Search NASA⌕ Search

SEARCH · Search NASA

Results for “PHIL”

Search indexed NASA NTRS and DOE OSTI research on propulsion, heat transfer, battery materials and energy systems. Follow report and document links to the original sources.

Quote a phrase for an exact phrase match. Source license links do not imply unrestricted reuse.

At least 19 records

PHIL Interface Design for Use With a Voltage-Regulated Amplifier

Power hardware-in-the-loop (PHIL) has emerged as a leading strategy to thoroughly assess the impact of proprietary inverter controls on a specific power system. The development of a PHIL test bed typically involves an inverter under test, a power amplifier, controllable DC supply, and a digital real-time simulator (DRTS) to simulate the power system under study. As a result of PHIL nonidealities, a form of digital compensation within the DRTS is used, which is commonly referred to as a PHIL interface. Many existing methods use legacy power amplifiers that do not contain internal voltage regulation. These existing interface methods are based around a voltage regulator within the DRTS and do not consider the interaction with the controls in newer amplifiers. In this study, a three-step approach of PHIL interface development for modern power amplifiers with built-in voltage regulation is introduced and is validated in hardware with a 30-kW grid-following inverter.

DRTS↗

PHIL Interface Design for Use With a Voltage-Regulated Amplifier: Preprint

As inverter controls have become increasingly complex, power hardware-in-the-loop (PHIL) has emerged as a leading strategy to thoroughly assess the impact of proprietary inverter controls on a specific power system. The development of a PHIL test bed typically involves the desired inverter, a power amplifier, and a digital real-time simulator (DRTS) to control the simulated power system. As a result of PHIL nonidealities, a form of digital compensation within the DRTS is used, which is commonly referred to as a PHIL interface. The interface design for PHIL test beds has been previously examined in the literature, but many existing methods use older power amplifiers that do not contain internal voltage regulation. These existing interface methods are based around a voltage regulator within the DRTS rather than one preexisting in hardware. In this study, a three-step approach of PHIL interface development for modern power amplifiers with built-in voltage regulation is introduced and validated in hardware with a single 30-kW grid-following inverter.

DRTS↗

Leveraging PHIL for Inverter Functionality Requirement Evaluation to Ensure a Reliable Grid

This presentation showcases NREL's ongoing research on advanced Multi-point Power Hardware-in-the-Loop (PHIL) systems, enabling comprehensive evaluation of interoperability, stability, and wide-area stability in complex power grids. Key features include high-power PHIL capabilities, seamless PHIL Interfaces for effortless Grid-Following (GFL) and Grid-Forming (GFM) mode switching, and advanced multi-domain PHIL/Controller Hardware-in-the-Loop (CHIL) capabilities for evaluating diverse technology mixes, facilitating rigorous testing and validation of emerging power systems for reliable integration, enhanced resilience, and optimal performance.

lab capabilities↗

Customized open source renewable energy models validated through PHIL lab experiments

Energy models for power systems require ongoing updates to reflect advancements in equipment technology and the increasing complexity of power electronic devices. This study utilizes a Power Hardware-in-the-Loop (PHIL) experimental setup to validate custom photovoltaic (PV) inverter models, aiming to enhance and expedite the development of advanced renewable energy models. The research compares the performance of a physical inverter with generic Renewable Energy Source (RES) models recommended by the Western Electricity Coordinating Council (WECC). As inverter-based renewable energy sources become more prevalent in modern electrical grids, it is crucial that dynamic models accurately represent their real-world behavior. Accurate models improve our understanding of these energy resources and their interactions with the grid. The proposed model enhancements are designed to better reflect real inverter performance, based on insights from PHIL experiments. These models are developed using the open source Modelica language and the OpenIPSL Modelica Library, allowing integration across various simulation tools without re-implementation. The paper concludes with a thorough assessment, comparing the enhanced models with PHIL experiments on a real PV inverter in a controlled laboratory setting. As a result, the study provides the enhanced WECC RES models and validation data as open source resources, facilitating further research and development.

