Search NASASearch

SEARCH · Search NASA

Results for “unbalanced faults”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

A Novel Protection Scheme for Unbalanced Faults in Inverter Dominated Networks: A Computationally Efficient Algorithm for Entry-Level Relays

Microgrids are now a common practice in distribution systems to increase resilience and reliability. However, microgrid protection remains a critical challenge, considering its requirement to operate in both grid connected and islanded, and the variability in fault characteristics under each mode of operation. This paper presents unbalanced power (S unb ) based fault detection algorithm, which considers local voltage and current unbalances to determine faults in the system. S unb is a computationally efficient fault detection algorithm that is suitable for implementation in the programmable logic of entry level protective relays. In addition, the difference in current and voltage unbalance (D n ) is used to determine the fault type. The proposed method demonstrates high sensitivity and selectivity for line-to-ground (LG), line-to-line (LL), and double line-to-ground (LLG) faults, representing the most common faults in distribution systems. It also allows relay coordination with upstream and downstream protection devices in both island and grid connected operation, while preserving grading margins. The same pickup and time multiplier settings of a particular relay for both modes of operation eliminates the need for adaptive settings, which rely on communication networks. Validation was performed with a hardware-in-the-loop (HIL) setup using Typhoon HIL real time simulator interfaced with three entry-level, SEL 751 relays. Results confirmed the algorithm’s ability to discriminate fault conditions, and determine the fault type under both operating modes, maintain fast detection times, and ensure proper protection coordination.

fault classification

End-To-End Decentralized Transmission Line Protection in IBR-Dominated Weak Grids Using Interpretable Data-Driven Methods

Traditional transmission line protection relies on predictable synchronous-based fault signatures, which frequently fail under the non-standard, current-limited fault characteristics of Inverter-Based Resources (IBRs). This study investigates how to achieve secure, communication-free fault isolation in IBR-dominated weak grids without relying on opaque, computationally heavy "black-box" machine learning algorithms. To address this, we propose a novel, standalone, and inherently interpretable data-driven protection framework. Unlike centralized methods requiring multi-terminal communication, this decentralized approach relies solely on local measurements using a hierarchical linear-kernel Support Vector Machine (SVM). The methodology decomposes the protection task into four sequential stages that mimic traditional protection elements: fault detection and fault direction identification, fault type classification, zone classification, and location estimation. This multi-stage architecture allows for specialized feature engineering at each stage, combining high computational efficiency with logic traceability. The framework's end-to-end performance was validated via C-code and PSCAD/EMTDC co-simulation, utilizing a real-world utility network and an OEM black-box IBR model. The proposed relay achieves 97.2% overall accuracy and provides a reliable trip decision within a 2.5-cycle window. The results confirm 100% accuracy in fundamental fault detection, reliable zone selectivity across low to moderate fault resistances, and robust security against non-fault transients, proving its immediate viability for integration into commercial numerical relays.

24 POWER TRANSMISSION AND DISTRIBUTION

In situ studies on heavy ion irradiation and partial oxidation induced stacking faults and nanograins in tungsten nanolaminates

Understanding the microstructural evolution of tungsten (W) under extreme irradiation environments is critical for its application as a plasma-facing material in future fusion reactors. Heavy ion irradiation study offers expedited damage accumulation and thus allows irradiation tolerance property prediction in a short period of time. In this study we explore in situ Kr ion irradiation of W nanolaminates at 800 °C and uncover a complex interplay of irradiation-induced transformations, including the emergence of stacking faults, nanograin formation, and generation of thickened grain boundaries defined as GB regions with the thickness of up to 15 nm. High-resolution transmission electron microscopy studies reveal the formation of extended planar faults and a metastable hexagonal close-packed (hcp) phase within the body-centered cubic (bcc) matrix. These structural transitions are facilitated by irradiation-induced shear. They are further stabilized by the presence of oxygen, which promotes stacking fault formation and vacancy trapping. Elevated temperatures enhance defect mobility, enabling dynamic recrystallization into ultrafine grains and the thickening of GBs due to defect absorption and impurity segregation. These findings unravel non-equilibrium phase transformation pathways in heavy ion irradiated W and highlight the critical role of impurity-mediated defect dynamics in governing its radiation tolerance properties.

Wazeer, Adil [Purdue University]

Utilities Perspective on Protection Challenges with High IBR Penetration

Utilities have seen rapid increase in Solar, Wind, and Battery Energy Storage Resources that interconnect to their electric system through Inverters. Inverter-Based Resources (IBRs) have fault current characteristics that are unlike the fault current response of traditional rotating-machine-based generators, which is well known and repeatable. IBR’s non-traditional fault current behavior is due to the IBR control scheme, which is configured to provide a clean AC output but also protect the inverter’s sensitive power electronics devices from damage, one source of which is overcurrent. This results in low fault current magnitude, low or no negative sequence current injection, the variability of sequence component currents, the variability of voltage with respect to current angles, and the lack of inertia. The control scheme also results in a fault current response that can vary between manufactures and between models of the same manufacturer. High penetration of IBRs can adversely affect the protection schemes applied in areas with high penetration of IBRs. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems. This is mainly because the existing protection elements and practices have been designed based on the fault current response of conventional rotating machines. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This presentation identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. Instead of facing on one issue, we are looking broadly on all the challenges that system protection has experienced with high penetration of IBRs. Based on the IBR response from various utilities during real fault events and gathering perspective from different utility SMEs via questionnaire, the presentation summarizes on gathered data and internal experiences.

