Search NASA⌕ Search

SEARCH · Search NASA

Results for “inverter integration”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 37 records · Page 2

Advanced Measurements for Resilient Integration of Inverter-Based Resources: PROGRESS MATRIX Year-1 Report

As nearly every aspect of the electric power grid undergoes rapid change, measurement technologies that support grid operation and planning must evolve as well. Recent large-scale deployments of inverter-based resources (IBRs) have brought to the forefront the critical need for new measurement technologies. Though these IBRs are vital to achieving the nation’s clean energy goals, their rapid deployment has in some cases led to negative impacts on the reliability and security of the bulk power system (BPS). Advanced power system measurements, including synchronized phasor and waveform measurements, are key to making IBR integration secure and reliable. To this end, the Department of Energy (DOE) initiated a project in 2022 to develop advanced measurement capabilities and analytics that will accelerate adoption of IBRs while improving the reliability and resilience of the BPS. This report discusses a portion of the findings from the project’s first year, which focused on surveying existing measurement capabilities of partner utilities and comparing these capabilities with the requirements of applications that support IBR integration. This report also discusses how these findings will guide the development and demonstration of a set of applications in the project’s second year.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Decentralized Control of Cascaded H-Bridge Inverters for Medium-Voltage Grid Integration: Preprint

This paper introduces a fully decentralized control strategy that allows for individualized active and reactive power control of H-bridge inverters connected in series. After formulating a model of the system power flows, we outline a communications-free approach where each inverter can act on independent commands. Inverter-level feedback is accomplished locally via a measurement of current flowing through the stack. A key feature is the lack of any centralized control routines or phase-locked loop. In this framework, the reactive power control loops achieve voltage synchronization among the converters and the grid, and the active power control loops modulate the terminal voltage amplitudes that influence power delivery. Furthermore, pole placement via state feedback is used to ensure stability of voltage synchronization while also enabling tracking of bidirectional power commands. Simulations are presented to validate the proposed approach.

communication-free modular converter control↗

Visibility-enhanced model-free deep reinforcement learning algorithm for voltage control in realistic distribution systems using smart inverters

Increasing integration of distributed solar photovoltaic (PV) into distribution networks could result in adverse effects on grid operation. Traditional model-based control algorithms require accurate model information that is difficult to acquire and thus are challenging to implement in practice. Here, this paper proposes a surrogate model-enabled grid visibility scheme to empower deep reinforcement learning (DRL) approach for distribution network voltage regulation using PV inverters with minimal system knowledge. In contrast to existing DRL methods, this paper presents and corroborates the adverse impact of missing load information on DRL performance and, based on this finding, proposes a surrogate model methodology to impute load information utilizing observable data. Additionally, a multi-fidelity neural network is utilized to construct the DRL training environment, chosen for its efficient data utilization and enhanced robustness to data uncertainty. The feasibility and effectiveness of the proposed algorithm are assessed by considering DRL testing across varying degrees of observable load information and diverse training environments on a realistic power system.

14 SOLAR ENERGY↗

MULTI-FIDELITY MODELING AND UNCERTAINTY QUANTIFICATION OF INVERTER BASED RESOURCES IN INTEGRATED T&D SYSTEMS

Uncertainty quantification plays a pivotal role in improving the accuracy and reliability of inverter operation within modern power systems that are increasingly dominated by inverter-based resources (IBRs). IBRs, especially those operating under grid forming (GFM) control, rely heavily on a complex set of control parameters and system measurements to maintain voltage, frequency, and power balance. Traditional deterministic modeling approaches often fail to capture these parameter deviations, potentially resulting in suboptimal control actions, reduced system stability, or even instability under high penetration of IBRs. In this paper, we demonstrate the application of model calibration and uncertainty quantification (UQ) principles to an integrated transmission and distribution (T&D) model involving a GFM converter and provide a framework for prioritizing control improvements, guiding robust design, and informing adaptive strategies that can accommodate real-time variability in system conditions. The proposed approach could be valuable in enhancing the robustness of current and future power systems under increased IBR penetrations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power Electronic Development Challenges for High Power Density Integrated Electric Drive Applications

