Search NASA⌕ Search

SEARCH · Search NASA

Results for “grid following”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 127 records · Page 7

Study of Inverter Control Strategies on the Stability of Low-Inertia Microgrid Systems

This paper investigates the stability of low-inertia microgrid systems with two control strategies that have different percentages of grid-forming (GFM) inverters. The first control strategy has approximately 50% GFM inverters, and all the battery inverters are working in GFM control mode. Originally, the second control strategy has approximately 10% GFM inverters, with only two battery inverters working in GFM control mode and the rest working in grid-following (GFL) PQ control mode based on current control, which cannot stabilize the microgrid system. Then, the second control strategy is modified to change the GFM inverters from droop control to isochronous control and the GFL battery inverters from traditional current control to voltage control for power control. Both control strategies can maintain system stability; however, the first control strategy can better handle contingency events. The study indicates that 1) a microgrid system with a higher percentage of GFM inverters has better stability; and 2) a microgrid with a lower percentage of GFM inverters can have poor stability, but improved control strategies in inverters can improve system stability. This study improves the understanding of how different percentages of GFM inverters and inverter control strategies affect the system stability of low-inertia microgrids.

droop control↗

Study of Inverter Control Strategies on the Stability of Microgrids Toward 100% Renewable Penetration: Preprint

This paper investigates microgrid transient stability with mixed generation - synchronous generator (SG), grid-forming (GFM) and grid-following (GFL) inverters - under increasing penetration levels toward a 100% renewable generation microgrid. Specifically, the dynamics of a microgrid with an SG and GFL inverter(s), an SG with GFM inverter(s), and an SG with GFM and GFL inverters under each penetration are evaluated with an electromagnetic transient study with two critical dynamic events: unplanned islanding and switching in a pumped induction motor load. Analysis and simulation results indicate that the microgrid with GFL inverters running in parallel with the SG can provide a faster power response than the GFM inverters to compensate for the deviations of the frequency and voltage. The scenario with the mixed SG, GFM, and GFL inverter has the best transient and steady-state stability toward 100% inverter-based resource (IBR) penetration. This comprehensive study provides helpful references for microgrid engineers to understand the microgrid stability when facing various choice of installing IBRs (GFL, GFM, or mixed).

droop control↗

Study of Inverter Control Strategies on the Stability of Microgrids Toward 100% Renewable Penetration

This paper investigates microgrid transient stability with mixed generation - synchronous generator (SG), grid-forming (GFM) and grid-following (GFL) inverters - under increasing penetration levels toward a 100% renewable generation microgrid. Specifically, the dynamics of a microgrid with an SG and GFL inverter(s), an SG with GFM inverter(s), and an SG with GFM and GFL inverters under each penetration are evaluated with an electromagnetic transient study with two critical dynamic events: unplanned islanding and switching in a pumped induction motor load. Analysis and simulation results indicate that the microgrid with GFL inverters running in parallel with the SG can provide a faster power response than the GFM inverters to compensate for the deviations of the frequency and voltage. The scenario with the mixed SG, GFM, and GFL inverter has the best transient and steady-state stability toward 100% inverter-based resource (IBR) penetration. This comprehensive study provides helpful references for microgrid engineers to understand the microgrid stability when facing various choice of installing IBRs (GFL, GFM, or mixed).

droop control↗

Study of Seamless Microgrid Transition Operation Using Grid-Forming Inverters: Preprint

This paper investigates operational techniques to achieve smooth microgrid (MG) transitions by dispatching the grid-forming (GFM) inverter. In traditional approaches, the GFM inverter must switch between grid-following (GFL) and GFM control mode during MG transition operation. Today's inverter technology allows GFM inverters to always operate in GFM control mode, so it is worthy to explore how to use them to achieve smooth MG transition operation. This paper proposes three operational techniques: a traditional scheme of switching between GFL and GFM control; a new scheme of consistent GFM control and shifting the droop intercept up before islanding operation; and a new scheme of consistent GFM control and shifting the droop intercept up before synchronization operation. A full hardware setup is established to compare the three techniques and showcase their implementations in real-world applications. As expected, the third technique outperforms the others and exhibits the best transition performance because the GFM inverter maintains the same operating points during the transition operation. Therefore, we conclude that ensuring smooth MG transition operation requires the GFM inverter(s) to maintain the same operating points (v, f, P, Q, and phase angle) during the transition operation in addition to minimizes the point of common coupling power flow.

