Power-Hardware-in-the-Loop Experiments of a Microgrid With a Grid-Forming Battery Inverter: Preprint

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Demonstration of Power System Black Start with Hydropower Generator and Battery Energy Storage: Preprint

Battery energy storage systems (BESS) are an important asset for power systems with high integration levels of renewable energy, and they can be controlled to provide various services to the grid. This paper presents the hardware demonstration and characterization of using a utility-scale BESS with grid-following (GFL) and grid-forming (GFM) controls and a run-of-river (ROR) hydropower plant to perform a bottom-up power system black start that enhances power systems' resiliency. ROR hydropower plants are generally not used for power system restoration due to their frequency instability during islanded operation; however, BESS with droop control can provide critical damping to convert a ROR hydropower generator into a blackstart- capable unit. To demonstrate this, we carry out hardware experiments at the megawatt-scale integrating a synchronous generator driven by a dynamometer, an actual GFL/GFM BESS, a medium-voltage impedance network, and a load bank. The demonstration shows the different roles of BESS with GFL and GFM control in power system restoration. GFL BESS can suffer from high-frequency oscillations, even instability, depending on the droop control gain and loading condition. The results provide further insights for system operators on how GFL- or GFMcontrolled BESS can enhance grid stability and how hydro-BESS hybrids can operate as a black-start-capable unit. The presented experimental results are also a valuable resource to understand the different stability characteristics of real-world BESS with different control modes.

24 POWER TRANSMISSION AND DISTRIBUTION↗

MULTI-FIDELITY MODELING AND UNCERTAINTY QUANTIFICATION OF INVERTER BASED RESOURCES IN INTEGRATED T&D SYSTEMS

Uncertainty quantification plays a pivotal role in improving the accuracy and reliability of inverter operation within modern power systems that are increasingly dominated by inverter-based resources (IBRs). IBRs, especially those operating under grid forming (GFM) control, rely heavily on a complex set of control parameters and system measurements to maintain voltage, frequency, and power balance. Traditional deterministic modeling approaches often fail to capture these parameter deviations, potentially resulting in suboptimal control actions, reduced system stability, or even instability under high penetration of IBRs. In this paper, we demonstrate the application of model calibration and uncertainty quantification (UQ) principles to an integrated transmission and distribution (T&D) model involving a GFM converter and provide a framework for prioritizing control improvements, guiding robust design, and informing adaptive strategies that can accommodate real-time variability in system conditions. The proposed approach could be valuable in enhancing the robustness of current and future power systems under increased IBR penetrations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Autonomous Inverter Controls for Resilient and Secure Grid Operation: Vector Control Design for Grid Forming

The project addresses both fundamental and practical challenges of GFM/GFL inverter control for the power grids with high inverter based resources (IBRs) penetration. A data- driven modeling technique is applied to accurately model dynamics of PWM inverters, including electromagnetic-transient (EMT). Systematic and integrative designs of grid- forming (GFM) and grid-following (GFL) primary controls are developed to guarantee system performance under either normal or abnormal operating conditions without violating constraints. This modeling and control framework provides black-start capability in case of an outage without relying on rotating generators, and its secondary control is also shown to enhance resilience against cyber-physical attacks.

14 SOLAR ENERGY↗

Scalable training of trustworthy and energy-efficient predictive graph foundation models for atomistic materials modeling: a case study with HydraGNN

We present our work on developing and training scalable, trustworthy, and energy-efficient predictive graph foundation models (GFMs) using HydraGNN, a multi-headed graph convolutional neural network architecture. HydraGNN expands the boundaries of graph neural network (GNN) computations in both training scale and data diversity. It abstracts over message passing algorithms, allowing both reproduction of and comparison across algorithmic innovations that define nearest-neighbor convolution in GNNs. This work discusses a series of optimizations that have allowed scaling up the GFMs training to tens of thousands of GPUs on datasets consisting of hundreds of millions of graphs. Our GFMs use multitask learning (MTL) to simultaneously learn graph-level and node-level properties of atomistic structures, such as energy and atomic forces. Using over 154 million atomistic structures for training, we illustrate the performance of our approach along with the lessons learned on two state-of-the-art US Department of Energy (US-DOE) supercomputers, namely the Perlmutter petascale system at the National Energy Research Scientific Computing Center and the Frontier exascale system at Oak Ridge Leadership Computing Facility. The HydraGNN architecture enables the GFM to achieve near-linear strong scaling performance using more than 2000 GPUs on Perlmutter and 16,000 GPUs on Frontier.