The ever-increasing demand for compact, efficient, and high-performance traction drive systems for transportation applications has accelerated the development of integrated electric drives. In these systems, the electric machine and inverter are integrated within a single housing, offering significant advantages in electrical performance, volume, weight, cost, and overall system efficiency. Despite these benefits, such high levels of integration introduce a new set of challenges, particularly in power electronic design and component selection. This article presents an in-depth investigation of a highly integrated electric drive architecture with an internal stator-mounted inverter, highlighting key design considerations and trade-offs aimed exclusively at maximizing system power density.Based on a comprehensive review of the literature, the power density of a voltage-source-inverter-driven electric drive is primarily governed by the volumetric contributions of the power modules, heat sinks, and DC-link capacitors. Accordingly, this work focuses on the optimization of these three critical components to enhance the inverter's overall power density. The proposed design achieves a power density of 100 kW/L, demonstrating the effectiveness of the presented approach for next-generation integrated electric drive systems.

33 ADVANCED PROPULSION SYSTEMS↗

A Real-Time ANPC Inverter Digital Twin with Integrated Design-For-Trust

The demand for renewable energy has increased over the last few years, and so has the demand for greater expectations within the energy market. This increasing trend has been accompanied by more significant usage of internet-connected devices (IoT), leading to critical electrical infrastructure being connected to the internet. Implementing internet connectivity with such devices and systems provides benefits such as improving the system's performance, facilitating irregularity and anomaly mitigation, and providing additional situational awareness for enhanced decision-making. However, enhancing the connected system with IoT introduces a drawback – a greater vulnerability to cyber-attacks. Cyber-attacks targeting critical infrastructure in the electrical sector have occurred in the United States and Ukraine. These cyber-attacks highlight and expose vulnerabilities that a system inherits when connecting to the internet. These attacks left thousands of customers without electricity for hours until operators could regain control of the electric utility grid. Therefore, to address the vulnerabilities of an internet-connected power electronic device, this work focused on the hardware layer of the system. Implementing a cyber-control system inside the hardware layer can significantly reduce the possibility of an attacker patching malicious controller firmware into a photovoltaic grid-connected inverter, thus mitigating the likelihood that the inverter becomes inactive a cyber-attack scenario. With this mitigation technique, if a cyberattack is successful and an attacker gains control of the network, a cyber-defense technique is in place to mitigate the impact of the cyber-attack. This additional protection layer was developed based on an innovative concept known as Digital Twin (DT). A DT, in this case, replicates an Active-Neutral Point Clamped (ANPC) inverter and was designed using a hardware language known as VHDL (Very High-Speed Integrated Circuit Hardware Description Language) and applied to Field-Programmable-GateArray (FPGA). The DT is embedded within the FPGA and contained in a controller board, the UCB (Unified Controller Board), developed by the University of Arkansas electrical engineering team. This UCB also contains two Digital Signal Processors (DSPs) responsible for generating associated signals to control an authentic physical inverter. These DSP signals are received and processed by the FPGA that implements the DT of an ANPC; in other words, it simulates in realtime the expected output of an actual ANPC inverter using the signals from the DSP. When a new firmware is ready to be patched, the DT provides output signals simulating behavior that a real ANPC inverter would generate with the new firmware. The new firmware is tested to check if it meets all the operational requirements established using a Design-For-Trust technique (DFTr). If the new firmware fails in at least one of the DFT tests, it is considered malicious and must be rejected. This work is divided into sections, such as Background, which explains the pieces that were used and the strategy behind this work; Process and Procedure, which explains the methodology that was adopted to prove the reliability and effectiveness of this work; Results and Discussion, where the simulations and results are described and explained; followed by Conclusion and Future work section, which concludes this work and adds possible future projects to continue this work further.

do Amaral Custodio, Paulo Vitor↗

Distributed Wind Controls: A Research Roadmap for Microgrids, Infrastructure Resilience, and Controls Launchpad (MIRACL)