grid-following control↗

PHIL Interface Design for Use With a Voltage-Regulated Amplifier: Preprint

As inverter controls have become increasingly complex, power hardware-in-the-loop (PHIL) has emerged as a leading strategy to thoroughly assess the impact of proprietary inverter controls on a specific power system. The development of a PHIL test bed typically involves the desired inverter, a power amplifier, and a digital real-time simulator (DRTS) to control the simulated power system. As a result of PHIL nonidealities, a form of digital compensation within the DRTS is used, which is commonly referred to as a PHIL interface. The interface design for PHIL test beds has been previously examined in the literature, but many existing methods use older power amplifiers that do not contain internal voltage regulation. These existing interface methods are based around a voltage regulator within the DRTS rather than one preexisting in hardware. In this study, a three-step approach of PHIL interface development for modern power amplifiers with built-in voltage regulation is introduced and validated in hardware with a single 30-kW grid-following inverter.

DRTS↗

Control Parameter Sensitivity Study for Inverter-Based-Resource Dominated Grids: A Small Signal Stability Approach and Framework

The growing adoption of renewable energy is driving the prevalence of inverter-based resources (IBRs) within power grids. Future power grids will integrate both grid-following IBRs (GFM-IBRs) and grid-forming IBRs (GFL-IBRs) alongside synchronous generators. Therefore, it is crucial to perform stability studies that account for all components and especially control interactions related to IBRs. Extensive research has performed to study the IBR-related stability, however, the sensitivity study of IBRs' control parameters on system stability has not been adequately studied yet, especially from a systematic way. Therefore, this paper conducts a small signal stability analysis for a generic grid with multiple types of resources and develops an analytical framework for assessing the sensitivity of control parameters affecting stability margins. To achieve that, the non-autonomous reduced-order non-linear dynamic model is developed for a generic power system with multiple synchronous generator-based resources (SGBRs), GFM-IBRs, and GFL-IBRs. Based on the analytic model, a systematic framework for parametric sensitivity on systems' asymptotic stability is developed. A parameter sensitivity analysis based on eigenvalue methods is proposed. The impact of the droop controllers of GFM-IBRs, PQ-dispatch and the PLL controller of GFL-IBR on the system asymptotic stability is discussed. This sensitivity study is aiming to provide deep insights on control parameters' impact on system stability, and gives direction for parameter tuning in case of instability.

24 POWER TRANSMISSION AND DISTRIBUTION↗

How Inverter-Based Resources (IBRs) Affect Protection Relay Elements

Inverter-based resources (IBRs) exhibit fault responses that differ significantly from those of synchronous generators, which can challenge the reliable operation of many commonly used power system protection elements. The fault response of IBRs is primarily influenced by their control algorithms and configurations, but the impact of these controls on protection relays is not yet fully understood. This presentation provides a comprehensive study of how IBR modeling and controls affect transmission line protection. Key modeling and control aspects include the DC source, inverter model, power level control, current control, and current limiting. The study reveals that certain aspects - such as the type of DC source (battery, PV, or hybrid), inverter model (average vs. switching), and power level control methods (PQ dispatch vs. Vdc-Vac control for grid-following IBRs, and droop vs. VSM for grid-forming IBRs) - do not significantly affect relay response. However, faster control loops, such as current control and current limiting, do influence the relay behavior. Additionally, the study explores the effects of other factors, including momentary cessation, operating points, fast/slow current responses, and grid strength on relay performance. Finally, the study offers recommendations for both IBR and protection engineers to improve IBR fault response and enhance the reliability of protection systems.

14 SOLAR ENERGY↗

A Comprehensive Study of the Impact of Inverter-Based Resource (IBR) Modeling and Control on Protection Relay Elements

Inverter-based resources (IBRs) exhibit fault responses that differ significantly from those of synchronous generators, which can challenge the reliable operation of many commonly used power system protection elements. The fault response of IBRs is primarily influenced by their control algorithms and configurations, but the impact of these controls on protection relays is not yet fully understood. This presentation provides a comprehensive study of how IBR modeling and controls affect transmission line protection. Key modeling and control aspects include the DC source, inverter model, power level control, current control, and current limiting. The study reveals that certain aspects - such as the type of DC source (battery, PV, or hybrid), inverter model (average vs. switching), and power level control methods (PQ dispatch vs. Vdc-Vac control for grid-following IBRs, and droop vs. VSM for grid-forming IBRs) - do not significantly affect relay response. However, faster control loops, such as current control and current limiting, do influence the relay behavior. Additionally, the study explores the effects of other factors, including momentary cessation, operating points, fast/slow current responses, and grid strength on relay performance. Finally, the study offers recommendations for both IBR and protection engineers to improve IBR fault response and enhance the reliability of protection systems.

