Sampling Compliance

A planned laboratory space and exhaust system modification to the Pacific Northwest National Laboratory Material Science and Technology Building indicated a new evaluation of the mixing at the air sampling system location would be required for compliance to ANSI/HPS N13.1-2011. The modified exhaust system would add a third fan thereby increasing the overall exhaust rate out the stack thus voiding the previous mixing study. Prior to modifying the radioactive air emissions exhaust system, a three-dimensional computational fluid dynamics computer model was used to evaluate the mixing at the sampling system location. Modeling of the new original three-fan system indicated that not all mixing criteria could be met. A second modeling effort was conducted with the addition of an air blender downstream of the confluence of the three fans which then showed satisfactory mixing results. The final installation included an air blender, and the exhaust system underwent full-scale tests to verify velocity, cyclonic flow, gas, and particulate uniformity. The modeling results and those of the full-scale tests show agreement between each of the evaluated criteria. The use of a computational fluid dynamics code was an effective aid in the design process and allowed the sampling system to remain in its original location while still meeting the requirements for sampling at a well-mixed location.

atmospheric emissions, air monitoring, environment↗

Computational Fluid Dynamics Modeling to Facilitate Qualification of Stack Sampling Probe Location

Computational fluid dynamics (CFD) modeling was used to help evaluate modifications to a radiological effluent stack and assist with establishing a stack sampling location that met the mixing criteria for qualification. Requirements for stack sampling location are listed in the American National Standards Institute/Health Physics Society (ANSI/HPS) N13.1-2021 standard. Modeling was performed to help develop a suitable design for increasing building ventilation for the radiological effluent stack. The ANSI/HPS N13.1-2021 criteria for the air monitoring probe location are that the coefficient of variation of velocity uniformity, gaseous tracer uniformity, and particulate tracer uniformity must be less than or equal to 20%. Furthermore, no point in the sampling location may have a gaseous tracer concentration that varies from the mean concentration by more than 30%. Additionally, the flow angle at the sampling location must not be more than 20 degrees. The ANSI/HPS N13.1-2021 standard allows for models (physical or computational) to be employed to perform the full suite of qualification tests, followed by a more limited set of verification tests on the actual stack to qualify the stack sampling location. Here, a series of computational model simulations were employed to evaluate the stack qualification criteria. Significant time and re-source savings are achieved using CFD modeling. CFD modeling demonstrated that the stack meets the criteria at the sample probe location. Verification tests were performed on the modified stack to measure the velocity uniformity and flow angle at the stack sampling location, and results demonstrated that the CFD model results may be used to support the qualification of the stack sampling location.

Air Monitoring↗

Measurement of vapor phase mercury emissions at coal-fired power plants using regular and speciating sorbent traps with in-stack and out-of-stack sampling methods

A systematic investigation of sorbent-trap sampling, which is a method that uses paired sorbent traps to measure total vapor phase mercury (Hg), was carried out at two coal-fired power plants. The objective of the study was to evaluate the effects (if any) on data quality when the following aspects of the sorbent trap method are varied: (a) sorbent trap configuration; (b) sampling time; and (c) analytical technique. Also, the performance of a speciating sorbent trap (i.e., a trap capable of separating elemental Hg from oxidized Hg), was evaluated by direct comparison against the Ontario Hydro (OH) reference method. Flue gas samples were taken using both 'regular' and modified sorbent trap measurement systems. Both short-term (1.5 h) and long-term (18 h to 10 days) samples were collected. The in-stack and out-of-stack sampling methods produced satisfactory relative accuracy results for both the short-term and long-term testing. For the short-term tests, the in-stack sampling results compared more favorably to the OH method than did the out-of-stack results. The relative deviation between the paired traps was considerably higher for the short-term out-of-stack tests than for the long-term tests. A one-way analysis of variance (ANOVA), showed a statistically significant difference (p < 0.1) between the direct combustion and wet-chemistry analytical methods used in the study; the results from the direct combustion method were consistently higher than the wet-chemistry results. The evaluation of the speciating mercury sorbent trap demonstrated that the trap is capable of providing reasonably accurate total mercury concentrations and speciation data that are somewhat comparable to data obtained with the OH method. 5 refs., 4 figs., 8 tabs.