Modelica↗

A Power-Hardware-in-the-Loop (PHIL) Evaluation of Service Restoration With Networked Microgrids

This paper describes the power-hardware-in-the- loop (PHIL) evaluation of the feasibility of service restoration solutions determined by the PowerModelsONM.jl tool. This tool incorporates microgrids and the networking of microgrids into its determination of an optimal service restoration solution. The paper presents PHIL simulation results for a case study based on a real distribution feeder with multiple microgrids, showcas- ing the effectiveness of networked microgrids in aiding system restoration after an outage. The study leverages high-fidelity, real- time electromagnetic transient models to ensure accuracy in the simulation results. This work is the final output from the Resilient Operation of Networked Microgrids (RONM) project funded by the U.S. Department of Energy Office of Electricity Microgrid Program and led by Los Alamos National Laboratory. RONM focused on the application of PowerModelsONM.jl to enhance the resilience of distribution systems.

fault location isolation and service restoration (↗

Impedance Analysis and PHIL Demonstration of Reactive Power Oscillations in a Wind Power Plant Using a 4-MW Wind Turbine

This paper presents impedance-based analysis, mitigation, and power-hardware-in-the-loop (PHIL) demonstration of reactive power oscillations in a wind power plant using a 4-MW Type III wind turbine drivetrain. Because such low-frequency oscillations result from interactions among slower control loops of wind turbines regulating phasor quantities—active and reactive power output of the wind turbine and the magnitude of voltages at the point of interconnection (POI)—a new type of admittance is defined in terms of phasor quantities for their analysis. The so-called power-domain admittance of a wind turbine is defined as the transfer function from the frequency and magnitude of voltages at the POI to the active and reactive power output of the turbine. The power-domain admittance responses of the 4-MW wind turbine are measured using a 7-MVA grid simulator to identify the source of the reactive power oscillations. Power-domain impedance analysis and PHIL experiments are performed to explain how a resonant mode manifests as turbine-to-turbine and plant-to-grid reactive power oscillations. It is discovered that weaker grids exhibiting high inductive impedance mitigate oscillations in the reactive power output of wind power plants; however, a higher grid impedance does not help in damping turbine-to-turbine reactive power oscillations. This paper presents a simple droop-based solution to eliminate both turbine-to-turbine and plant-to-grid reactive power oscillations.

17 WIND ENERGY↗

PHIL Validation of Ultracapacitor Storage for Black Start Application

A deck of slides that present the modeling, and calibration to conduct PHIL test of ultracapacitor energy storage system. The PHIL test has been done while preparing for the black start field demonstration with Idaho Falls Power. Presentation is invited to the 6th International Workshop on Grid Simulator Testing of Wind Turbine Power Trains and Other Renewable Technologies.

13 HYDRO ENERGY↗

I2SL Phil Wirdzek Leadership Award

I’m nominating Shannon Blair from Los Alamos National Laboratory’s (LANL) Sustainability Program and Michael Moss from LANL’s Pollution Prevention Program for the Phil Wirdzek Leadership Award for their efforts in reducing sulfur hexafluoride (SF 6 ) emissions at LANL and creating a system of accounting for improved tracking of SF 6 emissions in the future.

12 MANAGEMENT OF RADIOACTIVE AND NON-RADIOACTIVE W↗

NREL CGI and PHIL Platform for Validation of Multi-Technology Energy Systems at Scale

The presentation is an update on National Renewable Energy Laboratory Flatirons Campus' capabilities around multi-megawatt grid simulation and power hardware-in-the-loop. Recent improvements in operational and dynamic range of existing 7MVA Controllable Grid Interface (CGI) are described together with improvements in site-wide automation and data acquisition systems. In later part of presentation, a second 19.9MVA CGI that is currently under development is introduced. Its features are described further explaining future site's capabilities.

acquisition↗

Commercial PV Inverter IEEE 1547.1 Ride-Through Assessments Using an Automated PHIL Test Platform