14 SOLAR ENERGY↗

Operation and Control of a Back to Back Modular Multilevel Converter System for Grid Forming Application with Advanced Grid Support Functionalities

The main focus of this paper is to investigate the possibility of using modular multilevel converter based back-to-back system for grid forming applications. A decentralized hierarchical control architecture with a modified local controller based on nonlinear techniques for grid forming application have been investigated. Grid functionalities based on IEEE 1547-2018 for grid forming converters have been utilized. The local controllers ensure distortion free balanced sinusoidal output voltage on the grid forming side with unbalanced or nonlinear loading condition. The grid following side ensures unity power factor currents under unbalanced grid voltage condition. The dc bus voltage control ensures oscillation free voltage under balanced conditions and control of the average voltage under unbalanced condition. Efficacy of the overall system is verified by modeling the system in MATLAB/Simulink and PLECS domain and the most important case studies are presented.

advanced grid support functionalities↗

The Cause of Insufficient Damping in Phase-Locked-Loop and Its Influence

Phase-locked loop (PLL) is a critical component that synchronizes grid-following (GFL) inverter-based resources (IBR) to the grid. Insufficient damping in PLL has been identified as a cause associated with real-world weak grid stability issues. This paper reveals that the second-order low-pass filter deployed in a sophisticated PLL structure can have negative influence on damping performance and lead to system instability when the grid is weak and power generation is low. Improving the PLL damping is illustrated as one of the mitigation approaches. The dynamic study is carried out in electromagnetic transient (EMT) simulation environment. In addition to EMT demonstration, a simplified analytical model of PLL is developed to represent a PLL with the sophisticated structure. The resulting overall analytical model of the entire system is then used for eigenvalue- based analysis to illustrate the influence of PLL on dynamic modes.

Wang, Zhengyu↗

Power-Hardware-in-the-Loop Experiments of a Microgrid with a Grid-Forming Battery Inverter

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Power-Hardware-in-the-Loop Experiments of a Microgrid With a Grid-Forming Battery Inverter: Preprint

Microgrids continue to proliferate, and they are transitioning away from using conventional generating resources to increasingly relying on inverter-based resources (IBRs) as the voltage and frequency leaders. It is crucial to evaluate the capability of IBRs to provide microgrid stability and resilience. Hardware-in-the-loop (HIL) experiments were conducted to de-risk the field deployment of the San Diego Gas & Electric Company Borrego Springs Microgrid, where a battery inverter was upgraded with grid-forming (GFM) capability to serve as the island leader. This paper presents the HIL experimental results from an HIL test bed that uses a power-hardware-in-the-loop (PHIL) interface with a power inductor that was previously developed for PHIL simulations of microgrids where the inverters need to switch modes, i.e., between grid-following and GFM as the microgrid transitions between grid-connected and islanded operation. This paper presents more details on the interface and HIL simulation results of the planned islanding and load steps in islanded operation to show the effectiveness of the inverters in managing the voltage and frequency.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Large-Scale Hardware Experiment Demonstration of Operating High Inverter-Based Resource Power Systems With Grid-Forming Inverters

This paper presents experimental hardware results from a microgrid system as the penetration level of grid-forming (GFM) inverters increases. The experiment aims to showcase the advantages of GFM inverters in enhancing system stability and to investigate the operational challenges in systems relying entirely on inverter-based resources (IBRs). Five test scenarios are devised to progressively increase GFM inverter penetration levels: 0% (S1), 19% (S2), 37% (S3), 68% (S4), and 100% (S5). To ensure consistency, identical loading conditions and dynamic events are applied across all scenarios. The conducted tests include load step changes, output variation of grid-following (GFL) inverters during islanded mode, transition operations (such as synchronization to the grid and islanding), and rateof- change-of-frequency (ROCOF) and voltage jump tests during grid-connected mode. Key findings from the tests are summarized as follows: (1) Scenario S1 proved most challenging for load steps, and GFL variations because of insufficient GFM capacity, leaving the diesel generator unable to handle transient ridethrough; (2) Scenario S5 was the most difficult for transition operations, because the lack of a diesel generator to maintain stiff bus voltage resulted in unexpected reactive power flows during synchronization, causing the point of common coupling (PCC) breaker to trip; (3) Scenarios S4 and S5 were particularly challenging for ROCOF tests because of minimal system inertia, leading to large transients that triggered breaker trips; and (4) Scenario S4 exhibited the strongest voltage recovery capability because of the presence of the diesel generator and a higher number of GFM inverters, both of which possess the highest capacity for reactive power injection.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Use of Power Hardware-in-the-Loop and Controller Hardware-in-the-Loop to De-Risk the Use Of Grid-Forming Fuel Cell Inverters in Microgrids