01 COAL, LIGNITE, AND PEAT↗

Remaining Sites Verification Package for the 100-F-46, 119-F Stack Sampling French Drain, Waste Site Reclassification Form 2008-021

The 100-F-46 french drain consisted of a 1.5 to 3 m long, vertically buried, gravel-filled pipe that was approximately 1 m in diameter. Also included in this waste site was a 5 cm cast-iron pipeline that drained condensate from the 119-F Stack Sampling Building into the 100-F-46 french drain. In accordance with this evaluation, the confirmatory sampling results support a reclassification of this site to No Action. The current site conditions achieve the remedial action objectives and the corresponding remedial action goals established in the Remaining Sites ROD. The results of confirmatory sampling show that residual contaminant concentrations do not preclude any future uses and allow for unrestricted use of shallow zone soils. The results also demonstrate that residual contaminant concentrations are protective of groundwater and the Columbia River.

100-F-46 French Drain↗

Evaluation of Minimum Detectable Activities for Stack Sample Analyses

The Rad-NESHAP program takes samples at major point sources to track how much of select nuclides are being emitted out of the stack. Samples are taken at the site where the radiological operations are being performed. The samples are then sent to analytical laboratories for analysis to determine what nuclides exist in the sample. However, due to the sensitivity of the instruments, false positives are often reported. To reduce the number of false positives, the results reported from the analytical labs are compared to set detection limits. Anything below the set detection limit is considered part of the background while anything above the limit is considered a positive hit. Therefore, the detection limit must be set low enough that any false negatives do not result in a significant dose missed at the end of the year but high enough that there are not enough false positives to skew the annual dose being reported. All detection limits listed in this section for the analyses below were designed to meet the stated equivalent emissions rate and subsequent off-site doses. These minimum detectable activities (MDAs) were developed in the 1990s and documented in the memo cited for each analysis below. These limits and memos are all currently referenced in the Quality Assurance Project Plan (QAPP) for the Rad-NESHAP Compliance Task, which is being updated to a Project Implementation Plan (PIP) concurrently with this document. As part of this update process, the original MDAs defined in this section needed to be verified that they were still conservative and meet the off-site dose levels stated.

2019 MDA↗

Field-amplified sample stacking and focusing in nanofluidic channels

Nanofluidic technology is gaining popularity for bioanalytical applications due to advances in both nanofabrication and design. One major obstacle in the widespread adoption of such technology for bioanalytical systems is efficient detection of samples due to the inherently low analyte concentrations present in such systems. This problem is exacerbated by the push for electronic detection, which requires an even higher sensor-local sample concentration than optical detection. This paper explores one of the most common preconcentration techniques, field-amplified sample stacking, in nanofluidic systems in efforts to alleviate this obstacle. Holding the ratio of background electrolyte concentrations constant, the parameters of channel height, strength of electric field, and concentration are varied. Although in micron scale systems, these parameters have little or no effect on the final concentration enhancement achieved, nanofluidic experiments show strong dependencies on each of these parameters. Further, nanofluidic systems demonstrate an increased concentration enhancement over what is predicted and realized in microscale counterparts. Accordingly, a depth-averaged theoretical model is developed that explains these observations and furthermore predicts a novel focusing mechanism that can explain the increased concentration enhancement achieved. Specifically, when the electric double layer is sufficient in size relative to the channel height, negatively charged analyte ions are repelled from negatively charged walls, and thus prefer to inhabit the centerline of the channels. The resulting induced pressure gradients formed due to the high and low electrical conductivity fluids in the channel force the ions to move at a slower velocity in the low-conductivity region, and a faster velocity in the high-conductivity region, leading to focusing. A simple single-channel model is capable of predicting key experimental observations, while a model that incorporates the details of the fluid inlet and outlet ports allows for more detailed comparisons between model and experiment.

