Search NASA⌕ Search

SEARCH · Search NASA

Results for “grid forming inverter”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 181 records · Page 10

UNIFI Specifications for Grid-Forming Inverter-Based Resources: Version 3

The UNiversal Interoperability for grid-Forming Inverters (UNIFI) Consortium addresses fundamental challenges facing the integration of grid-forming (GFM) inverters in electric grids alongside rotating machines and other inverter-based resources (IBRs). This document defines a set of UNIFI specifications for GFM IBRs that provides requirements from both a power system level as well as functional requirements at the inverter level that are intended to provide means for the vendor-agnostic operation of GFM IBRs at any scale in electric power systems.

14 SOLAR ENERGY↗

Dynamic Interaction of Grid-Forming and Grid-Following Inverters with Synchronous Generators in Hybrid Power Plants

As the integration of renewable energy resources such as wind and solar generation continues to grow, the use of hybrid power plants with both synchronous machines and power electronic inverters operating in parallel becomes more common. This paper studies the impact on small-signal stability for these pairs of devices, first as an isolated two-device system and then as part of a 9-bus test system. Each operational scenario was studied with both a grid-following inverter and a grid-forming inverter. In each scenario, the state variables associated with the synchronous generator's excitation system were found to be responsible for the inception of instability. These results underscore the importance of accurate modeling of excitation systems when modeling power systems with hybrid power plants.

hybrid power plant↗

Decentralized Distribution System Restoration with Grid-Forming/Following Inverter-Based Resources

The high penetration of distributed energy resources (DERs) in active distribution systems has posed challenges to the centralized distribution system restoration (DSR) strategies in current practice. On the other hand, the advancement in smart inverter technologies enables the bottom-up restoration capability. This paper is motivated to develop a 3-layered hierarchical framework for decentralized DSR, based on the grid-forming (GFM) and grid-following (GFL) grid-edge inverters. The first layer presents the tertiary control, which determines the load pickup schedule and generation dispatch of DERs, using the alternating direction method of the multipliers algorithm. The second layer consists of two control functions: GFM control, which regulates voltage and frequency, establishing a stable grid for GFL inverters to follow; and GFL control, which regulates the real and reactive power. In the third layer, the primary control is proposed to regulate the inverter voltage and current, which is developed based on the virtual oscillator control (VOC). Furthermore, the developed framework is tested in the modified IEEE 13-node test feeder. Two scenarios of grid-connected and islanded operating modes are designed, and simulation results demonstrate the effectiveness of decentralized DSR strategies for controlling grid-edge inverters to enhance the distribution system resilience.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Large-Signal Stability Improvement of Parallel Grid-Forming Inverter-Driven Black Start: Preprint

With the rapid increase of inverter-based resources in modern grids, advanced grid-forming (GFM) inverter capa- bilities, such as system restoration and operation under faults, are urgently needed to realize power electronics-dominant grids at scale. One such capability is inverter-driven black start using GFM inverters. This paper analyzes the ability of two recently proposed advanced GFM controls to help GFM inverters sustain system-wide, off-nominal conditions and remain synchronized until they can overcome the momentary overloading as more GFMs join the process without generator sequence coordination or communications and finally stabilize the grid. Through an extensive set of 1,200 full-order electromagnetic transient simu- lations, we evaluate the black-start process while employing the various GFM inverter controls. The results show that the GFM current limiter and primary control have a significant impact on the stability of the system during dynamic operating conditions and thus impact the success of inverter-driven system restoration.

current limit↗

Evaluation of Optimal Net Load Management in Microgrids Using Hardware-in-the-Loop Simulation