24 POWER TRANSMISSION AND DISTRIBUTION

Atomic faulting drives exceptional toughness in low thermal expansion chromium alloys

Endowing functional properties with mechanical responses in traditional metals has been a frontier topic, akin to transforming base metal into gold. Chromium and its alloys, with their functional deficiencies and limited ductility, serve as typical examples. Herein, we report a Cr96Fe4Ge1.3B1 alloy that unifies low thermal expansion (LTE, αl = 1.79 × 10-6 K-1, 200 − 315 K) with exceptional toughness (240.2 J·cm-3). The enhancement in mechanical responses is primarily attributed to layered Cr2B intermetallic precipitates, which ameliorate interfacial cohesion and simultaneously refine the grain structure. The weakened interlayer interactions within the Cr-B layers facilitate the nucleation and movement of numerous tiny stacking faults in precipitates, efficiently alleviating strain energy and resulting in marked work-hardening ability. Additionally, antiferromagnetic fluctuations in the BCC matrix contribute to the unique LTE behavior. This paves the way for the design of high-performance alloys featuring layered-symmetry precipitates.

Yu, Chengyi [University of Science and Technology

Dissecting Disorder: Defect-Driven Structural Complexity in Layered Li3InCl6 Solid Electrolyte

Halide solid electrolytes have emerged as promising candidates for solid-state batteries owing to their high oxidative stability and ionic conductivity. Among them, Li3InCl6 (LIC) has attracted significant attention. However, diffraction patterns of LIC synthesized via different methods exhibit distinct differences particularly at low-angle reflectionsindicative of underlying structural disorder. These variations are attributed to deviations from ideal crystallographic order, especially stacking faults, whose impact on structure and ion transport remains poorly understood. Here, we identify and quantify stacking faults in LIC samples prepared under different synthetic conditions. Using X-ray diffraction and time-of-flight neutron diffraction, we construct and refine stacking fault models that accurately reproduce the experimental diffraction features. LIC samples with higher degrees of stacking faults exhibit only negligible differences in ionic conductivities and activation energies. This indicates that stacking faults have a limited impact on altering the Li+ diffusion pathway along the c-axis, likely due to the high concentration of vacancies in the In layers, while Li+ diffusion remains nearly unchanged in the ab-plane. Our results account for the observed differences in diffraction patterns across samples and provide a quantitative assessment of faulting probabilities and stacking sequences. The insights gained from this study are expected to be broadly applicable to other layered halide solid electrolytes and contribute to a deeper understanding of the role of structural disorder in ion transport.

Liu, Jue [ORNL] (ORCID:000000024453910X)

Building Operation Model (Morpheus) for Dallas Fort Worth Airport (CRADA CRD-19-16301 Final Report)

The primary objective of this project was to leverage digital twin technology to enhance the design and operation of DFW Airport terminals and their associated energy systems. To achieve this, Morpheus, a building digital twin, was developed to guide improvements in airport operations, specifically targeting reductions in peak power demand and overall energy consumption.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI

A Sensitivity-driven Wide Area Protection (SWAP) Coordination Tool for High Penetration of Inverter-based Resources (IBR)

Traditionally, power system generation sources have been composed of synchronous generators, of which the fault current behavior is understood with minimal differences between generation size and types due to the physics of their construction. Present protection schemes and modeling methods are based upon these understood characteristics. Most renewable generation is composed of inverter-based resources (IBR), in which fault current is determined by switching control software and hardware limitations, each of which can vary between manufacturers and even between models of the same manufacturer. The resulting fault current is low in magnitude, low in negative-sequence current, unpredictable phase angles, and is a challenge to model. These characteristics also result in a challenge to traditional protection schemes and fault simulation software. To address several of these concerns, the project has the following goals: 1. Improve IBR models: Improve IBR models used in short circuit (SC) programs to accurately capture the response of IBRs at the bulk power system (BPS) level for fault and protection studies. 2. Develop automation tool: Develop an automation tool that allows engineers to identify protection coordination and sensitivity issues by performing SC and protection coordination studies in a high IBR-penetrated grid by applying variations to the IBR models, faults, contingencies, etc. 3. Develop schemes: Develop new protection mitigation solution schemes that complement the existing protection systems to ensure safe operation of the BPS with higher IBR penetration levels. The project team did not achieve this final goal, as the Department of Energy (DOE) stopped the project early due to changes in DOE funding priorities. The termination notice came at the beginning of the final project phase, while the team was identifying and beginning to investigate protection issues. It should be noted that the team discussed a 100% penetration scenario. However, this scenario would require the use of grid-forming IBR models that are not presently available. Since developing these models requires additional effort, the 100% penetration scenario was not pursued during this project. In the future, developing the methodology and models for the 100% scenario could benefit the industry.