71 CLASSICAL AND QUANTUM MECHANICS, GENERAL PHYSIC↗

Scaled Tests and Modeling of Effluent Stack Sampling Location Mixing

The Pacific Northwest National Laboratory researchers used a computational fluid dynamics (CFD) computer code to evaluate the mixing at a sampling system location of a research and development facility. The facility requires continuous sampling for radioactive air emissions. Researchers sought to determine whether the location would meet the criteria for uniform air velocity and contaminant concentration as prescribed in the American National Standard Institute (ANSI) standard, Sampling and Monitoring Releases of Airborne Radioactive Substances from the Stacks and Ducts of Nuclear Facilities. Standard ANSI/HPS N13.1-1999 requires that the sampling location be well-mixed and stipulates specific tests (e.g., velocity, gas, and aerosol uniformity and cyclonic flow angle) to verify the extent of mixing.. The exhaust system for the Radiochemical Processing Laboratory was modeled with a CFD code to better understand the flow and contaminant mixing and to predict mixing test results. The CFD results were compared to actual measurements made at a scale-model stack and to the limited data set for the full-scale facility stack. Results indicated that the CFD code provides reasonably conservative predictions for velocity, gas, and aerosol uniformity. Cyclonic flow predicted by the code is less than that measured by the required methods. In expanding from small to full scale, the CFD predictions for full-scale measurements show similar trends as in the scale model and no unusual effects. This work indicates that a CFD code can be a cost-effective aid in design or retrofit of a facility’s stack sampling location that will be required to meet Standard ANSI/HPS N13.1-1999.

air monitoring↗

Assessment of the 3420 Building Filtered Exhaust Stack Sampling Probe Location

Pacific Northwest National Laboratory performed several tests in the exhaust air discharge from the new 3420 Building Filtered Exhaust Stack to determine whether the air sampling probe for emissions monitoring for radionuclides is acceptable. The method followed involved adopting the results of a previously performed test series from a system with a similar configuration, followed by several tests on the actual system to verify the applicability of the previously performed tests. The qualification criteria for these types of stacks include metrics concerning 1) uniformity of air velocity, 2) sufficiently small flow angle with respect to the axis of the duct, 3) uniformity of tracer gas concentration, and 4) uniformity tracer particle concentration.

54 ENVIRONMENTAL SCIENCES↗

Assessment of the Building 3430 Filtered Exhaust Stack Sampling Probe Location

Pacific Northwest National Laboratory performed a demonstration to determine the acceptable location in which to place an air sampling probe for emissions monitoring for radionuclides in the exhaust air discharge from the new 3430 Building Filtered Pathway Stack . The method was to adopt the results of a previously performed test series for a system of similar configuration, followed by a partial test on the actual system to verify the applicability of previously performed tests. The qualification criteria included 1) a uniform air velocity, 2) an average flow angle that does not deviate from the axis of the duct by more than 20°, 3) a uniform concentration of tracer gases, and 4) a uniform concentration of tracer particles. Section 1 provides background information for the demonstration, and Section 2 describes the test strategy, including the criteria for the applicability of model results and the test matrix. Section 3 describes the flow angle test and the velocity uniformity test, Section 4 provides the test results, and Section 5 provides the conclusions. Appendix A includes the test data sheets, and Appendix B gives applicable qualification results from the previously tested model stack. The data from the previously tested and similarly designed stack was demonstrated to be applicable to the current design for the 3430 Building Filtered Pathway stack. Therefore, this new system also meets the qualification criteria given in the ANSI/HPS N13.1 standard. Changes to the system configuration or operations outside of the bounds of this report (e.g., exhaust velocity increases, relocation of sample probe) will require retesting/reevaluation to determine compliance to the requirements.