This paper presents the performance evaluation of a net load management (NLM) engine that balances load and generation in an isolated community to power a critical facility after a grid interruption event (e.g., the loss of a large generation unit). This NLM engine is particularly important for microgrid systems because it provides a high-speed, cost-optimal control solution to coordinate grid-forming inverters and to dispatch grid-following inverters and deferrable loads in microgrid systems to enhance grid resilience and reliability. The NLM algorithm cost-optimally dispatches the grid-following inverters and deferrable loads based on the demanded power and load priorities, and the grid-forming inverters use droop control to form system voltages and share active and reactive power. A controller-hardware-in-the-loop platform is developed to evaluate the control performance of the NLM algorithm with two sequential contingency events of lost generation units. The experimental results indicate that the NLM engine can maintain system stability, achieve the targeted system voltage and frequency, and balance load and generation to serve the critical facility with improved system resilience and reliability.

grid-following inverter↗

Evaluation of Optimal Net Load Management in Microgrids Using Hardware-in-the-Loop Simulation

This presentation discusses the performance evaluation of a net load management (NLM) engine that balances load and generation in an isolated community to power a critical facility after a grid interruption event (e.g., the loss of a large generation unit). This NLM engine is particularly important for microgrid systems because it provides a high-speed, cost-optimal control solution to coordinate grid-forming inverters and to dispatch grid-following inverters and deferrable loads in microgrid systems to enhance grid resilience and reliability. The NLM algorithm cost-optimally dispatches the grid-following inverters and deferrable loads based on the demanded power and load priorities, and the grid-forming inverters use droop control to form system voltages and share active and reactive power. A controller-hardware-in-the-loop platform is developed to evaluate the control performance of the NLM algorithm with two sequential contingency events of lost generation units. The experimental results indicate that the NLM engine can maintain system stability, achieve the targeted system voltage and frequency, and balance load and generation to serve the critical facility with improved system resilience and reliability.

droop control↗

Performance Evaluation of a Microgrid System with Grid-Forming and Grid-Following Inverters with Diesel Generators: Insights From Hardware Experiments

This paper presents a comprehensive performance evaluation of a microgrid system integrating grid-forming (GFM) inverters, grid-following (GFL) inverters, and a diesel generator, focusing on their interactions and behavior under various dynamic events. The study is conducted using a pure hardware setup comprising two GFM inverters, one GFL inverter, a diesel generator, load banks, a point of common coupling (PCC), and an emulated main grid. The evaluation specifically examines dynamic scenarios, including voltage jumps, phase jumps, rate of change of frequency (ROCOF), synchronization, and islanding operations, which pose critical challenges to system stability. Among all the tests conducted, the overloading and phase jump tests proved to be the most challenging. The capacity of the DC side is crucial for withstanding overloading and grid disturbance tests; otherwise, GFM inverters frequently trip due to DC undervoltage. Throughout all grid disturbance tests, the diesel generator consistently stands out as the most robust and reliable GFM unit in the system. Overall, insights from these hardware experiments shed light on the response characteristics of different generation types during grid disturbances and identify potential stability concerns in such hybrid microgrid systems.

14 SOLAR ENERGY↗

UNIFI's Grid-Forming (GFM) Inverter Reference Design: A Tutorial on Modeling, Control, and Experimental Implementation of GFM Inverters

The UNIFI Consortium's tutorial on grid-forming (GFM) inverters provides a comprehensive guide to the modeling, control, and experimental implementation of GFM inverters. As the integration of renewable energy accelerates, the transition from traditional grid following (GFL) to GFM inverters is crucial to ensure stable and sustainable power systems. This document outlines a reference design for three-phase and single-phase GFM inverters developed at the University of Texas at Austin. The tutorial also provides step-by-step guidance for accessing and using UNIFI’s GitHub repository, enabling users to design, build, and test GFM inverters efficiently. By fostering collaboration and equipping users with accessible resources, this initiative aims to drive widespread adoption of GFM technology across academia, utilities, and industries.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Influence of Control and Limiter Schemes on Sequence-Domain Fault Models of Grid-Forming Inverter-Interfaced Distributed Generators