14 SOLAR ENERGY

Utility Experience with Inverter Based Resource Impacts on Transmission Protection

High penetration of inverter-based resources (IBR) can adversely affect the transmission protection schemes in the area. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems because the existing system has been designed based on the fault current response of conventional rotating-machine-based generators. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This report identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. It includes a broad review of all challenges that system protection has experienced so far with high penetration of IBRs. Key issues have been identified based on a survey of different utility protection engineers. Finally, fault event recordings are shown to demonstrate some actual cases of mis-operations of relays near IBRs.

24 POWER TRANSMISSION AND DISTRIBUTION

Unveiling field-transverse spin anisotropy in the spin liquid candidate α-RuCl3 via spin Hall magnetoresistance

α-RuCl3 has emerged as a possible candidate for a quantum spin liquid (QSL) that promises exotic quasiparticles relevant for fault-tolerant quantum computation. Here, we report spin-sensitive transport measurements using a proximal spin Hall metal, platinum (Pt), to probe magnetic moments in the insulator α-RuCl3. We observe spin Hall magnetoresistance (SMR), where both the transverse and longitudinal resistivities exhibit angular oscillations between the in-plane magnetic field and the current, driven by the interplay between the spin Hall effect in Pt and local magnetic moments in α-RuCl3. These oscillations occur from 1.5 to 18 T, covering the zigzag antiferromagnetic, putative QSL, and supposedly partially field-polarized phases. The phase of the SMR oscillations suggests that the local moments, whether static or fluctuating, develop spin anisotropy with a quantization axis in-plane and largely transverse to the magnetic field across all fields from 1.5 to 18 T. Temperature dependence indicates that the spin anisotropy operates at an energy scale similar to that of the reported QSL signatures in α-RuCl3.

Idzuchi, Hiroshi [Tohoku University, Japan]

Evaluation of high-temperature properties of binary, eutectic Ni-X alloys (X = B, Ca, Ce, La, Y, Zr)

We investigated the high-temperature behavior of binary eutectic nickel-base alloys with low-solubility elements, towards developing alloys with new combinations of structural and functional (e.g. thermal or corrosion) properties. Based on thermodynamic screening, we cast binary near-eutectic Ni-B, Ni-Ca, Ni-Ce, Ni-La, Ni-Y, and Ni-Zr alloys and characterized their microstructure and high-temperature properties. All alloys (except Ni-Ca) contain a fine eutectic microstructure, containing submicron alternating lamellae of γ-Ni and continuous intermetallic phases. The eutectic microstructure did not significantly coarsen at 700°C (except for Ni-B), but measurably coarsened in all alloys at 900°C, most quickly in Ni-B, followed by Ni-Ce, Ni-La, Ni-Y, and Ni-Zr. Coarsening in these alloys occurs by fault migration; diffusion within the intermetallic, and its interfacial energy, likely influence coarsening kinetics. At room-temperature, all alloys possess negligible ductility due to the continuous, brittle intermetallic. At 700 and 900°C, the Ni-Zr alloy showed the best combination of strength and ductility. Oxidation experiments at 900°C on Ni-Zr and Ni-Ce revealed heavy internal oxidation of the continuous intermetallic phase. Overall, the Ni-Zr alloy showed good high-temperature coarsening resistance and strength, though ductility and oxidation resistance require improvement for use in structural applications. Possible routes for improving alloy properties via additive manufacturing are discussed.

Ekaputra, Clement [ORNL] (ORCID:0000000307166479)

Sensitivity Analysis of Numerical Modeling Input Parameters on Wind Turbine Loads in Deterministic Transient Load Cases

Aero-hydro-elastic-servo numerical models used to design and analyze wind turbines are based on thousands of variable input parameters that dictate the inflow, aerodynamic, structural, and control characteristics of the system as well as sea state, hydrodynamic, and mooring characteristics for fixed-bottom and floating offshore wind turbines. Each of these parameters has some level of uncertainty, which can significantly impact the predicted loads. Understanding the uncertainty in the inputs is critical to understanding the uncertainty in the outputs. This work demonstrates a screening technique to identify which parameters ultimate loads are most sensitive to so that more focus can be given to quantifying the possible range of those parameters. This technique has been demonstrated previously for different turbine and load case types and is extended here for a floating offshore wind turbine in design load cases with transient events both in the inflow and operations. Each load case features a deterministic gust, including variations in wind speed, direction, and shear. Load cases are considered with an operating turbine as well as with prescribed fault, startup, and shutdown procedures. The study found that key input parameters with a large impact on loads include the length of the gust, the magnitude of direction change and speed in the gust, the initial wind speed, and the shape of the gust profile.

17 WIND ENERGY