54 ENVIRONMENTAL SCIENCES↗

Assessment of the National Research Universal Reactor Proposed New Stack Sampling Probe Location for Compliance with ANSI/HPS N13.1-1999

This document reports on a series of tests conducted to assess the proposed air sampling location for the National Research Universal reactor (NRU) complex exhaust stack, located in Chalk River, Ontario, Canada, with respect to the applicable criteria regarding the placement of an air sampling probe. Due to the age of the equipment in the existing monitoring system, and the increasing difficulty in acquiring replacement parts to maintain this equipment, a more up-to-date system is planned to replace the current effluent monitoring system, and a new monitoring location has been proposed. The new sampling probe should be located within the exhaust stack according to the criteria established by the American National Standards Institute/Health Physics Society (ANSI/HPS) N13.1-1999, Sampling and Monitoring Releases of Airborne Radioactive Substances from the Stack and Ducts of Nuclear Facilities. These criteria address the capability of the sampling probe to extract a sample that represents the effluent stream. The internal Pacific Northwest National Laboratory (PNNL) project for this task was 65167, Atomic Energy Canada Ltd. Chalk River Effluent Duct Flow Qualification. The testing described in this document was guided by the Test Plan: Testing of the NRU Stack Air Sampling Position (TP-STMON-032).

21 SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS↗

Assessment of the 3410 Building Filtered Exhaust Stack Sampling Probe Location

Pacific Northwest National Laboratory performed several tests in the exhaust air discharge from the new 3410 Building Filtered Exhaust Stack to determine whether the air sampling probe for emissions monitoring for radionuclides is acceptable. The method followed involved adopting the results of a previously performed test series from a system with a similar configuration, followed by several tests on the actual system to verify the applicability of the previously performed tests. The qualification criteria for these types of stacks include metrics concerning 1) uniformity of air velocity, 2) sufficiently small flow angle with respect to the axis of the duct, 3) uniformity of tracer gas concentration, and 4) uniformity tracer particle concentration.

54 ENVIRONMENTAL SCIENCES↗

Reference document for LANL stack sampling and ANSI N13.1 (Article) Gielow RL and McNamee MR 1993. Numerical Flue Gas Flow Modeling for Continuous Emissions Monitoring Applications. EPRI CEM Users Group Meeting. Baltimore. RP1961-13

American National Standard N13.1 “sets forth guidelines and performance criteria for sampling the emissions of airborne radioactive substances in the air discharge ducts and stacks of nuclear facilities. Emphasis is on extractive sampling from a location in a stack or duct where the contaminant is well mixed. At such a location, sampling may be conducted at a single point. This standard provides performance-based criteria for the use of air sampling probes, transport lines, sample collectors, sample monitoring instruments, and gas flow measuring methods. This standard also covers sampling program objectives, quality assurance issues, developing air sampling action levels, system optimization, and system performance verification. Workplace, containment, and environmental air monitoring are not addressed. Specific sample analysis methods and the reporting or interpreting of results are also not addressed.” (HPS 2011).

61 RADIATION PROTECTION AND DOSIMETRY↗

Assessment of the Group 5-6 (LB C2, LB S2, LV S1) Stack Sampling Probe Locations for Compliance with ANSI/HPS N13.1 1999

This document reports on a series of tests to assess the proposed air sampling locations for the Hanford Tank Waste Treatment and Immobilization Plant (WTP) Group 5-6 exhaust stacks with respect to the applicable criteria regarding the placement of an air sampling probe. The LB-C2, LV-S1, and LB S2 exhaust stacks were tested together as a group (Test Group 5-6) because the common factor in their design is that the last significant flow disturbance upstream of the air sampling probe is a reduction in duct diameter. Federal regulations( ) require that a sampling probe be located in the exhaust stack according to the criteria of the American National Standards Institute/Health Physics Society (ANSI/HPS) N13.1-1999, Sampling and Monitoring Releases of Airborne Radioactive Substances from the Stack and Ducts of Nuclear Facilities. These criteria address the capability of the sampling probe to extract a sample that represents the effluent stream. The testing on scale models of the stacks conducted for this project was part of the River Protection Project—Waste Treatment Plant Support Program under Contract No. DE-AC05-76RL01830 according to the statement of work issued by Bechtel National Inc. (BNI, 24590-QL-SRA-W000-00101, N13.1-1999 Stack Monitor Scale Model Testing and Qualification, Revision 1, 9/12/2007) and Work Authorization 09 of Memorandum of Agreement 24590-QL-HC9-WA49-00001. The internal Pacific Northwest National Laboratory (PNNL) project for this task is 53024, Work for Hanford Contractors Stack Monitoring. The testing described in this document was further guided by the Test Plan Scale Model Testing the Waste Treatment Plant LB-C2, LB-S2, and LV-S1 (Test Group 5-6) Stack Air Sampling Positions (TP-RPP-WTP-594). The tests conducted by PNNL during 2009 and 2010 on the Group 5-6 scale model systems are described in this report. The series of tests consists of various measurements taken over a grid of points in the duct cross-section at the designed sampling probe locations and at five duct diameters up and downstream from the design location to accommodate potential construction variability. The tests were done only at the design sampling probe location on the scale model of LB-S2 because that ductwork was already constructed. The ANSI/HPS N13.1-1999 criteria and the corresponding results of the test series on the scale models are summarized in this report.