The Microgrids, Infrastructure Resilience, and Advanced Controls Launchpad (MIRACL) project’s controls research area aims to expand the benefits from distributed wind (DW) generation assets beyond solely providing low cost power directly to consumers. To make distributed wind turbines operate more effectively there is a need for more advanced ways to control them, allowing power companies, businesses, and energy consumers to take advantage of the unique characteristics of wind energy. DW can contribute to the safe and secure operation of grid by providing services such as voltage regulation, frequency regulation, spinning reserves, and even black start capabilities. In the larger DER context where much of the research has focused around solar technologies, the inertia available in wind technologies has generally not been considered. For wind turbines to provide these services in an optimal and expanded way, development and demonstration of control methods and communication interfaces within a grid and microgrid framework are required. In this document, NREL led the literature review in collaboration with SNL, of DER controls-focused integration research to establish a baseline for the controls research under the MIRACL project to identify specific control functions to be focused on throughout this project. This literature review focused primarily on the control functions of variable distributed generation, largely pulling from past solar PV and battery controls works, with a specific focus on applicability for distributed wind energy systems. The goal of this document is to identify a research roadmap based on the open literature and past national laboratory works to inform advanced wind turbine and power electronics control functions for four use cases: 1) distributed wind in isolated systems, 2) grid-connected microgrids (wind-hybrid systems and islanded operation), 3) behind-the-meter distributed wind applications in the power distribution systems, and 4) front-of-the-meter distributed wind applications in the power distribution systems.

17 WIND ENERGY↗

Adding power of artificial intelligence to situational awareness of large interconnections dominated by inverter‐based resources

Abstract Large‐scale power systems exhibit more complex dynamics due to the increasing integration of inverter‐based resources (IBRs). Therefore, there is an urgent need to enhance the situational awareness capability for better monitoring and control of power grids dominated by IBRs. As a pioneering Wide‐Area Measurement System, FNET/GridEye has developed and implemented various advanced applications based on the collected synchrophasor measurements to enhance the situational awareness capability of large‐scale power grids. This study provides an overview of the latest progress of FNET/GridEye. The sensors, communication, and data servers are upgraded to handle ultra‐high density synchrophasor and point‐on‐wave data to monitor system dynamics with more details. More importantly, several artificial intelligence (AI)‐based advanced applications are introduced, including AI‐based inertia estimation, AI‐based disturbance size and location estimation, AI‐based system stability assessment, and AI‐based data authentication.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid-Forming Inverters: Project Demonstrations and Pilots

Power system operators around the world are pushing the limits of integrating inverter-based resources (IBRs) to very high levels, approaching 100% instantaneous penetration under certain operating conditions. This often applies to smaller power systems with very little or no ac interconnections to other neighboring regions or sometimes to fringes of large balancing areas, such as Denmark or Portugal, within the mainland European power system. These jurisdictions have identified the potential of grid-forming (GFM) technology as a key enabler to support the energy transition with very few or no synchronous generators online. Until recently, practical applications of GFM inverters were limited to microgrids and isolated grids and in smaller grid applications on the order of a few tens of megawatts (MW).

Australia↗

PV Inverter Systems Enabled by Monolithically Integrated SiC based Four Quadrant Power Switch (4-QPS) [BiDFET]