Unlike synchronous generators, the fault response of grid-forming (GFM) inverter-interfaced distributed generators (IIDGs) is notably governed by the selection of control and current limiting strategies rather than inherent physical traits. While recent research has focused on the sequence domain fault model of GFM IIDGs, a research gap exists in elucidating the influence of control and current limiting schemes on this model's characteristics. This article aims to fill this void by examining how different control and current limiting schemes influence the positive and negative sequence impedances in the phasor-domain fault model of GFM IIDGs. This investigation encompasses droop-based, virtual synchronous machine-based, and virtual oscillator-based reference generation controls alongside rotating and stationary reference-frame-based voltage controls. Furthermore, saturation-based, latching-based, circular and virtual impedance-based current limiting schemes are analyzed. To achieve this goal, a thorough numerical simulation study is conducted. Findings indicate that outer reference generation controls exhibit minimal impact. Conversely, the choice of voltage control and various current limiting schemes emerge as the predominant factors shaping the sequence models of GFM IIDGs. These analyses and results are instrumental in devising reliable protection strategies within inverter-based grids, as a comprehensive understanding of electrical elements in the sequence domain is imperative for effective protective measures.

current limiters↗

Efficient Topology Assessment for Integrated Transmission and Distribution Network with 10,000+ Inverter-based Resources

The renewable energy proliferation calls upon the grid operators and planners to systematically evaluate the potential impacts of distributed energy resources (DERs). Considering the significant differences between various inverter-based resources (IBRs), especially the different capabilities between grid-forming inverters and grid-following inverters, it is crucial to develop an efficient and effective assessment procedure besides available co-simulation framework with high computation burdens. This paper presents a streamlined graph-based topology assessment for the integrated power system transmission and distribution networks. Graph analyses were performed based on the integrated graph of modified miniWECC grid model and IEEE 8500-node test feeder model, high performance computing platform with 40 nodes and total 2400 CPUs has been utilized to process this integrated graph, which has 100,000+ nodes and 10,000+ IBRs. The node ranking results not only verified the applicability of the proposed method, but also revealed the potential of distributed grid forming (GFM) and grid following (GFL) inverters interacting with the centralized power plants.

Graph Analysis, Topology evaluation, Infrastructur↗

Advanced grid-forming (GFM) inverter controls, modeling and system impact study for inverter dominated grids

Our main goals in this project are to understand: 1) the stability of the power system with very high penetration of PV or other inverter-based resources (IBR), 2) the interactions among IBRs and traditional generators, and 3) the impact of the GFM inverters on bulk power system. To achieve these goals, we took a holistic research and development approach. First, an impedance-based large system modeling and stability analysis tool was developed to aid the large IBR system small-signal stability analysis. Second, consensus-based control and transient overload ride through were developed to control and coordinate multiple GFM inverters in a large system to maintain transient stability during big grid events. Third, high fidelity electromagnetic transient (EMT) IBR models were developed and integrated into a large reduced WECC model to study the system impact from IBRs. Lastly, extensive validation tests of the GFM control which was developed in this project and implemented in two 1MW commercial solar inverters were performed using different validation platforms, e.g., control hardware-in-the-loop (CHIL) platform, power hardware- in-the-loop (PHIL) platform, and a real PV plant.

14 SOLAR ENERGY↗

Stabilizing the Power System in 2035 and Beyond: Evolving from Grid-Following to Grid-Forming Distributed Inverter Controllers (Final Technical Report)

Under existing grid operations, large synchronous generators provide sufficient rotational inertia to form a rigid backbone for the bulk power system. With photovoltaics (PV) forecasted to provide more than 600 GW of generation by 2050 under the U.S. Department of Energy’s SunShot Initiative objectives, however, it is clear that power electronic inverters will play a dominant role in future systems, and low-inertia stability must be ensured to maintain system reliability. Today, the risks to system stability can be observed on geographically small islands, such as Hawaii, which contain a relatively large amount of installed PV. These risks stem from a fundamental shortcoming of contemporary control strategies—existing inverter controllers cannot guarantee grid stability. Given that future power systems driven by sustainable resources will be characterized by low inertia, locations such as Hawaii provide a glimpse into the obstacles facing future power systems. Considering these challenges, the aim of this project was to develop and demonstrate distributed inverter controllers that enable the reliable control of low-inertia power systems with hundreds of gigawatts of integrated PV.