11 NUCLEAR FUEL CYCLE AND FUEL MATERIALS↗

Assessment of Waste Treatment Plant Lab C3V (LB-S1) Stack Sampling Probe Location for Compliance with ANSI/HPS N13.1-1999

This report documents a series of tests used to assess the proposed air sampling location in the Hanford Tank Waste Treatment and Immobilization Plant (WTP) Lab C3V (LB-S1) exhaust stack with respect to the applicable criteria regarding the placement of an air sampling probe. Federal regulations require that an air sampling probe be located in the exhaust stack in accordance with the criteria of American National Standards Institute/Health Physics Society (ANSI/HPS) N13.1-1999, Sampling and Monitoring Releases of Airborne Radioactive Substances from the Stack and Ducts of Nuclear Facilities. These criteria address the capability of the sampling probe to extract a sample that represents the effluent stream.

Air Sampling Probe↗

Assessment of the LV-C2 Stack Sampling Probe Location for Compliance with ANSI/HPS N13.1-1999

This document reports on a series of tests conducted to assess the proposed air sampling location for the Hanford Tank Waste Treatment and Immobilization Plant (WTP) Low-Activity Waste (LAW) C2V (LV-C2) exhaust stack with respect to the applicable criteria regarding the placement of an air sampling probe. Federal regulations require that a sampling probe be located in the exhaust stack according to the criteria established by the American National Standards Institute/Health Physics Society (ANSI/HPS) N13.1-1999, Sampling and Monitoring Releases of Airborne Radioactive Substances from the Stack and Ducts of Nuclear Facilities. These criteria address the capability of the sampling probe to extract a sample that represents the effluent stream. The tests were conducted on the LV-C2 scale model system. Based on the scale model tests, the location proposed for the air sampling probe in the scale model stack meets the requirements of the ANSI/HPS N13.1-1999 standard for velocity uniformity, flow angle, gas tracer and particle tracer uniformity. Additional velocity uniformity and flow angle tests on the actual stack will be necessary during cold startup to confirm the validity of the scale model results in representing the actual stack.

12 MANAGEMENT OF RADIOACTIVE AND NON-RADIOACTIVE W↗

Assessment of the Group 3-4 (HV-S1, HV-S2, IHLW-S1) Stack Sampling Probe Locations for Compliance with ANSI/HPS N13.1-1999

This document reports on a series of tests conducted to assess the proposed air sampling locations for the Hanford Tank Waste Treatment and Immobilization Plant (WTP) Group 3-4 exhaust stacks with respect to the applicable criteria regarding the placement of an air sampling probe. The HV-S1, HV-S2, and IHLW-S1 exhaust stacks were tested together as a group (Test Group 3-4) because they share a geometric attribute: the common factor in their design is that the last significant flow disturbance upstream of the air sampling probe is a jog (i.e., two conjoined bends of equal and opposite curvature resulting in a change in elevation of the duct). Federal regulations require that a sampling probe be located in the exhaust stack according to criteria established by the American National Standards Institute/Health Physics Society (ANSI/HPS) N13.1-1999, Sampling and Monitoring Releases of Airborne Radioactive Substances from the Stack and Ducts of Nuclear Facilities. These criteria address the capability of the sampling probe to extract a sample that represents the effluent stream.

Glissmeyer, John A.↗