The purpose of this project was to develop a new breed of Power Conversion Systems (PCS) for PV integration that is enabled by the newly developed 4-Quadrant Single Die SiC Power Semiconductor Switches (4-QPS) or also referred to as “Bidirectional FET (BIDFET)”. This work includes semiconductor die development, advanced packaging, converter design, development, and testing of 4-QPS enabled hardware prototypes at 1 kW (for single phase residential application) and 10 kW (for three phase commercial application). The BiDirectional Field-Effect Transistor (BiDFET) can enable circuit topologies requiring four-quadrant switches, that were earlier designed using discrete combinations of MOSFETs, IGBTs, GaN HEMTs, and PiN diodes. The monolithic nature of the BiDFET allows lower device count, smaller switch volume, lower inductance, and simpler packaging, and hence more reliable and commercially viable implementation in power electronics converters. The matrix converter topologies, now feasible using BiDFETs, can eliminate the bulky and unreliable dc link capacitors or inductors required for conventional voltage-source or current-source converters in ac–ac and ac–dc applications. The 1.2 kV BiDFET has the potential to disrupt all the applications utilizing 1.2 kV switches, including electric vehicle (EV) drivetrain, bidirectional EV chargers, industrial motor drives, solid-state transformers, datacenter power supplies, elevator drives, dc microgrids, energy storage grid integration, solid-state breakers, etc.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Deep Learning-Based Failure Prognostic Model for PV Inverter Using Field Measurements

Here, this study presents a novel approach for the precise monitoring and prognosis of photovoltaic (PV) inverter status, which is crucial for the proactive maintenance of PV systems. It addresses the gaps in traditional model-based methods, which tend to neglect the overall reliability of inverters, and the limitations of data-driven approaches that largely depend on simulated data. This research presents a robust solution applicable to real-world scenarios. The proposed data-driven model for PV inverter failure prognosis employs actual inverter measurements, integrating various operational and weather-related factors based on domain knowledge. This approach effectively represents inverter stressors and operational status. Utilizing an Enhanced Siamese Convolutional Neural Network (ESCNN), the model merges operational data with domain knowledge features, redefining the prognosis challenge as a classification task. Furthermore, the paper discusses an ESCNN-based real-time inverter failure monitoring method developed on the well-trained model. The proposed models are rigorously trained and tested with real inverter data and a novel filtering method is included to address accidental failures in practical scenarios. The results validate the model's efficacy, and the directions for future research are also outlined.

42 ENGINEERING↗

Fault-Tolerant Decentralized Control for Large-Scale Inverter-Based Resources for Active Power Tracking

Integration of inverter-based resources (IBRs) which lack the intrinsic characteristics such as the inertial response of the traditional synchronous-generator (SG)-based sources presents a new challenge in the form of analyzing the grid stability under their presence. While the dynamic composition of IBRs differs from that of the SGs, the control objective remains similar in terms of tracking the desired active power. This letter presents a decentralized primal-dual-based fault-tolerant control framework for the power allocation in IBRs. Overall, a hierarchical control algorithm is developed with a lower level addressing the current control and the parameter estimation for the IBRs and the higher level acting as the reference power generator to the low level based on the desired active power profile. The decentralized network-based algorithm adaptively splits the desired power between the IBRs taking into consideration the health of the IBRs transmission lines. The proposed framework is tested through a simulation on the network of IBRs and the high-level controller performance is compared against the existing framework in the literature. The proposed algorithm shows significant performance improvement in the magnitude of power deviation and settling time to the nominal value under faulty conditions as compared to the algorithm in the literature.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Battery inverter experimental data

The increase in power electronic based generation sources require accurate modeling of inverters. Accurate modeling requires experimental data over wider operation range. We used 30 kW off-the-shelf grid following battery inverter in the experiments. We used controllable AC supply and controllable DC supply to emulate AC and DC side characteristics. The experiments were performed at NREL's Energy Systems Integration Facility. Inverter is tested under 100%, 75%, 50%, 25% load conditions. In the first dataset, for each operating condition, controllable AC source voltage is varied from 0.9 to 1.1 per unit (p.u) with a step value of 0.025 p.u while keeping the frequency at 60 Hz. In the second dataset, under similar load conditions (100%, 75%, 50%, 25% ), the frequency of the controllable AC source voltage was varied from 59 Hz to 61 Hz with a step value of 0.2 Hz. Voltage and frequency range is chosen based on inverter protection. Voltages and currents on DC and AC side are included in the dataset.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Split phase inverter data