14 SOLAR ENERGY↗

Interconnection and Interoperability Requirements of Hydrogen Assets to Enable Grid Integration

Traditionally, the inverters used for distributed energy resources (DERs) including solar, energy storage and hydrogen fuel cells are grid following assets. Grid following assets track real power and reactive power setpoints decided by either a local autonomous controller or a remote controller like a microgrid controller. In the past five years, multiple challenges have increased the need for grid forming inverters that can interface to a wide variety of energy resources. These grid forming inverters are becoming critical assets for power systems to enable the replacement of existing rotational machines and provide grid services such as grid resiliency services and black-start. Hydrogen assets (fuel cells) have the potential to successfully replace rotating machines and act as voltage and frequency master by leveraging the long-duration and seasonal energy storage capabilities of hydrogen technologies. This poster presents the progress made in budget period 1 of the proposed work. We will leverage an existing ARIES platform experimental setup to run power-hardware-in-the-loop and controller-hardware-in-the-loop experiments with grid forming fuel cell inverters to develop and document the standardization requirements.

electrolyzer↗

Grid-Forming PV Inverter: Technology Development and Microgrid Applications

Presently, excluding residential backup power applications, grid-forming (GFM) inverters are commercially available for battery energy storage system (BESS) and some PV plus battery systems but not yet for stand-alone PV. This tech update investigates the control design for GFM PV inverter, especially the control required to provide active power reserve and to stabilize the dc link voltage. Subsequently, the use cases of GFM PV plants in utility-level microgrids are discussed considering fully inverter-based microgrids (i.e., with PV and BESS) as well as mixed-source microgrids (i.e., with PV and diesel generator). Scenarios where active power up-reserve from GFM PV plants is beneficial are illustrated. Moreover, requirements and specifications for GFM PV plant, especially for its active power reserve function are developed. In addition, stability of an example utility-level microgrid with two GFM PV plants and a diesel generator is analyzed to shed light on the potential unstable interaction between multiple GFM resources and the countermeasures. This research aims to advance GFM PV technology to offer more flexibility in microgrid design. With GFM PV available, depending on the level of reliability required, cost-benefit analysis, etc., the GFM BESS or diesel generator may be sized smaller while leveraging the full potential of PV generation inside the microgrid.

14 SOLAR ENERGY↗

Parallel Grid-Forming Inverter-Driven Black Start: Power-Hardware-in-the-Loop Validation: Preprint

With power systems encountering increasing deployment levels of inverter-based resources (IBRs), system restoration using grid-forming (GFM) IBRs has gained attention. Engineered to establish grid voltages in the absence of a stiff grid, black-start-capable GFM IBRs are expected to enhance power system resilience by playing a critical role in bottom-up system restoration. This paper experimentally studies the feasibility of the novel approach through power-hardware-in-the-loop (PHIL) testing and validation with a commercial GFM inverter. The PHIL test setup demonstrates an inverter-driven black start of a 5-MW unbalanced distribution feeder where two GFM inverters collectively black start the feeder: one is a commercial hardware GFM inverter interacting through the PHIL interface, and the other is a software GFM emulated by a real-time simulation with full electromagnetic transient (EMT) models. Both GFM inverters are equipped with negative-sequence voltage control to suppress the voltage imbalance resulting from the unbalanced loading, allowing us to study the dynamic interactions between the GFMs with their control parameters unknown. To evaluate the dynamic behavior of the GFM inverters under the entire black-start process, the EMT model of the distribution system details the transformer and motor dynamics to emulate their inrush and startup behaviors. It abstracts conventional grid-connected inverter dynamics, i.e., grid-following inverters. Oscilloscope measurements of the hardware GFM inverter are also presented for critical steps. Takeaways for further study and field deployment are provided.

grid-forming inverter↗

Power-Hardware-in-the-Loop Experiments of a Microgrid With a Grid-Forming Battery Inverter: Preprint

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