As more countries seek solutions to their de-carbonization targets using renewable energy (RE) technologies, interconnection standards and national grid codes for distributed energy resources (DER) are being updated to support higher penetrations of RE and improve grid stability. Common grid-code revisions mandate DER devices, such as solar inverters and energy storage systems, ride-through (RT) voltage and frequency disturbances. This is necessary because as the percentage of generation from DER increases, there is a greater risk power system faults will cause many or all DER to trip, triggering a substantial load-generation imbalance and possible cascading blackout. This paper demonstrates for the first time a methodology to verify commercial DER devices are compliant to new voltage, frequency, and rate of change of frequency (ROCOF) RT requirements established in IEEE Std. 1547-2018. The methodology incorporates a software automation tool, called the SunSpec System Validation Platform (SVP), in combination with a hardware-in-the-loop (HIL) system to execute the IEEE Std. 1547.1-2020 RT test protocols. In this paper, the approach is validated with two commercial photovoltaic inverters, the test results are analyzed for compliance, and improvements to the test procedure are suggested.

14 SOLAR ENERGY↗

Network Reduction for Power Hardware-in-the-Loop (PHIL) Simulation

This paper proposes single-port equivalent and two-port equivalent network reduction methods to respectively reduce single-port and two-port areas in a large power network. Parameters of the reduced systems are rigorously derived, which guarantees that the electrical quantities at the port(s) remain unchanged over the reduction, including voltage magnitude and phase and active and reactive power injections into the area to be reduced. The proposed techniques are applied to reduce a practical Maui grid, where the total numbers of buses, lines and transformers are respectively reduced from 212, 106 and 108 to 45, 30 and 13. Dynamic behaviors between the full model and the reduced model are compared in detail to illustrate the efficacy and accuracy of the proposed network reduction.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Modeling and Feedback Compensator Design for Power-Hardware-in-the-Loop System for Medium-Voltage Grid-Connected Power Converters

Hardware-in-the-loop (HIL) evaluation is a method in which the test subject is split into a physical part and a simulated part, and these parts are connected with interfaces to form a combined physical-numerical system. Power-hardware-in-the-loop (PHIL) systems, where actual hardware is connected to a real-time model, can exhibit issues of instability, inaccuracy and errors when operating in a closed-loop. The challenges of generating a PHIL setup are that, first, because of the limited dynamic response of the different parts of the system, the test results might be inaccurate, and, second, because of the high frequency noise introduced by the sensors to the closed-loop system, it can be difficult to design a compensator for the real-time emulator response, while stabilizing the closed-loop system at the same time. In this paper, different parts of a PHIL system are characterized, and the feedback compensator system design is proposed for the stable operation of the closed-loop PHIL system. The issues as observed in a PHIL system without any compensator are demonstrated using experimental results, and the effectiveness of a first order phase lead compensator is validated.

compensator design↗

Systematic Characterization of Power Hardware-in-the-Loop Evaluation Platform Stability: Preprint

This paper presents a systematic approach to characterize the stability of a power-hardware-in-the-loop (PHIL) platform, an important step in PHIL tests. Many existing works focus the stability assessments on the PHIL interface algorithm; however, this work considers all software and hardware subsystems that form the closed loop of the PHIL experiment and develops a complete closed-loop stability assessment. This assessment is developed in the context of a common framework that can be readily applied to other PHIL platforms. This paper presents methods for characterizing key PHIL subsystems toward obtaining transfer functions to be used for analysis. The systematic stability assessment approach is demonstrated for a case study involving PHIL testing of a solar inverter and validated using experimental data. assessment. This assessment is developed in the context of a common framework that can be readily applied to other PHIL platforms. This paper presents methods for characterizing key PHIL subsystems toward obtaining transfer functions to be used for analysis. The systematic stability assessment approach is demonstrated for a case study involving PHIL testing of a solar inverter and validated using experimental data.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Advanced Power-Hardware-in-the-Loop Evaluation of Inverter-Based Resources (IBRs)