The increase in power electronic based generation sources require accurate modeling of inverters. Accurate modeling requires experimental data over wider operation range. We used 8.35 kW off-the-shelf grid following split phase PV inverter in the experiments. We used controllable AC supply and controllable DC supply to emulate AC and DC side characteristics. The experiments were performed at NREL's Energy Systems Integration Facility. Inverter is tested under 100%, 75%, 50%, 25% load conditions. In the first dataset, for each operating condition, controllable AC source voltage is varied from 0.9 to 1.1 per unit (p.u) with a step value of 0.025 p.u while keeping the frequency at 60 Hz. In the second dataset, under similar load conditions (100%, 75%, 50%, 25% ), the frequency of the controllable AC source voltage was varied from 59 Hz to 61 Hz with a step value of 0.2 Hz. Voltage and frequency range is chosen based on inverter protection. Voltages and currents on DC and AC side are included in the dataset.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modeling of Grid-Forming and Grid-Following Inverters for Dynamic Simulation of Large-Scale Distribution Systems

Historically, distribution system planning studies mainly focused on steady state and quasi-steady state analysis, with limited attention paid to dynamic analysis. This paper develops three-phase, electromechanical models for both grid-forming and grid-following inverters, and integrates them into an open source, three-phase distribution network solver, thereby enabling dynamic simulation of large-scale, three-phase unbalanced distribution systems with high penetration of inverter-based DERs. The proposed inverter models are validated against electromagnetic simulation and field test data from the CERTS/AEP microgrid testbed, and simulated in an islanded 5252 node distribution system in the GridLAB-D simulation environment. Simulation verifies the effectiveness of the proposed inverter models for large-scale distribution system analysis. Finally, study results show that compared to traditional grid-following inverters, the high penetration of grid-forming inverters can improve the voltage and frequency stability of islanded distribution systems.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Small-Signal Stability of Grid-Forming Inverters Using Current-Limiting and Frequency Stabilization

This paper presents a small-signal stability analysis of grid-forming (GFM) inverters under current-limiting conditions. It examines how adjustments in virtual impedance angles, implemented through advanced current-limiting and frequency stabilization techniques, influence small-signal stability. This paper studies a GFM inverter control integrating a fictitious power technique stabilizing primary control by adding a virtual power term and a hybrid current limiter integrating virtual impedance in the anti-wind-up feedback with current reference saturation limiting. A small-signal model is developed to assess the impact of virtual impedance angles on GFM inverter dynamics during grid disturbances, such as voltage drops. The findings indicate that although increasing the virtual impedance angle (to make it more inductive) enhances large-signal stability and voltage support during faults, it can induce oscillations and lead to instability if the angle exceeds certain thresholds. Based on the small-signal models, this paper provides design considerations for the current-limiter impedances to ensure reliable GFM inverter behavior under grid disturbances while maintaining small-signal stability.

current limiting↗

Multi-Objective Boundary Analysis of Discrete and Integrated SiC FET Modular Non-inverting Buck and Boost Converters for Fuel Cell EVs

This paper presents a multi-objective analysis of discrete and integrated SiC FET-based non-inverting buck-boost converter modules for modular fuel cell electric vehicle (EV) systems. Two converter ratings, 60 kW and 90 kW, are evaluated for both implementations, scalable up to 420 kW and 450 kW, respectively. Performance is assessed across efficiency, volumetric and gravimetric power density, cost, thermal stress, and estimated lifetime, where lifetime is derived from SiC FET B10 power-cycling data and junction temperature variations at rated power. A normalized overall performance index combined with a Pareto-boundary framework is used to identify configurations that optimally balance competing objectives. Results show that most configurations lie on the Pareto front, providing balanced trade-offs, while certain high-power discrete (90 kW at 450 kW) and integrated (60 kW at 180−420 kW) configurations are dominated. In general, discrete modules are more favorable for lower-power modular systems due to higher power density and lower cost, whereas integrated modules become more advantageous at higher power levels due to improved thermal behavior and longer lifetime. These findings provide practical design guidance for scalable fuel cell converter architectures and highlight the importance of system-level trade-offs in modular power electronics design.

Asa, Erdem [ORNL] (ORCID:0000000190884812)↗