97 MATHEMATICS AND COMPUTING↗

Optimization-Based Model Reduction Scheme for Renewable Energy Power Plants Using Standardized Testing Scenarios

This paper presents an optimization-based model reduction scheme for renewable energy (RE) power plants consisting of inverter-based resources (IBRs) operating in grid-following (GFL) or grid-forming (GFM) modes. More importantly, the datasets feeding the optimization-based model reduction scheme are generated and re-used through the standardized grid-interactive testing scenarios. Particularly, the proposed scheme makes use of the power plant point of common coupling (PCC) measurements of various quantities specified by standardized tests (e.g., voltage and frequency ride through) as per IEEE 2800, to estimate the parameters of the reduced-order model such that its dynamic performance aligns with the original detailed power plant model. The proposed model reduction approach does not require the parameters of individual IBRs and using standardized test data as input to the formulated optimization problem simplifies the reduced-order modelling scheme. Extensive case studies following standardized test scenarios verified the remarkable accuracy of the proposed approach.

Yallamilli, Ram S. [Purdue University]↗

Small-Signal Stability Constrained Optimal Power Flow of Inverter-Dominated Power Systems with Flexible Operation Mode Selection

Given the intermittence and low inertia nature of inverter-based resources (IBRs), modern power systems with high penetration of IBRs challenge the conventional optimal power flow (OPF) analysis and the system may experience unexpected failures if stability constraints are not incorporated. This study proposes a small-signal stability-constrained OPF (SSSC-OPF) with flexible operation mode selection between grid-forming (GFM) and grid-following (GFL) modes for IBRs to address these challenges. The approach aims to maintain system stability with a sufficient stability margin while minimizing operation costs. The effectiveness of the proposed method is validated through extensive case studies on the IEEE 14-bus system. The results demonstrate that the proposed method is able to support system-level power flow analysis, reduce generation costs, and ensure stability under various disturbances.

grid-following↗

Grid Forming Control of PMSG-based Wind Turbines under Fault Conditions

Grid-forming control is widely envisioned as core technology ensuring stable operation of future power systems with increasing deployment of converter-interfaced renewable generation. However, research on grid forming control of wind turbines, especially under faults, is still in its early stages. In this context, this paper augments dual-port grid-forming control for type IV wind turbines with auxiliary controls to enable reliable fault ride through capabilities. In particular, the proposed control does not require a dc chopper or mode switching to grid-following control. Instead, energy-balancing dual-port GFM control is augmented with active rotor speed damping control and threshold virtual impedance for current limiting during faults. Different operating conditions of wind turbines are considered in a detailed electromagnetic transient simulation study to validate the effectiveness of the proposed control.

Lyu, Xue↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: Droop, Virtual Synchronous Machine (VSM), and dispatchable Virtual Oscillator Control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy, and with no explicit tuning of the solver, lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

electromagnetic transient simulation↗

Wideband Impedance Passivation of MMCs for Suppressing Harmonic Oscillations

Harmonic instability and associated oscillation events have become one of the main concerns in MMC-based HVdc systems. These oscillations can appear in the range from a few hundred hertz to several kilohertz, and the root cause is identified as delay-induced negative damping of MMC impedance appearing at the system resonance frequency. Here, this paper introduces a wideband impedance reshaping method through MMC control to eliminate such negative damping for both grid-following (GFL) and grid-forming (GFM) MMCs, which makes the MMC impedance completely passive from the second harmonic frequency upward, thus preventing all harmonic oscillations. First, simplified impedance models of MMCs are derived for the harmonic stability analysis and the impedance reshaping control design. Next, a passivity-based impedance reshaping method is presented, as well as practical considerations for its implementation. In addition, to maintain the MMC's disturbance ride-through capability, an adaptive activation scheme is developed, which enables the wideband impedance reshaping control only in the presence of harmonic oscillation events. The effectiveness of the proposed method is validated by frequency domain analysis and by electromagnetic transient (EMT) simulations of two typical MMC-based power systems.

17 WIND ENERGY↗

UPS XML Format and Data

This is the XML data and format for UPS supercomponent including subcomponents: Grid following inverter (GFL), Grid forming inverter (GFM), and dc-dc converter connected to the energy storage and the AI load.

Marthi, Phani Ratna Vanamali [ORNL] (ORCID:0000000↗

Inverter-Based Power Systems From an Electric Circuit Perspective

This presentation reports a twin circuit theory that enables us to interpret power system dynamics from a electric circuit perspective. Our proposed twin circuit theory can roughly prove the dissipating energy flow (DEF) method, and shows the positive impacts of well-designed grid-forming (GFM) inverters on power systems stability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Study of the Protection Improvements for a Weak Grid Area With High Inverter-Based Resources (IBRs)