Power-hardware-in-the-loop evaluation of IBRs has become more and more important as it provides reliable testing results to investigate the real responses of inverters with interconnected systems. A successful laboratory PHIL testing gives confidence of the hardware system to be deployed and de-risk technology integration prior to field deployment. So far, there are two important applications for PHIL evaluation: (1) test stability and functionality of large utility inverters into the system when it interconnects to the distribution systems/microgrids; and (2) test the collective grid service that inverters can provide to the grid. For the first application, the PHIL evaluation has high requirements for the stability and accuracy of the PHIL interface as the close-loop in digital real time simulator (DRTS) should replicate the actual current and voltage dynamics in the inverter. This is challenging because of the delays, sensing errors, nonlinearities of inverters, and hardware bandwidth limitations of the elements in the HIL loop. For the second application, multiple inverters will be tested resulting in multiple PCCs, which naturally causes competing dynamics and oscillations among hardware inverters if traditional PHIL interface is used. Therefore, new PHIL interface should be developed to compromise between stability and accuracy and represent the dispatched grid services for the hardware inverters. In this presentation, we will share our latest work in developing PHIL interface in these two applications to address the two key challenges.

DERMS↗

A Novel Power-Hardware-in-the-Loop Interface Method for Grid-forming Inverter Systems: Preprint

Power Hardware-in-the-Loop (PHIL) simulation of grid-forming (GFM) inverter systems facilitates the testing of drastic scenarios like on-grid to off-grid transition, islanded microgrid operation without stiff grid etc. To the authors best knowledge, most of studies in literature are focused on PHIL simulation for grid-following inverter systems and only few studies are focused on GFM inverters and those are challenging and problematic especially for high-power applications. In this article, a novel PHIL simulation platform is proposed that enables interfacing of high-power GFM inverter systems. It proposes the concept of a virtual GFM inverter as a part of the proposed PHIL interface for GFM inverter. This addition of virtual GFM inverter in the PHIL interface expands the conventional Ideal Transformer Model (ITM) method and enables it to overcome the issues of instability of existing ITM methods. In the validation stage, a PHIL experiment is conducted on a 3-phase 480 V, 125 kVA GFM inverter system with proposed interfacing method. The results corroborates the fact that the proposed PHIL simulation method performs well and stable for GFM inverter system.

grid-forming inverters↗

Novel Power-Hardware-in-the-Loop Interface Method for Grid-Forming Inverter Systems

Power-hardware-in-the-loop (PHIL) simulations of grid-forming (GFM) inverter systems facilitate the testing of drastic scenarios, such as on-grid to off-grid transitions and islanded microgrid operations without a stiff grid. To the authors’ best knowledge, most studies in the literature focus on PHIL simulations for grid-following inverter systems. Only a few studies focus on GFM inverters, and those are challenging and problematic, especially for high-power applications. This article proposes a novel PHIL simulation platform that enables interfacing high-power GFM inverter systems. The paper proposes the concept of a virtual GFM inverter as a part of the proposed PHIL interface. This addition of a virtual GFM inverter in the PHIL interface expands the conventional ideal transformer model (ITM) method and enables it to overcome the issues of instability of existing ITM methods. In the validation stage, a PHIL experiment is conducted on a three-phase, 480-V, 125-kVA GFM inverter system with the proposed interfacing method. The results corroborate that the proposed PHIL simulation method performs well and is stable for GFM inverter systems.

droop control↗

Optimal Power Hardware-in-the-Loop Interfacing: Applying Modern Control For Design and Verification of High-Accuracy Interfaces

Here, we develop a novel approach to designing power hardware-in-the-loop (PHIL) simulation interfaces that maximizes simulation bandwidth and accuracy by leveraging a modern control framework that explicitly considers objectives on accuracy and can automatically synthesize an optimal controller that meets these objectives while stabilizing the closed-loop system. The method developed improves upon common approaches to PHIL interface design that typically involve multiple design steps for manual compensation and stabilization design that can result in interfaces that are stable but have suboptimal bandwidth and accuracy. The approach developed is general and can be applied to most PHIL system configurations. The modeling framework allows for the inclusion of scaling factors and hardware-under-test current injection models that are common to practical PHIL simulations and have significant impacts on stability. We also present practical methods and metrics for verifying the absolute accuracy of PHIL simulation results without relying on relative comparisons to potentially inaccurate models or previous simulation results. We demonstrate the accuracy evaluation method and show the improved performance achievable when using the optimal PHIL interface design approach in an experimental case study involving a 100-kVA battery inverter.

42 ENGINEERING↗