Microgrids continue to proliferate, particularly those that rely on inverter-based resources as the microgrid's voltage and frequency leader. Hardware-in-the-loop simulations can de-risk microgrid deployments, and therefore we need power-hardware-in-the-loop (PHIL) interfaces for grid-forming (GFM) inverters to enable simulations of seamless transitions between islanded and grid-connected operation. Such interfaces are particularly challenging when the inverters need to switch modes, i.e., between grid-following (GFL) and GFM as the microgrid transitions between grid-connected and islanded operation. This presentation shows the use of PHIL interfaces for such microgrids and the preliminary experimental results.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Real-time Implementation of Grid Code Compliant Grid Edge Energy Management System

Integrated distributed energy resources (DER) in a distribution system need to follow grid codes to avoid violations that result in DER/circuit segment disconnection. To comply with grid code requirements at the grid edge level, network constrained grid edge energy management system (EMS) can be deployed. The objective of grid edge EMS is to provide economic solution for active and reactive power DER setpoints at each dispatch interval and ensure voltage regulation to support secure interconnection of the grid edge segment to the distribution system with multiple inverter based DER units. In this work, real-time simulation of grid code compliant grid edge EMS is deployed in a realistic feeder circuit segment. For real-time simulation, communication between the grid edge EMS and DERs is done exploiting IEC 61850-7-420. It enables interoperability among different DERs and grid edge EMS. No prior art has deployed IEC 61850-7-420 GOOSE communication protocol for grid edge EMS. Conversion of IEC 61850 GOOSE messages to Modbus communication protocol is also performed to communicate with grid edge EMS in commodity-off the shelf embedded boards in this work. The real-time simulation in OPAL-RT real-time digital simulator shows the out-performance of grid edge EMS by reducing the voltage violation in the distribution circuit.

Energy management system↗

Grid-Forming Frequency Shaping Control for Low-Inertia Power Systems

As power systems transit to a state of high renewable penetration, little or no presence of synchronous generators makes the prerequisite of well-regulated frequency for grid-following inverters unrealistic. Thus, there is a trend to resort to grid-forming inverters which set frequency directly. We propose a novel grid-forming frequency shaping control that is able to shape the aggregate system frequency dynamics into a first-order one with the desired steady-state frequency deviation and Rate of Change of Frequency (RoCoF) after a sudden power imbalance. The no overshoot property resulting from the first-order dynamics allows the system frequency to monotonically move towards its new steady-state without experiencing frequency Nadir, which largely improves frequency security. We prove that our grid-forming frequency-shaping control renders the system internally stable under mild assumptions. The performance of the proposed control is verified via numerical simulations on a modified Icelandic Power Network test case.

control systems↗

Grid-Forming Frequency Shaping Control for Low-Inertia Power Systems

As power systems transit to a state of high renewable penetration, little or no presence of synchronous generators makes the prerequisite of well-regulated frequency for grid-following inverters unrealistic. As such, there is a trend to resort to grid-forming inverters which set frequency directly. We propose a novel grid-forming frequency shaping control that is able to shape the aggregate system frequency dynamics into a first-order one with the desired steady-state frequency deviation and Rate of Change of Frequency (RoCoF) after a sudden power imbalance. The no overshoot property resulting from the first-order dynamics allows the system frequency to monotonically move towards its new steady-state without experiencing frequency Nadir, which largely improves frequency security. We prove that our grid-forming frequency-shaping control renders the system internally stable under mild assumptions. The performance of the proposed control is verified via numerical simulations on a modified Icelandic Power Network test case.

24 POWER TRANSMISSION AND DISTRIBUTION↗