This project designs enhanced protection scheme for the real-world weak grid area with a high penetration of IBRs. As the existing protection schemes are originally designed for traditional synchronous machines, we first evaluate if the protection scheme will continue to operate reliably in systems with high levels of IBRs. Hardware relays are tested using a controller-hardware-in-the-loop setup. PSCAD electromagnetic transient simulation with IBR original equipment manufacturer black-box models is used to perform fault studies and generate COMTRADE data, which are replayed by a real-time digital simulator (RTDS) to feed input to the hardware relays. Three scenarios are analyzed: normal operation, an N-1 contingency, and an IBR-only scenario. The evaluation results reveal the following: 1) the protection scheme remains reliable under normal conditions and N-1 contingencies and 2) in IBR-only scenarios, differential protection (87L) continues to operate reliably, whereas local protection elements, such as distance and directional elements, fail because of the lack of regulated negative sequence current contributed by IBRs. Enhanced protection is designed to address the challenge of lack of negative sequence current from IBRs, including increased restraining factors a2 and k2 to block 32Q or using V instead QV ORDER for ground faults, enhanced mho distance element with voltage and phase angle supervision for L-L faults. The efficacy of enhanced protection logic is validated and proven to work reliably. Additionally, IEEE Std. 2800-2022 negative sequence current compliant GFL and GFM IBRs from another vendor are tested and proven to work reliably without need for enhanced logic. Therefore, this work provides valuable decision-making for utilities facing protection system challenges due to IBRs, either designing enhanced protection scheme or requesting their IBRs being IEEE Std. 2800-2022 compliant to produce regulated negative sequence current for protection relay to make correct decision.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Field Verification of Grid-Forming Inverter-Based Power Plant Performance for Transmission System Reliability

This report describes some examples of the operation of two grid-forming (GFM) inverter-based photovoltaic-battery hybrid power plants connected to the electric system of the island of Kauai in Hawaii. Both plants are photovoltaic power plants with battery energy storage and are connected to the networked transmission system operated by Kauai Island Utility Cooperative (KIUC), along with several other power plants including an oil-fired plant, diesel generators, small hydroelectric plants, a biofuel plant, and several other photovoltaic plants.

14 SOLAR ENERGY↗

BIL GRID-READY WIND: Reliable and Economical Grid Services Design, Implementation, and Demonstration at the Great Pathfinder Wind Power Plant

The GRID-READY WIND project aimed to demonstrate the ability of utility-scale wind power plants (WPPs) to deliver traditional and emerging grid services (GSs) in both grid-following (GFL) and grid-forming (GFM) modes through a centralized control framework, supplemented by local control adjustments at the wind turbine generator as needed. Throughout the project, the team offered recommendations on how the grid services demonstrated with WPPs could be applied to other inverter-based resources (IBRs), such as photovoltaic (PV) systems and battery energy storage systems (BESS), while considering the unique dynamics of these resources arising from their energy generation characteristics. The project sought to enhance the confidence of system operators (SOs) and planners in utilizing WPPs, alongside other IBRs such as PV plants and BESS, to provide essential grid services over extended periods under diverse operating conditions, thereby supporting their integration into the bulk power system.

17 WIND ENERGY↗

Equivalent-Circuit Models of Grid-Forming IBRs for Electromagnetic-Transient Simulations: Preprint

We derive equivalent-circuit models of control- and physical-layer subsystems of grid-forming (GFM) inverter-based resources (IBRs) for electromagnetic-transient (EMT) simulations. Three different primary controllers are considered: droop, virtual synchronous machine (VSM), and dispatchable virtual oscillator control (dVOC). In addition, the models include cascaded voltage- and current-control loops, and LCL output filters. Simulations for a single-inverter setup and for a network of five inverters in a modified IEEE 14-bus topology are presented. The equivalent-circuit models simulated with analog electronic circuit-simulator software (in our case, LTspice) offer the same accuracy with up to 150x lower computational burden compared to block-diagram-based implementations in commercial off-the-shelf EMT software (in our case, MATLAB-Simulink).

circuit-equivalent model↗

Studying the Impact of IBR Modeling on the Commonly Applied Transmission Line Protective Elements

It is a well-accepted fact that detailed inverter-based resource (IBR) models are needed for electromagnetic transient (EMT) studies, especially for protection studies and protection designs. However, it is not clear which modeling aspects should be included in the EMT model to accurately represent the IBR fault responses. Therefore, this paper addresses this gap by evaluating the impact of key modeling aspects (DC source, inverter model, power control, current/voltage control, and current limiting) on the response of protective relay elements both qualitatively and quantitatively. Both grid-following (GFL) and grid-forming (GFM) IBR models are comprehensively evaluated through a simplified real-world transmission network by varying the IBR modeling aspects, fault locations, and types. The insights and findings from this paper will benefit the power system protection community because this work provides modeling requirements and guidelines for IBR modeling so that correct IBR models will be used for protection scheme settings design.

grid-following inverter↗